Page 41

iEM3100 / iEM3200 / iEM3300 series user manual

Front panel display and meter setup

 

 

Configuration menu for iEM3100 / iEM3110 / iEM3115 / iEM3300 / iEM3310

Wiring

 

 

Type

 

 

 

 

 

Frequency

 

 

 

Frequency

 

 

 

 

 

 

 

Date

 

 

 

Date

 

 

 

 

 

 

 

Time

 

 

 

Time

 

 

 

 

 

 

 

Pulse Output

 

 

Pulse Constant

 

 

 

 

 

 

 

 

 

 

Pulse Width

 

 

Multi Tariffs

 

 

Control mode

 

 

 

 

 

 

 

 

 

 

Disable

 

 

 

 

 

 

by Internal Clock

 

Schedule

 

 

 

 

 

 

 

 

 

by Digital Input

 

by 2 Tariffs

 

 

 

 

by Communications

 

by 3 Tariffs

 

 

 

 

 

 

by 4 Tariffs

Contrast

 

 

 

Contrast

 

 

 

 

 

 

 

AiEM3110 / iEM3115 / iEM3310

BiEM3110 / iEM3310

CiEM3115

Password

 

Password

 

Reset Config

 

Reset Config

 

Section

Parameter

Options

Description

 

 

 

 

 

 

3PH3W

 

 

 

3PH4W

 

Wiring

Type

1PH2W L-N

Select the power system type the meter is wired to.

 

 

1PH2W L-L

 

 

 

1PH3W L-L-N

 

 

 

 

 

Frequency

Frequency

50

Select the frequency of the electrical power system, in Hz.

60

 

 

 

Date (iEM3110 / iEM3115 /

Date

DD-MMM-YYYY

Set the current date using the specified format.

iEM3310)

 

 

 

Time (iEM3110 / iEM3115 /

Time

hh:mm

Use the 24-hour format to set the time.

iEM3310)

 

 

 

 

 

100

 

 

 

200

 

 

Pulse Constant

1000

Set the pulses per kWh for the pulse output.

 

(imp/kWh)

1

 

 

Pulse Output

 

10

 

 

20

 

 

 

 

 

 

50

 

 

Pulse Width

100

Set the pulse width (ON time).

 

(ms)

200

 

 

 

 

300

 

 

 

 

Select the tariff control mode:

 

 

 

• Disable: the Multi Tariff function is disabled.

 

 

Disable

• by Digital Input: the digital input is associated with the multi-tariff function. A

 

 

signal to the digital input changes the active tariff.

Multi Tariffs (iEM3115)

Control Mode

by Digital Input

• by Internal Clock: the device clock controls the active tariff. If you set the

 

 

by Internal Clock

Control Mode to by Internal Clock, you must also configure the schedule.

 

 

 

Set the time when each tariff period starts, using the 24 hour clock format

 

 

 

(00:00 to 23:59). The start time of the next tariff is the end time of the current

 

 

 

tariff. For example, T2 start equals the end of T1.

Contrast

Contrast

1-9

Increase or decrease the value to increase or decrease the display contrast.

Password

 

 

 

(iEM3110 / iEM3115 /

Password

0-9999

Sets the password for accessing the meter configuration screens and resets.

iEM3310)

 

 

 

Reset Config

Reset Config

Settings are reset to their defaults, except for Password. Meter restarts.

 

 

 

 

