Schneider Electric iEM3200 Read Device Identification, Overload Alarm iEM3155 / iEM3255 / iEM3355

Page 61

iEM3100 / iEM3200 / iEM3300 series user manual

 

 

 

Communications via Modbus RS-485

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Energy values – 32-bit floating point

 

 

 

 

 

 

 

 

Register

Action

Size

Type

Units

Description

 

Address

(R/W/WC)

 

 

 

 

 

 

 

 

Total Energy (cannot be reset)

 

 

 

 

 

 

 

 

 

 

45100

R

2

Float32

Wh

Total Active Energy Import

 

 

 

 

 

 

 

 

45102

R

2

Float32

Wh

Total Active Energy Export

 

Not applicable for iEM3150 / iEM3250 / iEM3350

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45104

R

2

Float32

VARh

Total Reactive Energy Import

 

Not applicable for iEM3150 / iEM3250 / iEM3350

 

 

 

 

 

 

 

45106

R

2

Float32

VARh

Total Reactive Energy Export

 

Not applicable for iEM3150 / iEM3250 / iEM3350

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Partial Energy

 

 

 

 

 

 

 

 

 

 

 

 

45108

R

2

Float32

Wh

Partial Active Energy Import

 

45110

R

2

Float32

VARh

Partial Reactive Energy Import

 

Not applicable for iEM3150 / iEM3250 / iEM3350

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Phase Energy

 

 

 

 

 

 

 

 

 

 

 

 

45112

R

2

Float32

Wh

Active Energy Import Phase 1

 

45114

R

2

Float32

Wh

Active Energy Import Phase 2

 

45116

R

2

Float32

Wh

Active Energy Import Phase 3

 

Input Metering Counter

 

 

 

 

 

 

 

 

 

 

 

45118

R

2

Float32

Unit

Input Metering Accumulation

 

Not applicable for iEM3150 / iEM3250 / iEM3350

 

 

 

 

 

 

 

Energy by Tariff (iEM3155 / iEM3255 / iEM3355 only)

 

 

 

 

 

 

 

 

45120

R

2

Float32

Wh

Rate A Active Energy Import

 

 

 

 

 

 

 

 

45122

R

2

Float32

Wh

Rate B Active Energy Import

 

 

 

 

 

 

 

 

45124

R

2

Float32

Wh

Rate C Active Energy Import

 

 

 

 

 

 

 

 

45126

R

2

Float32

Wh

Rate D Active Energy Import

 

 

 

 

 

 

 

 

Overload Alarm (iEM3155 / iEM3255 / iEM3355)

 

 

 

 

 

 

 

 

Register

Action

Size

Type

Units

Description

 

Address

(R/W/WC)

 

 

 

 

 

 

Overload Alarm Setup:

 

45001

R/WC

1

Bitmap

0x0000 = Disabled

 

 

 

 

 

 

0x0100 = Enabled

 

45002

R/WC

2

Float32

kW

Pickup Setpoint

 

 

 

 

 

 

Digital Output to Associate:

 

45004

R/WC

1

Bitmap

0x0000 = Digital Output unassociated to overload alarm

 

 

 

 

 

 

0x0100 = Digital Output associated to overload alarm

 

 

 

 

 

 

Activated Status:

 

45005

R

1

Bitmap

0x0000 = Alarm is inactive

 

 

 

 

 

 

0x0100 = Alarm is active

 

 

 

 

 

 

Unacknowledged Status:

 

45006

R

1

Bitmap

0x0000 = Historic alarm is acknowledged by the user

 

 

 

 

 

 

0x0100 = Historic alarm is unacknowledged by the user

 

45007

R

4

DATETIME

Last Alarm - Time Stamp

 

45011

R

2

Float32

kW

Last Alarm - Value

 

 

 

 

 

 

 

Read Device Identification

The meters supports the Read Device Identification function with the mandatory objects

VendorName, ProductCode and Revision Number.

