Designer Series Gas Fireplaces

ventING installation

horizontal termination configuration (Continued)

If a 90° elbow is used in the horizontal vent run, the horizontal vent length is reduced by 36" (914 mm). Figure 25. This does not apply if the 90° elbows are used to increase or redirect a vertical rise. Figure 25

Example: According to the vent graph, Figure 22, the maximum horizontal vent length in a system with a 7.5' vertical rise is 20’ (6 m) and if a 90° elbow is required in the horizontal vent it must be reduced to 17' (5.2 m). Refer to Page 17 “How to Use Vent Graph.”

In Figures 26 and 27, Dimension A plus B must not be greater than 17' (5.2 m).

The maximum number of 45° elbows permitted per side wall installation is two (2). These elbows can be installed in either the vertical or horizontal run.

For each 45° elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by 18" (45 cm). This does not apply if the 45° elbows are installed on the vertical part of the vent system.

The maximum number of elbow degrees in a system is 270°. Figure 27

A

FP2305

90°

B

7’6”

Figure 25 -

Horizontal Run Reduction

A

B

7’

10’

 

 

 

90° Elbow = 3'

 

 

A + B = 17' Maximum

 

1

 

 

 

 

 

2

7’6”

Example:

Elbow 1

=

90°

3

 

4

 

 

Elbow 2

=

45°

 

 

 

 

 

Elbow 3

=

45°

 

 

 

Elbow 4

=

90°

 

 

Total Angular Variation

=

270°

 

 

FP2306

 

 

 

 

 

Figure 26 -

 

 

 

 

 

Maximum Vent Run with Elbows

 

 

 

 

 

 

 

 

1 + 2 + 3 + 4 = 270°

1 Example:

2

3

4

Figure 27 -

FP2307

Maximum Elbow Usage

 

20