UsingAA the Auto Clean function

Auto clean function will prevent from growing mold by eliminating the moisture inside of the indoor unit. Your indoor unit evaporates the moisture inside of the unit. Activate this function to provide you with more clean and healthier air.

30/32/36T

30/32/36U

Press the Auto Clean button.

When the air conditioner is turned off,

The Auto clean indicator on the indoor unit display appears and the Auto cleaning function runs.

When the air conditioner is turned on,

After stopping the air conditioner operation, the Auto clean indicator on the indoor unit display appears and the Auto cleaning function runs.

Auto Cleaning time can vary, depending on the previously used mode.

Auto(cool), Cool, Dry mode : approximately 30 minutes.

Auto(heat-AQseries), Heat(AQseries), Fan mode : approximately 15 minutes.

Cancel Press the Auto Clean button once again.

• When the air conditioner is turned on, the Auto clean function runs after

stopping the air conditioner operation.

Using the Quiet function

Press the Quiet button while the air conditioner is operating in Cool/Heat mode,Fan speed is set to Auto.

Cancel Press the Queit button once again.

• Press the Quiet button once again,Fan speed remain Auto speed.

• The air conditioner has no Quiet function .

16

MAX4 AQ&AST&U_IB&IM_DB98-34063A_E.indd 16

2013-3-18 15:46:35

Image 16
Contents English Contents SafetAA y precautions Important safety symbols and precautionsFollow directions Wall socketFor Using For Cleaning ChecAA king before use Operation rangesPower ChecAA king the name of the partsMain parts  AQ/AS 30/32/36T  Display  AQ/AS 30/32/36TChecAA king the remote controller Remote controller buttonsRemote controller display Battery changing timeStoring the remote controller Inserting the batteriesBasicAA function Press the button to adjust the temperature Press the button to set the desired fan speedUsing the Turbo function Press the Air swing button on the remote controllerAdjusA ting the air flow direction Vertical air flowAA mode Press the button on the remote controllerPress the Time Up or Time Down button to set the time Press the Set button to active it onPress the On Timer/Off Timer button SettinAA g the On/Off timerAdditional options available in On timer mode Using the Smart Saver function From the moment you have set the timerIf the air conditioner is on If the air conditioner is off Turn off automaticallyUsingAA the Auto Clean function Using the Quiet functionWhen the air conditioner is turned on 30/32/36T 30/32/36UCleaning the indoor unit Cleaning the outdoor unit heat exchangerOpening the panel Heat exchangerCleanAA ing the air conditioner Cleaning the air filterRemoving the Air filter Open the panel and put the Air filter outBio filter AACleaning the air conditionerBio filter sky-blue Deodorizing filter Deodorizing filter blackMainAA taining the air conditioner Periodical checksTroubleshootingAA Flow movement changes. It is normal ConnectionSafety precautions General informationChoosing the installation location Installing the unitPower supply line, fuse or circuit breaker  a place where the air filter can be replaced easilyWhere sulfide gas exists ChooAA sing the installation locationOutdoor Unit When installing more than 1 outdoor unit When the air outlet is towards the wall Figure Description Top view Side viewAccessories in the indoor unit case AccessoriesAccessories in the outdoor unit case Fixing the installation plate Optional accessoriesTools required for installation General Tools Tools for test operationsCable specification Connecting the assembly cableConnecting the cable Each wire is labeled with the corresponding terminal number Extend the assembly cable if necessaryInstallation Smooth the cut edges Cut off the remaining foam insulationAAPurging the indoor unit Cutting or extending the pipeUnscrew the caps at the end of each pipe Put a flare nut slightly into the pipe and modify the flareCuttingAA or extending the pipe Outer DiameterDrain hose installation Two hoses are firmly connected, there is no water leakageHose tight Check for leakage on both side of the drain outletPurging the connected pipes AQseriesAdding Refrigerant Add refrigerant charge according to table belowIf you use a pipe shorter than 4 30/32 or 5 36 m Purge time is normalPerfoAA rming the gas leak tests Fixing the indoor unit in placeOutdoor unit installed on the wall by rack Fixing the outdoor unit in placeAppropriate support wall or ground ModelPress the Power button and check the following Press the Power button to stop the operationFinalAA Check and Trial Operation Check the followingsAfter tube contraction work is completed, wrap it with Apply heat to the contraction tube to contract itInsulation tape to finish AATechnical Specifications AS36UGBUMG AS30UGBUMGEnglish Questions or COMMENTS? EgyptAir Conditioner