Communications via BACnet

 

 

Chapter 8 Communications via BACnet

What is in this chapter?

This chapter contains the following sections:

BACnet communications overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 BACnet protocol support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 BACnet communications implementation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 BACnet object and property information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91

BACnet communications overview

Communications via BACnet MS/TP protocol is available on the iEM3165, iEM3265 and iEM3365.

The information in this section is intended for users with an advanced understanding of BACnet protocol, their communications network and their power system.

Key terms

Term

Definition

 

 

APDU

Application protocol data unit, that data portion of a BACnet message.

Confirmed message

A message for which the device expects an answer.

COV

Change of value, sets the amount by which a value has to change in order for the meter to send a

subscription notification.

 

 

A BACnet device is a unit that is designed to understand and use BACnet protocol (for example, a

Device

BACnet-enabled meter or software program). It contains information about the device and device

 

data in objects and object properties. Your meter is a BACnet device.

MS/TP

Master-slave/token-passing over RS-485.

Object

Represents the device and device data. Each object has a type (for example, analog input or binary

input) and has a number of properties.

 

Present value

The current value of an object.

 

 

Property

The smallest piece of information in BACnet communications, it consists of a name, data type and

value.

 

Service

Messages from one BACnet device to another.

 

 

 

Creates a relationship between the server and the meter, so that when the present value property

Subscription

of an object changes by more than the configured COV threshold (COV_Increment), a notification is

 

sent.

Subscription notification

The message the meter sends to indicate a COV event has occurred.

 

 

Unconfirmed message

A message for which the device does not expect an answer.

 

 

Related topics

See www.bacnet.org for more information on the BACnet protocol.

BACnet protocol support

Go to www.schneider-electric.com and search for your meter model to access the PICS (Protocol Implementation Conformance Statement) for your meter.

The meter supports the BACnet protocol as follows:

BACnet component

Description

 

 

Protocol version

1

 

 

Protocol revision

6

 

 

Standardized device profile (Annex L)

BACnet Application Specific Controller (B-ASC)

 

 