DOCA0005EN-04

61

Image 61
Contents IEM3100 / iEM3200 / iEM3300 series Page DOCA0005EN-04 Important information Safety informationPlease note FCC Part 15 notice Related documents About the bookDocument scope Validity noteContents Chapter Troubleshooting 103 Chapter SpecificationsChapter Power, energy and power factor 105 Chapter Communications via M-BusHazard of Electric SHOCK, EXPLOSION, or ARC Flash Safety precautionsSafety precautions DOCA0005EN-04 What is in this chapter? Main characteristicsChapter Overview Overview of meter functions5 a meters Digital outputs Or overload alarm Pulse output onlyFunction IEM31 and iEM33 series Typical applicationsIEM32 series Typical applicationsOverview Dimensions Hardware and installationIEM31 and iEM32 meters IEM33 metersAll meters Meter sealing points Hardware overviewIEM3100 / iEM3110 / iEM3115 Direct measurement up to 63 a Digital input IEM3200 / iEM3210 / iEM3215 Measurement with CTs IEM3235 Measurement with CTs and M-Bus communications IEM3300 / iEM3310 Direct measurement up to 125 a IEM3275 Measurement with CTs and LonWorks communicationsDigital input iEM3355 / iEM3365 Mounting the meter on a DIN rail DIN rail mounting and dismountingDismounting the meter from a DIN rail Pulse output wiring iEM3110 / iEM3210 / iEM3310 Input, output and communications wiringDigital input wiring iEM3115 / iEM3215 M-Bus communications connection is polarity-independent Bus communications wiring iEM3135 / iEM3235 / iEM3335LonWorks communications wiring iEM3175 / iEM3275 / iEM3375 Power system wiringVoltage input protection Current input protection for 1 a and 5 a metersFuses and disconnect switch Direct measurement meter wiringPower system IEMPower system Wiring Power system WiringSingle-phase systems with CTs 1 a meter wiringMA fuses and disconnect switch Shorting block Three-phase systems with CTs Three-phase systems with CTs and VTs Hardware and installation DOCA0005EN-04 1234.5 Front panel display and meter setupData display Data display screen overviewData display screens Example navigating the display screensData display screens iEM3150 / iEM3250 / iEM3350 Phase 3 CurrentMulti Tariff feature ResetsResetting accumulated energy using the display Reset DescriptionMeter status information Clock behavior on power interruptionDevice clock Date/time formatSetting the clock initially Device configurationEntering configuration mode Front panel display in configuration modeExample Configuring a list value Com. Protection settingModifying parameters Selecting a value from a listCanceling an entry Configuration mode menusExample configuring a numeric value 1PH2W L-L 1PH3W L-L-N Section Parameter Options DescriptionConfiguration menu for iEM3150 / iEM3350 Com.Protection Contrast Password Reset Config By Internal Clock Configuration menus for iEM3200 / iEM3210 / iEM3215 Configuration menus for iEM3250 Com.Protection 3PH3W 3PH4W Section Parameter Options Description Front panel display and meter setup DOCA0005EN-04 Communications LED indicator for Modbus devices Modbus communications settingsCommunications via Modbus RS-485 Modbus communication overviewFunction list Modbus functionsTable format Unit tableCommand interface overview Command interfaceCommand request Command resultCommand Action Size Type Unit Range Description Command listSet Date/Time Action Size Type Unit Range Description NumberSet Tariff iEM3155 / iEM3255 / iEM3355 Set Pulse Output iEM3155 / iEM3255 / iEM3355Size Type Unit Range Description Overload Alarm Setup iEM3155 / iEM3255 / iEM3355 Input Metering Setup iEM3155 / iEM3255 / iEM3355Communications Setup Reset Partial Energy Counters Meter Setup and StatusReset Input Metering Counter iEM3155 / iEM3255 / iEM3355 Modbus register listCommand Interface Energy Pulse Output Setup iEM3155 / iEM3255 / iEM3355Input Metering Setup iEM3155 / iEM3255 / iEM3355 CommunicationDigital Input iEM3155 / iEM3255 / iEM3355 Current, voltage, power, power factor and frequencyDigital Output iEM3155 / iEM3255 / iEM3355 Meter DataEnergy, energy by tariff and input metering Read Device