Schneider Electric iEM3300, iEM3200, iEM3100 user manual Energy, energy by tariff and input metering

Page 60

Communications via Modbus RS-485

 

 

 

 

iEM3100 / iEM3200 / iEM3300 series user manual

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Register

Action

Size

Type

Units

Description

 

Address

(R/W/WC)

 

 

 

 

 

 

 

 

Power Factor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total Power Factor:

 

 

 

 

 

 

-2 < PF < -1 = Quad 2, active power negative, capacitive

 

3084

R

2

Float32

-1 < PF < 0 = Quad 3, active power negative, inductive

 

 

 

 

 

 

0 < PF < 1 = Quad 1, active power positive, inductive

 

 

 

 

 

 

1 < PF < 2 = Quad 4, active power positive, capacitive

 

 

 

 

 

 

 

 

Frequency

 

 

 

 

 

 

 

 

 

 

 

 

3110

R

2

Float32

Hz

Frequency

Energy, energy by tariff and input metering

Most energy values are available in both signed 64-bit integer and 32-bit floating point format. The energy and energy by tariff measurements listed below are preserved through power failures.

Energy reset and active tariff information

Register

Action

Size

Type

Units

Description

Address

(R/W/WC)

 

 

 

 

 

 

3252

R

4

DATETIME

Energy Reset Date and Time

 

 

 

 

 

 

3554

R

4

DATETIME

Input Metering Accumulation Reset Date and Time

Not applicable for iEM3150 / iEM3250 / iEM3350

 

 

 

 

 

 

 

 

 

 

MultiTariffs Energy Active Rate

 

 

 

 

 

0: multi tariff disabled

4191

R/WC

1

UInt16

1 to 4: rate A to rate D

Not applicable for iEM3150 / iEM3250 / iEM3350

 

 

 

 

 

 

 

 

 

 

NOTE: You can only set the tariff using this method if the Tariff Mode

 

 

 

 

 

is set to by Communication.

Energy values – 64-bit integer

Register

Action

Size

Type

Units

Description

Address

(R/W/WC)

 

 

 

 

 

 

Total Energy (cannot be reset)

 

 

 

 

 

 

 

 

3204

R

4

Int64

Wh

Total Active Energy Import

3208

R

4

Int64

Wh

Total Active Energy Export

Not applicable for iEM3150 / iEM3250 / iEM3350

 

 

 

 

 

 

 

 

 

 

 

3220

R

4

Int64

VARh

Total Reactive Energy Import

Not applicable for iEM3150 / iEM3250 / iEM3350

 

 

 

 

 

 

 

 

 

 

 

3224

R

4

Int64

VARh

Total Reactive Energy Export

Not applicable for iEM3150 / iEM3250 / iEM3350

 

 

 

 

 

Partial Energy

 

 

 

 

 

 

 

 

 

 

3256

R

4

Int64

Wh

Partial Active Energy Import

 

 

 

 

 

 

3272

R

4

Int64

VARh

Partial Reactive Energy Import

Not applicable for iEM3150 / iEM3250 / iEM3350

 

 

 

 

 

Phase Energy

 

 

 

 

 

 

 

 

 

 

3518

R

4

Int64

Wh

Active Energy Import Phase 1

 

 

 

 

 

 

3522

R

4

Int64

Wh

Active Energy Import Phase 2

 

 

 

 

 

 

3526

R

4

Int64

Wh

Active Energy Import Phase 3

 

 

 

 

 

 

Input Metering Counter

 

 

 

 

 

 

 

 

 

3558

R

4

Int64

Unit

Input Metering Accumulation

Not applicable for iEM3150 / iEM3250 / iEM3350

 

 

 

 

 

 

 

 

 

 

 

Energy by Tariff (iEM3155 / iEM3255 / iEM3355 only)

 

 

 

 

 

 

4196

R

4

Int64

Wh

Rate A Active Energy Import

 

 

 

 

 

 

4200

R

4

Int64

Wh

Rate B Active Energy Import

 

