Designer Series Gas Fireplaces

ventING installation

vertical through-the-roof applications

This Gas Fireplace has been approved for,

Vertical installations up to 40' (12 m) in height. Up to a 10' (3 m) horizontal vent run can be installed within the vent system using a maximum of two 90° elbows. Figure 28

40' Maximum Height 8' Minimum Height

10'

Maximum

40' Maximum Height

8' Minimum Height

Support Straps

Every 3'

10'

Maximum

Support Straps

Every 3'

FP2308

Figure 30 -

Support Straps for Horizontal Runs

Up to two 45° elbows may be used within the horizontal run. For each 45° elbow used on the horizontal plane, the maximum horizontal length must be reduced by 18" (450 mm).

Example: Maximum horizontal length

No elbows

=

10’ (3 m)

1 x 45° elbows

=

8.5’ (2.6 m)

2 x 45° elbows

=

7’ (2.1 m)

A minimum of an 8' (2.5 m) vertical rise is required.

Two sets of 45° elbows offsets may be used within the vertical sections. From 0 to a maximum of 8' (2.5 m) of vent pipe can be used between elbows. Figure 31

The maximum angular variation allowed in the system is 270°. Figure 31

The minimum height of the vent above the high- est point of penetration through the roof is 2' (610 mm).

 

1

 

 

 

 

2

 

 

 

 

3

 

 

 

 

4

 

 

 

 

 

 

 

1

Example:

Elbow 1

=

90°

2

3

 

Elbow 2

=

45°

 

Elbow 3

=

45°

4

 

Elbow 4

=

90°

 

 

Total Angular Variation

=

270°

 

Figure 31 -

Maximum Elbow Usage

FP2309

22

42D0200

Page 22
Image 22
Monessen Hearth CL)NVC/PVC, PF, CR, 624DV(ST manual Vertical through-the-roof applications