Monessen Hearth PF, CR, CL)NVC/PVC Designer Series Gas Fireplaces, ventING installation, 42D0200

Models: CL)NVC/PVC PF 624DV(ST CR

1 52
Download 52 pages 60.61 Kb
Page 24
Image 24
4. Connect a section of pipe and extend up through the hole.

Designer Series Gas Fireplaces

ventING installation

4. Connect a section of pipe and extend up through the hole.

NOTE: If an offset is needed to avoid obstructions, you must support the vent pipe every three

(3)feet. Use wall straps for this purpose. Refer to Page 23, Figure 30. Whenever possible, use 45° elbows instead of 90° elbows. The 45° elbow offers less restriction to the flow of the flue gases and intake air.

5.Place the flashing over the pipe section(s) extending through the roof. Secure the base of the flash- ing to the roof and framing with roofing nails. Be sure roofing material overlaps the top edge of the flashing. There must be a 1" clearance from the vent pipe to combustible materials.

6.Continue to add pipe sections until the height of the vent cap meets the minimum building code requirements.

NOTE: You must increase vent height for steep roof pitches. Nearby trees, adjoining roof lines, steep pitched roofs, and other similar factors may cause poor draft or down-drafting in high winds. Increasing the vent height may solve this problem.

NOTE: If the vent pipe passes through any occupied areas above the first floor, including storage spaces and closets, you must enclose pipe. You may frame and sheetrock the enclosure with standard construction material. Make sure to meet the minimum allowable clearances to combustibles. Do not fill any of the required clearance spaces with insulation.

24

42D0200

Page 24
Image 24
Monessen Hearth PF, CR, CL)NVC/PVC, 624DV(ST manual Designer Series Gas Fireplaces, ventING installation, 42D0200