 

 

 

 

 

4204

R

4

Int64

Wh

Rate C Active Energy Import

 

 

 

 

 

 

4208

R

4

Int64

Wh

Rate D Active Energy Import

 

 

 

 

 

 

60

DOCA0005EN-04

Image 60
Contents IEM3100 / iEM3200 / iEM3300 series Page DOCA0005EN-04 Safety information Important informationPlease note FCC Part 15 notice About the book Related documentsDocument scope Validity noteContents Chapter Specifications Chapter Troubleshooting 103Chapter Power, energy and power factor 105 Chapter Communications via M-BusSafety precautions Hazard of Electric SHOCK, EXPLOSION, or ARC FlashSafety precautions DOCA0005EN-04 Main characteristics What is in this chapter?Chapter Overview Overview of meter functionsDigital outputs Or overload alarm Pulse output only 5 a metersFunction Typical applications IEM31 and iEM33 seriesIEM32 series Typical applicationsOverview Hardware and installation DimensionsIEM31 and iEM32 meters IEM33 metersHardware overview All meters Meter sealing pointsIEM3100 / iEM3110 / iEM3115 Direct measurement up to 63 a Digital input IEM3200 / iEM3210 / iEM3215 Measurement with CTs IEM3235 Measurement with CTs and M-Bus communications IEM3275 Measurement with CTs and LonWorks communications IEM3300 / iEM3310 Direct measurement up to 125 aDigital input iEM3355 / iEM3365 DIN rail mounting and dismounting Mounting the meter on a DIN railDismounting the meter from a DIN rail Input, output and communications wiring Pulse output wiring iEM3110 / iEM3210 / iEM3310Digital input wiring iEM3115 / iEM3215 Bus communications wiring iEM3135 / iEM3235 / iEM3335 M-Bus communications connection is polarity-independentPower system wiring LonWorks communications wiring iEM3175 / iEM3275 / iEM3375Voltage input protection Current input protection for 1 a and 5 a metersDirect measurement meter wiring Fuses and disconnect switchPower system IEMPower system Wiring Power system Wiring1 a meter wiring Single-phase systems with CTsMA fuses and disconnect switch Shorting block Three-phase systems with CTs Three-phase systems with CTs and VTs Hardware and installation DOCA0005EN-04 Front panel display and meter setup 1234.5Data display Data display screen overviewExample navigating the display screens Data display screensPhase 3 Current Data display screens iEM3150 / iEM3250 / iEM3350Resets Multi Tariff featureResetting accumulated energy using the display Reset DescriptionClock behavior on power interruption Meter status informationDevice clock Date/time formatDevice configuration Setting the clock initiallyEntering configuration mode Front panel display in configuration modeCom. Protection setting Example Configuring a list valueModifying parameters Selecting a value from a listConfiguration mode menus Canceling an entryExample configuring a numeric value Section Parameter Options Description 1PH2W L-L 1PH3W L-L-NConfiguration menu for iEM3150 / iEM3350 Com.Protection Contrast Password Reset Config By Internal Clock Configuration menus for iEM3200 / iEM3210 / iEM3215 Configuration menus for iEM3250 Com.Protection 3PH3W 3PH4W Section Parameter Options Description Front panel display and meter setup DOCA0005EN-04 Modbus communications settings Communications LED indicator for Modbus devicesCommunications via Modbus RS-485 Modbus communication overviewModbus functions Function listTable format Unit tableCommand interface Command interface overviewCommand request Command resultCommand list Command Action Size Type Unit Range DescriptionSet Date/Time Action Size Type Unit Range Description NumberSet Pulse Output iEM3155 / iEM3255 / iEM3355 Set Tariff iEM3155 / iEM3255 / iEM3355Size Type Unit Range Description Input Metering Setup iEM3155 / iEM3255 / iEM3355 Overload Alarm Setup iEM3155 / iEM3255 / iEM3355Communications Setup Meter Setup and Status Reset Partial Energy CountersReset Input Metering Counter iEM3155 / iEM3255 / iEM3355 Modbus register listEnergy Pulse Output Setup iEM3155 / iEM3255 / iEM3355 Command InterfaceInput Metering Setup iEM3155 / iEM3255 / iEM3355 CommunicationCurrent, voltage, power, power factor and frequency Digital Input iEM3155 / iEM3255 / iEM3355Digital Output iEM3155 / iEM3255 / iEM3355 Meter DataEnergy, energy by tariff and input metering Overload Alarm iEM3155 / iEM3255 / iEM3355 Read Device IdentificationEnergy values 32-bit floating point Object ID Name/Description Length Value LED indicators for LonWorks meters Communications via LonWorksLonWorks communications overview LonWorks communication implementationLocation of the service pin and Neuron ID General variablesSystem variables Green communications LEDEnergy and energy by tariff measurements Type DescriptionInstantaneous RMS measurements System configuration information Digital input configuration and status informationAlarm status Meter status informationMeter configuration properties ResetsDate/time setup Network variable label Type Description ActionBasic setup Digital input setupInput metering setup Struct Members Range / options DescriptionOverload alarm setup Multi Tariff setupNetwork propagation rate setup Range / options DescriptionInstalling and registering the LonMaker plug-in Browsing the meter using the LonMaker plug-in LonMaker plug-in interfacePlug-in has the following tabs Tab name DescriptionMeter Status Communications via LonWorks DOCA0005EN-04 Configuring basic communications settings Communications via M-BusBus communications overview Key termsBus protocol support Bus protocol implementationVariable data structure telegram information Fixed data headerData record header information Manufacturer-specific Vife codes Description Bin HexTelegram information for data records Meter informationBin Hex Primary VIF Primary VifeInstantaneous measurements Date and time informationData format Data format Primary VIFPower system configuration information Digital input and output status informationData format Primary Vife Telegram information for meter configuration Alarm status informationSupported Vife codes for meter configuration Action Description Bin HexDate/time setup Power system setupMulti Tariff setup Data format Primary VIF DescriptionDigital input setup Digital output setupOverload alarm setup and acknowledgment Baud rateBus tool for data display and meter configuration Installing the M-Bus toolAccessing the meter using the tool ResetsViewing meter data using the M-Bus tool Configuring the meter using the M-Bus tool Select Setup Config to switch to configuration modeSection Description Communications via M-Bus DOCA0005EN-04 Communications via BACnet BACnet communications overviewBACnet protocol support Related topicsConfiguring basic communication parameters BACnet communications implementationFollowing standard object types are supported Object typeCommunications LED indicator for BACnet meters BACnet object and property informationChange of Value COV subscriptions Device objectObject ID Units Default COV Object name / description Analog Input objectsEnergy and energy by tariff measurements Instantaneous RMS measurements Meter informationCommunications settings information Digital input and output setting informationCommand Analog Value objectBinary Input objects Object ID Object name / descriptionCommunications via BACnet DOCA0005EN-04 Chapter Specifications Electrical characteristicsPower system inputs iEM31 meters Power system inputs iEM33 metersPower system inputs iEM32 meters Characteristic Value MetersInputs and outputs Mechanical characteristics Environmental characteristicsMeasurement accuracy Internal clock Modbus communicationsLonWorks communications Bus communications BACnet communicationsSpecifications 102 DOCA0005EN-04 Troubleshooting Do not open the meter. Opening the meter voids the warrantyDiagnosis screen lists any current diagnostic codes Diagnosis screenDiagnostic codes Description Possible solutionPower, energy and power factor Power PQSPower and the PQ coordinate system Power flowPower factor PF True PF and displacement PFEnergy delivered imported / energy received exported PF lead / lag conventionPower and PF lead / lag PF sign conventionPF lead / lag summary PF sign in IECPower factor register format To +1Quadrant To +1 +1 to +2Quadrant PF range PF formulaPower, energy and power factor 110 DOCA0005EN-04 Page Schneider Electric 35, rue Joseph Monier CS30323