DOCA0005EN-04

89

Image 89
Contents IEM3100 / iEM3200 / iEM3300 series Page DOCA0005EN-04 Please note Safety informationImportant information FCC Part 15 notice Related documents About the bookDocument scope Validity noteContents Chapter Troubleshooting 103 Chapter SpecificationsChapter Power, energy and power factor 105 Chapter Communications via M-BusHazard of Electric SHOCK, EXPLOSION, or ARC Flash Safety precautionsSafety precautions DOCA0005EN-04 What is in this chapter? Main characteristicsChapter Overview Overview of meter functionsFunction Digital outputs Or overload alarm Pulse output only5 a meters IEM31 and iEM33 series Typical applicationsIEM32 series Typical applicationsOverview Dimensions Hardware and installationIEM31 and iEM32 meters IEM33 metersIEM3100 / iEM3110 / iEM3115 Direct measurement up to 63 a Hardware overviewAll meters Meter sealing points Digital input IEM3200 / iEM3210 / iEM3215 Measurement with CTs IEM3235 Measurement with CTs and M-Bus communications IEM3300 / iEM3310 Direct measurement up to 125 a IEM3275 Measurement with CTs and LonWorks communicationsDigital input iEM3355 / iEM3365 Mounting the meter on a DIN rail DIN rail mounting and dismountingDismounting the meter from a DIN rail Digital input wiring iEM3115 / iEM3215 Input, output and communications wiringPulse output wiring iEM3110 / iEM3210 / iEM3310 M-Bus communications connection is polarity-independent Bus communications wiring iEM3135 / iEM3235 / iEM3335LonWorks communications wiring iEM3175 / iEM3275 / iEM3375 Power system wiringVoltage input protection Current input protection for 1 a and 5 a metersFuses and disconnect switch Direct measurement meter wiringPower system IEMPower system Wiring Power system WiringMA fuses and disconnect switch Shorting block 1 a meter wiringSingle-phase systems with CTs Three-phase systems with CTs Three-phase systems with CTs and VTs Hardware and installation DOCA0005EN-04 1234.5 Front panel display and meter setupData display Data display screen overviewData display screens Example navigating the display screensData display screens iEM3150 / iEM3250 / iEM3350 Phase 3 CurrentMulti Tariff feature ResetsResetting accumulated energy using the display Reset DescriptionMeter status information Clock behavior on power interruptionDevice clock Date/time formatSetting the clock initially Device configurationEntering configuration mode Front panel display in configuration modeExample Configuring a list value Com. Protection settingModifying parameters Selecting a value from a listExample configuring a numeric value Configuration mode menusCanceling an entry 1PH2W L-L 1PH3W L-L-N Section Parameter Options DescriptionConfiguration menu for iEM3150 / iEM3350 Com.Protection Contrast Password Reset Config By Internal Clock Configuration menus for iEM3200 / iEM3210 / iEM3215 Configuration menus for iEM3250 Com.Protection 3PH3W 3PH4W Section Parameter Options Description Front panel display and meter setup DOCA0005EN-04 Communications LED indicator for Modbus devices Modbus communications settingsCommunications via Modbus RS-485 Modbus communication overviewFunction list Modbus functionsTable format Unit tableCommand interface overview Command interfaceCommand request Command resultCommand Action Size Type Unit Range Description Command listSet Date/Time Action Size Type Unit Range Description NumberSize Type Unit Range Description Set Pulse Output iEM3155 / iEM3255 / iEM3355Set Tariff iEM3155 / iEM3255 / iEM3355 Communications Setup Input Metering Setup iEM3155 / iEM3255 / iEM3355Overload Alarm Setup iEM3155 / iEM3255 / iEM3355 Reset Partial Energy Counters Meter Setup and StatusReset Input Metering Counter iEM3155 / iEM3255 / iEM3355 Modbus register listCommand Interface Energy Pulse Output Setup iEM3155 / iEM3255 / iEM3355Input Metering Setup iEM3155 / iEM3255 / iEM3355 CommunicationDigital Input iEM3155 / iEM3255 / iEM3355 Current, voltage, power, power factor and frequencyDigital Output iEM3155 / iEM3255 / iEM3355 Meter DataEnergy, energy by tariff and input metering Energy values 32-bit floating point Overload Alarm iEM3155 / iEM3255 / iEM3355Read Device Identification Object ID Name/Description Length Value Communications via LonWorks LED indicators for LonWorks metersLonWorks communications overview LonWorks communication implementationGeneral variables Location of the service pin and Neuron IDSystem variables Green communications LEDType Description Energy and energy by tariff measurementsInstantaneous RMS measurements Digital input configuration and status information System configuration informationAlarm status Meter status informationResets Meter configuration propertiesDate/time setup Network variable label Type Description ActionDigital input setup Basic setupInput metering setup Struct Members Range / options DescriptionMulti Tariff setup Overload alarm setupNetwork propagation rate setup Range / options DescriptionInstalling and registering the LonMaker plug-in LonMaker plug-in interface Browsing the meter using the LonMaker plug-inPlug-in has the following tabs Tab name DescriptionMeter Status Communications via LonWorks DOCA0005EN-04 Communications via M-Bus Configuring basic communications settingsBus communications overview Key termsBus protocol implementation Bus protocol supportData record header information Variable data structure telegram informationFixed data header Description Bin Hex Manufacturer-specific Vife codesMeter information Telegram information for data recordsBin Hex Primary VIF Primary VifeDate and time information Instantaneous measurementsData format Data format Primary VIFData format Primary Vife Power system configuration informationDigital input and output status information Alarm status information Telegram information for meter configurationSupported Vife codes for meter configuration Action Description Bin HexPower system setup Date/time setupMulti Tariff setup Data format Primary VIF DescriptionDigital output setup Digital input setupOverload alarm setup and acknowledgment Baud rateInstalling the M-Bus tool Bus tool for data display and meter configurationAccessing the meter using the tool ResetsViewing meter data using the M-Bus tool Section Description Configuring the meter using the M-Bus toolSelect Setup Config to switch to configuration mode Communications via M-Bus DOCA0005EN-04 BACnet communications overview Communications via BACnetBACnet protocol support Related topicsBACnet communications implementation Configuring basic communication parametersFollowing standard object types are supported Object typeBACnet object and property information Communications LED indicator for BACnet metersChange of Value COV subscriptions Device objectEnergy and energy by tariff measurements Object ID Units Default COV Object name / descriptionAnalog Input objects Meter information Instantaneous RMS measurementsDigital input and output setting information Communications settings informationAnalog Value object CommandBinary Input objects Object ID Object name / descriptionCommunications via BACnet DOCA0005EN-04 Electrical characteristics Chapter SpecificationsPower system inputs iEM31 meters Power system inputs iEM33 metersInputs and outputs Power system inputs iEM32 metersCharacteristic Value Meters Measurement accuracy Mechanical characteristicsEnvironmental characteristics LonWorks communications Internal clockModbus communications BACnet communications Bus communicationsSpecifications 102 DOCA0005EN-04 Do not open the meter. Opening the meter voids the warranty TroubleshootingDiagnosis screen lists any current diagnostic codes Diagnosis screenDescription Possible solution Diagnostic codesPower PQS Power, energy and power factorPower and the PQ coordinate system Power flowTrue PF and displacement PF Power factor PFEnergy delivered imported / energy received exported PF lead / lag conventionPF sign convention Power and PF lead / lagPF lead / lag summary PF sign in IECTo +1 Power factor register formatQuadrant To +1 +1 to +2PF formula Quadrant PF rangePower, energy and power factor 110 DOCA0005EN-04 Page Schneider Electric 35, rue Joseph Monier CS30323