Samsung AS30UGBNUMG, AQ36UGBNUMG, AS36UGBNUMG Extend the assembly cable if necessary, Installation

Page 31

1. Extend the assembly cable if necessary.

• Do not connect two or more different cables to extend the length. It may cause fire.

2 . Open the front grille.

3 . Remove the screw securing the connector cover.

4 . Pass the assembly cable through the rear of the indoor unit and connect the assembly cable to terminals. (Refer to the picture below)

• Each wire is labeled with the corresponding terminal number.

5 . Pass the other end of the cable through the 65mm hole in the wall.

6 . Close the connector cover by tightening the screw carefully.

7 . Close the front grille.

8 . Remove the terminal board cover on the side of the outdoor unit. 9. Connect the cables to the terminals as seen in the picture.

• Each wire is labeled with the corresponding terminal number.

Indoor unit

Indoor unit

N1

L1

1

2

3

4

 

 

 

 

N1

L1

1

2

3

4 Ground wire

 

 

 

 

 

 

 

(Green/Yellow)

 

N1

L1

1

2

3

4

Ground wire

Outdoor unit

 

 

 

 

 

 

(Green/Yellow)

 

N1

L1

1

2

3

4

N L

N L

Outdoor unit

Circuit Breaker (main power)

• End of the wire must be circular.

• After connecting the cables, make sure terminal numbers on the indoor/outdoor unit matches.

Screws on terminal block must not be unscrewed with the torque less than 12kgf•cm.

10.Connect the grounding conductor to the grounding terminals.

11.Close the terminal board cover by tightening the screw carefully.

• In Russia and Europe, consult with the supply authority to determine the supply system impedance before

installation.

• Connect the wires firmly so that wires can not be pulled out easily. (If they are loose, it could cause burn-out of the wires.)

• Connect the wires according to color codes, referring to the wiring diagram.

• The power cable and the interconnection cable should be selected according to the specification in page 30.

Power Wiring and Communication Wiring Configuration

Be sure to run the power supply cable and the communication cable through electrical conduit as seen in the picture.

Install the communication cable, indoor power cable and the main power cable in the cable tube.

• Secure the cable tube to the outdoor knockout using the CD connector and bushing.

• Arrange the cables as shown in the picture.

• The diameter of the 6 knock-out holes is Ø27.8 mm(Ø1-3/32 inch).

ENGLISH

Communication cable

Main power cable

(Inside)

(Outside)

31

MAX4 AQ&AST&U_IB&IM_DB98-34063A_E.indd 31

2013-3-18 15:46:38

Image 31
Contents English Contents Wall socket SafetAA y precautionsImportant safety symbols and precautions Follow directionsFor Using For Cleaning Operation ranges ChecAA king before useDisplay  AQ/AS 30/32/36T PowerChecAA king the name of the parts Main parts  AQ/AS 30/32/36T Remote controller buttons ChecAA king the remote controllerInserting the batteries Remote controller displayBattery changing time Storing the remote controllerBasicAA function Press the button to set the desired fan speed Press the button to adjust the temperatureVertical air flow Using the Turbo functionPress the Air swing button on the remote controller AdjusA ting the air flow directionPress the Set button to active it on AA modePress the button on the remote controller Press the Time Up or Time Down button to set the timePress the On Timer/Off Timer button SettinAA g the On/Off timerAdditional options available in On timer mode Turn off automatically Using the Smart Saver functionFrom the moment you have set the timer If the air conditioner is on If the air conditioner is off30/32/36T 30/32/36U UsingAA the Auto Clean functionUsing the Quiet function When the air conditioner is turned onHeat exchanger Cleaning the indoor unitCleaning the outdoor unit heat exchanger Opening the panelOpen the panel and put the Air filter out CleanAA ing the air conditionerCleaning the air filter Removing the Air filterBio filter AACleaning the air conditionerBio filter sky-blue Deodorizing filter black Deodorizing filterPeriodical checks MainAA taining the air conditionerTroubleshootingAA Connection Flow movement changes. It is normalGeneral information Safety precautions a place where the air filter can be replaced easily Choosing the installation locationInstalling the unit Power supply line, fuse or circuit breakerWhere sulfide gas exists ChooAA sing the installation locationOutdoor Unit Top view Side view When installing more than 1 outdoor unitWhen the air outlet is towards the wall  Figure Description Accessories in the indoor unit case Accessories Accessories in the outdoor unit case Tools for test operations Fixing the installation plateOptional accessories Tools required for installation General ToolsCable specification Connecting the assembly cableConnecting the cable Each wire is labeled with the corresponding terminal number Extend the assembly cable if necessaryInstallation Cut off the remaining foam insulation Smooth the cut edgesPut a flare nut slightly into the pipe and modify the flare AAPurging the indoor unitCutting or extending the pipe Unscrew the caps at the end of each pipeOuter Diameter CuttingAA or extending the pipeCheck for leakage on both side of the drain outlet Drain hose installationTwo hoses are firmly connected, there is no water leakage Hose tightAQseries Purging the connected pipesPurge time is normal Adding RefrigerantAdd refrigerant charge according to table below If you use a pipe shorter than 4 30/32 or 5 36 mFixing the indoor unit in place PerfoAA rming the gas leak testsModel Outdoor unit installed on the wall by rackFixing the outdoor unit in place Appropriate support wall or groundCheck the followings Press the Power button and check the followingPress the Power button to stop the operation FinalAA Check and Trial OperationAfter tube contraction work is completed, wrap it with Apply heat to the contraction tube to contract itInsulation tape to finish AS36UGBUMG AS30UGBUMG AATechnical SpecificationsEnglish Egypt Questions or COMMENTS?Air Conditioner