Identification Overload Alarm iEM3155 / iEM3255 / iEM3355Energy values 32-bit floating point Object ID Name/Description Length Value Communications via LonWorks LED indicators for LonWorks metersLonWorks communications overview LonWorks communication implementationGeneral variables Location of the service pin and Neuron IDSystem variables Green communications LEDType Description Energy and energy by tariff measurementsInstantaneous RMS measurements Digital input configuration and status information System configuration informationAlarm status Meter status informationResets Meter configuration propertiesDate/time setup Network variable label Type Description ActionDigital input setup Basic setupInput metering setup Struct Members Range / options DescriptionMulti Tariff setup Overload alarm setupNetwork propagation rate setup Range / options DescriptionInstalling and registering the LonMaker plug-in LonMaker plug-in interface Browsing the meter using the LonMaker plug-inPlug-in has the following tabs Tab name DescriptionMeter Status Communications via LonWorks DOCA0005EN-04 Communications via M-Bus Configuring basic communications settingsBus communications overview Key termsBus protocol implementation Bus protocol supportFixed data header Variable data structure telegram informationData record header information Description Bin Hex Manufacturer-specific Vife codesMeter information Telegram information for data recordsBin Hex Primary VIF Primary VifeDate and time information Instantaneous measurementsData format Data format Primary VIFDigital input and output status information Power system configuration informationData format Primary Vife Alarm status information Telegram information for meter configurationSupported Vife codes for meter configuration Action Description Bin HexPower system setup Date/time setupMulti Tariff setup Data format Primary VIF DescriptionDigital output setup Digital input setupOverload alarm setup and acknowledgment Baud rateInstalling the M-Bus tool Bus tool for data display and meter configurationAccessing the meter using the tool ResetsViewing meter data using the M-Bus tool Select Setup Config to switch to configuration mode Configuring the meter using the M-Bus toolSection Description Communications via M-Bus DOCA0005EN-04 BACnet communications overview Communications via BACnetBACnet protocol support Related topicsBACnet communications implementation Configuring basic communication parametersFollowing standard object types are supported Object typeBACnet object and property information Communications LED indicator for BACnet metersChange of Value COV subscriptions Device objectAnalog Input objects Object ID Units Default COV Object name / descriptionEnergy and energy by tariff measurements Meter information Instantaneous RMS measurementsDigital input and output setting information Communications settings informationAnalog Value object CommandBinary Input objects Object ID Object name / descriptionCommunications via BACnet DOCA0005EN-04 Electrical characteristics Chapter SpecificationsPower system inputs iEM31 meters Power system inputs iEM33 metersCharacteristic Value Meters Power system inputs iEM32 metersInputs and outputs Environmental characteristics Mechanical characteristicsMeasurement accuracy Modbus communications Internal clockLonWorks communications BACnet communications Bus communicationsSpecifications 102 DOCA0005EN-04 Do not open the meter. Opening the meter voids the warranty TroubleshootingDiagnosis screen lists any current diagnostic codes Diagnosis screenDescription Possible solution Diagnostic codesPower PQS Power, energy and power factorPower and the PQ coordinate system Power flowTrue PF and displacement PF Power factor PFEnergy delivered imported / energy received exported PF lead / lag conventionPF sign convention Power and PF lead / lagPF lead / lag summary PF sign in IECTo +1 Power factor register formatQuadrant To +1 +1 to +2PF formula Quadrant PF rangePower, energy and power factor 110 DOCA0005EN-04 Page Schneider Electric 35, rue Joseph Monier CS30323