for horizontal termination
Select the amount of vertical rise desired. All horizontal run of venting must have 1/4" rise for every 12" of run towards the termination.
You may use up to three 90° elbows in this vent configuration. Refer to Horizontal Termination Configu- rations on Pages 22 and 23.
For vertical termination
Measure the distance from the fireplace floor to the ceiling. Add the ceiling thickness, the vertical rise in an attic or second story, and allow for sufficient vent height above the roof line.
NOTE: You may use two 45° elbows in place of a 90° elbow. You must follow rise to run ratios when using 45° elbows. The appliance is approved for use with three 90° elbows maximum or a combination of 90° and 45° elbows up to a maximum of 270°.
For two-story applications, firestops are required at each floor level. If an offset is needed in the attic, additional pipe and elbows will be required.
You may use a chase with a vent termination with exposed pipe on the exterior of the house. Refer to Installing Vent System in a Chase below. If pipe is enclosed in chase, it is not exposed.
It is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust. Certain limitations apply to vent configurations and must be strictly followed.
Installing a vent system in an outside chase
A chase is a vertical boxlike structure built to enclose venting that runs along the outside of a building. A chase is required for such venting.
Vertical Termination
Horizontal Termination
There are two basic types of direct-vent installation:
Never run the vent pipe down. This may cause excessive temperatures which could cause a fire.
WARNING It is important to select the proper length of vent pipe for the type of termination you choose. It is also
important to note the wall thickness.
Designer Series Gas Fireplaces
installation planning
VentING installation

WARNING

Treatment of firestops and construction of the chase may vary from building type to building type. These instructions are not substitutes for the requirements of local building codes. You must follow all local building codes.

NOTICE

When installing in a chase, you should insulate the chase as you would the outside walls of your home. This is especially important in cold climates. Insulation should be considered a combustible material. Maintain proper clearances to all combustible materials.

WARNING

Always maintain minimum clearances around vent systems. The minimum clearances to combustibles for horizontal vent pipe are 3" at the top and 1" at the sides and bottom of the vent system until the pipe penetrates the nearest vertical wall. A 1" minimum clearance all around the pipe must be maintained. Do not pack the open air spaces with insulation or other materials. This could cause high temperatures and may present a fire hazard.

14

42D0200

Page 14
Image 14
Monessen Hearth CL)NVC/PVC, PF, CR, 624DV(ST manual 42D0200