Designer Series Gas Fireplaces

ventING installation

termination clearances for buildings with combustible and noncombustible exteriors

G G=6" (152mm)

V

Inside Corner

G

V

G = Combustible 24"(610mm) Noncombustible 18"(457mm)

V

F F=6" (152mm)

Outside Corner

H

V

J

Combustible &

Noncombustible

H = 24" (610mm)

J = 20" (508mm)

 

D

C

C

 

V

E

C = Maximum depth of 48" (1219mm) for alcove location

D = Minimum width for back wall of alcove location Combustible - 38" (965mm) Noncombustible - 24" (610mm)

E = Clearance from corner in alcove location

Combustible - 6" (152mm) Noncombustible - 2" (51mm)

Balcony with No Side Wall

Balcony with Perpendicular

 

 

 

Alcove Location

 

 

Figure 14 -

Side Wall

 

40

 

 

 

 

 

Allowable Venting Chart

 

 

38

 

 

 

 

 

How To Use The Vent Graph

 

 

36

 

 

 

 

Vertical

 

 

34

 

Dimensions in

 

The Vent Graph should be read in conjunction with the following

 

 

 

 

 

 

 

 

32

 

 

 

 

 

 

Feet

 

 

vent installation instructions to determine the relationship between

 

30

 

 

 

Dimension

 

 

 

 

 

ing through the outer wall. Using this dimension on the Sidewall

 

 

 

 

 

 

 

 

 

 

 

the vertical and horizontal dimensions of the vent system.

 

28

 

 

 

 

 

1. Determine the height of the center of the horizontal vent pipe exit-

 

 

 

 

 

 

 

26

 

 

 

 

 

 

 

 

 

 

 

 

 

Vent Graph below, locate the point intersecting with the slanted

 

24

 

 

 

HorizontalVentPipe

From theFloorofUnit

 

12

 

 

 

Example: If the vertical dimension from the floor of the fireplace

 

 

 

 

graph line.

 

 

22

 

 

 

 

 

2. From the point of this intersection, draw a vertical line to the

 

20

 

 

 

 

 

bottom of the graph.

 

 

18

 

 

 

 

 

 

 

16

 

 

 

 

 

3. Select the indicated dimension, and position the fireplace in

 

 

 

 

 

 

 

14

 

 

 

 

 

accordance with same.

 

 

 

 

eg: A

 

 

 

 

 

 

 

 

 

is 11' (3.4 m) the horizontal run to the face of the outer wall must

 

10

 

 

 

 

to

 

8

 

 

 

 

the

not exceed 14' (4.3 m).

 

 

 

 

 

 

Example: If the vertical dimension from the floor of the unit is

 

6

 

 

 

 

Center

7’ (2.14m), the horizontal run to the face of the outer wall must

20"

4

 

 

 

 

not exceed 8Z\x' (2.6 m).

 

 

2

 

 

 

 

of

 

 

 

 

 

 

 

 

Sidewall Vent Graph showing the relationship between vertical and

 

2

4

6

8 10 1214 16 1820

 

the

horizontal dimensions for a Direct Vent flue system.

 

 

 

 

 

Horizontal Dimension From the Outside Face of the

 

 

 

Figure 15 - Wall to the Center of the Fireplace Vent Flange

 

Rear Wall Venting Graph

 

 

 

 

 

16

42D0200

Page 16
Image 16
Monessen Hearth PF, CR, CL)NVC/PVC, 624DV(ST manual How To Use The Vent Graph, Dimensions, Feet