Designer Series Gas Fireplaces | fireplace installation |
WARNING
Only persons licensed to work with gas piping may make the necessary gas connections to this appliance.
CAUTION
A manual shutoff valve must be installed upstream of the appliance. Union tee and plugged 1/8” NPT pressure tapping point should be installed upstream of the appliance. Figure 35
NOTE : The gas line connection may be made using 1/2" rigid tubing or an approved flex connector. Since some municipalities have additional local codes it is always best to consult your local authorities and the current edition of the National Fuel Gas Code ANSI.Z223.1, NFPA54. In Canada
A listed manual shutoff valve must be installed upstream of the appliance. Union tee and plugged 1/8" NPT pres- sure tapping point should be installed upstream of the appliance. Figure 36
IMPORTANT: Install main gas valve (equipment shutoff valve) in an accessible location. The main gas valve is for turning on or shutting off the gas to the fireplace.
Check your building codes for any special requirements for locating equipment shutoff valve to fireplaces.
Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess seal- ant in pipe could result in clogged burner system valves.
CAUTION
Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.
We recommend that you install a sediment trap/drip leg
in supply line as shown in Figure 36. Locate sediment trap/drip leg where it is within reach for cleaning. Install in piping system between fuel supply and burner system. Locate sediment trap/drip leg where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into the burner system gas controls. If sediment trap/drip leg is not installed or is installed wrong, burner system may not run properly.
CSA
Shutoff Valve with 1/8" NPT Tap*
Approved Flexible Gas Line
Sediment Trap/Drip Leg
Figure 36 -
Gas Connection
Tee Joint
Pipe Nipple
Cap
Natural Gas
From Gas Meter
(4.5" w.c. to 10.5" w.c. Pressure)
Propane/LP
From External Regulator
(11" w.c. to 13" w.c. Pressure)
26 | 42D0200 |