DOCA0005EN-04

41

Image 41
Contents IEM3100 / iEM3200 / iEM3300 series Page DOCA0005EN-04 Please note Safety informationImportant information FCC Part 15 notice Related documents About the bookDocument scope Validity noteContents Chapter Troubleshooting 103 Chapter SpecificationsChapter Power, energy and power factor 105 Chapter Communications via M-BusHazard of Electric SHOCK, EXPLOSION, or ARC Flash Safety precautionsSafety precautions DOCA0005EN-04 What is in this chapter? Main characteristicsChapter Overview Overview of meter functionsFunction Digital outputs Or overload alarm Pulse output only5 a meters IEM31 and iEM33 series Typical applicationsIEM32 series Typical applicationsOverview Dimensions Hardware and installationIEM31 and iEM32 meters IEM33 metersIEM3100 / iEM3110 / iEM3115 Direct measurement up to 63 a Hardware overviewAll meters Meter sealing points Digital input IEM3200 / iEM3210 / iEM3215 Measurement with CTs IEM3235 Measurement with CTs and M-Bus communications IEM3300 / iEM3310 Direct measurement up to 125 a IEM3275 Measurement with CTs and LonWorks communicationsDigital input iEM3355 / iEM3365 Mounting the meter on a DIN rail DIN rail mounting and dismountingDismounting the meter from a DIN rail Digital input wiring iEM3115 / iEM3215 Input, output and communications wiringPulse output wiring iEM3110 / iEM3210 / iEM3310 M-Bus communications connection is polarity-independent Bus communications wiring iEM3135 / iEM3235 / iEM3335LonWorks communications wiring iEM3175 / iEM3275 / iEM3375 Power system wiringVoltage input protection Current input protection for 1 a and 5 a metersFuses and disconnect switch Direct measurement meter wiringPower system IEMPower system Wiring Power system WiringMA fuses and disconnect switch Shorting block 1 a meter wiringSingle-phase systems with CTs Three-phase systems with CTs Three-phase systems with CTs and VTs Hardware and installation DOCA0005EN-04 1234.5 Front panel display and meter setupData display Data display screen overviewData display screens Example navigating the display screensData display screens iEM3150 / iEM3250 / iEM3350 Phase 3 CurrentMulti Tariff feature ResetsResetting accumulated energy using the display Reset DescriptionMeter status information Clock behavior on power interruptionDevice clock Date/time format Setting the clock initially Device configuration Entering configuration mode Front panel display in configuration modeExample Configuring a list value Com. Protection settingModifying parameters Selecting a value from a listExample configuring a numeric value Configuration mode menusCanceling an entry 1PH2W L-L 1PH3W L-L-N Section Parameter Options DescriptionConfiguration menu for iEM3150 / iEM3350 Com.Protection Contrast Password Reset Config By Internal Clock Configuration menus for iEM3200 / iEM3210 / iEM3215 Configuration menus for iEM3250 Com.Protection 3PH3W 3PH4W Section Parameter Options Description Front panel display and meter setup DOCA0005EN-04 Communications LED indicator for Modbus devices Modbus communications settingsCommunications via Modbus RS-485 Modbus communication overviewFunction list Modbus functionsTable format Unit tableCommand interface overview Command interfaceCommand request Command resultCommand Action Size Type Unit Range Description Command listSet Date/Time Action Size Type Unit Range Description NumberSize Type Unit Range Description Set Pulse Output iEM3155 / iEM3255 / iEM3355Set Tariff iEM3155 / iEM3255 / iEM3355 Communications Setup Input Metering Setup iEM3155 / iEM3255 / iEM3355Overload Alarm Setup iEM3155 / iEM3255 / iEM3355 Reset Partial Energy Counters Meter Setup and StatusReset Input Metering Counter iEM3155 / iEM3255 / iEM3355 Modbus register listCommand Interface Energy Pulse Output Setup iEM3155 / iEM3255 / iEM3355Input Metering Setup iEM3155 / iEM3255 / iEM3355 CommunicationDigital Input iEM3155 / iEM3255 / iEM3355 Current, voltage, power, power factor and frequencyDigital Output iEM3155 / iEM3255 / iEM3355 Meter DataEnergy, energy by tariff and input metering Energy values 32-bit floating point Overload Alarm iEM3155 / iEM3255 / iEM3355Read Device Identification Object ID Name/Description Length Value Communications via LonWorks LED indicators for LonWorks metersLonWorks communications overview LonWorks communication implementationGeneral variables Location of the service pin and Neuron IDSystem variables Green communications LEDType Description Energy and energy by tariff measurementsInstantaneous RMS measurements Digital input configuration and status information System configuration informationAlarm status Meter status informationResets Meter configuration propertiesDate/time setup Network variable label Type Description ActionDigital input setup Basic setupInput metering setup Struct Members Range / options DescriptionMulti Tariff setup Overload alarm setupNetwork propagation rate setup Range / options DescriptionInstalling and registering the LonMaker plug-in LonMaker plug-in interface Browsing the meter using the LonMaker plug-inPlug-in has the following tabs Tab name DescriptionMeter Status Communications via LonWorks DOCA0005EN-04 Communications via M-Bus Configuring basic communications settingsBus communications overview Key termsBus protocol implementation Bus protocol supportData record header information Variable data structure telegram informationFixed data header Description Bin Hex Manufacturer-specific Vife codesMeter information Telegram information for data recordsBin Hex Primary VIF Primary VifeDate and time information Instantaneous measurementsData format Data format Primary VIFData format Primary Vife Power system configuration informationDigital input and output status information Alarm status information Telegram information for meter configurationSupported Vife codes for meter configuration Action Description Bin HexPower system setup Date/time setupMulti Tariff setup Data format Primary VIF DescriptionDigital output setup Digital input setupOverload alarm setup and acknowledgment Baud rateInstalling the M-Bus tool Bus tool for data display and meter configurationAccessing the meter using the tool ResetsViewing meter data using the M-Bus tool Section Description Configuring the meter using the M-Bus toolSelect Setup Config to switch to configuration mode Communications via M-Bus DOCA0005EN-04 BACnet communications overview Communications via BACnetBACnet protocol support Related topicsBACnet communications implementation Configuring basic communication parametersFollowing standard object types are supported Object typeBACnet object and property information Communications LED indicator for BACnet metersChange of Value COV subscriptions Device objectEnergy and energy by tariff measurements Object ID Units Default COV Object name / descriptionAnalog Input objects Meter information Instantaneous RMS measurementsDigital input and output setting information Communications settings informationAnalog Value object CommandBinary Input objects Object ID Object name / descriptionCommunications via BACnet DOCA0005EN-04 Electrical characteristics Chapter SpecificationsPower system inputs iEM31 meters Power system inputs iEM33 metersInputs and outputs Power system inputs iEM32 metersCharacteristic Value Meters Measurement accuracy Mechanical characteristicsEnvironmental characteristics LonWorks communications Internal clockModbus communications BACnet communications Bus communicationsSpecifications 102 DOCA0005EN-04 Do not open the meter. Opening the meter voids the warranty TroubleshootingDiagnosis screen lists any current diagnostic codes Diagnosis screenDescription Possible solution Diagnostic codesPower PQS Power, energy and power factorPower and the PQ coordinate system Power flowTrue PF and displacement PF Power factor PFEnergy delivered imported / energy received exported PF lead / lag conventionPF sign convention Power and PF lead / lagPF lead / lag summary PF sign in IECTo +1 Power factor register formatQuadrant To +1 +1 to +2PF formula Quadrant PF rangePower, energy and power factor 110 DOCA0005EN-04 Page Schneider Electric 35, rue Joseph Monier CS30323