Samsung AS36UGBNUMG, AQ36UGBNUMG manual Smooth the cut edges, Cut off the remaining foam insulation

Page 32

CAUTION

Make a knockout hole by driving in a nail.

When installing the cables through the knockout hole, remove all burrs and protect them with the protection tape.

Apply rust resisting paint around the hole.

Installing and connecting the assembly pipe of the indoor unit

Connect indoor and outdoor units with field-supplied copper pipes by means of flare connections. Use insulated seamless refrigeration grade pipe only, (Cu DHP type according to ISO1337), degreased and deoxidized, suitable for operating pressures of at least 4200 kPa and for burst pressure of at least 20700 kPa. Under no circumstances must sanitary type copper pipe be used.

There are 2 refrigerant pipes of different diameters:

• The smaller one is for the liquid refrigerant

• The larger one is for the gas refrigerant

A short pipe is already fitted to the air conditioner. You may need to extend the pipe using the assembly pipe (optional).

The connection procedure for the refrigerant pipe varies

A

B

according to the exit position of the pipe when facing the wall:

 

 

• Right(A)

C

Left(B)

Underside(C)

Rear

1.Cut out the appropriate knock-out piece (A, B, C) on the rear of the indoor unit unless you connect the pipe directly from the rear.

2.Smooth the cut edges.

3.Remove the protection caps of the pipes and connect the assembly pipe to each pipe. Tighten the nuts first with your hands, and then with a torque wrench, applying the following torque:

• If you want to shorten or extend the pipes, refer to page 33~34.

Outer Diameter

Torque (kgf•cm)

ø6.35 mm

140~170

ø9.52 mm

250~280

ø12.70 mm

380~420

ø15.88 mm

440~480

ø19.05 mm

990~1210

ø22.23 mm

990~1210

4.Cut off the remaining foam insulation.

5.If necessary, bend the pipe to fit along the bottom of the indoor unit. Then pull it out through the appropriate hole.

The pipe should not project from the rear of the indoor unit.

The bending radius should be 100 mm or more.

6.Pass the pipe through the hole in the wall.

7.For further details on how to connect to the outdoor unit and purge the air, refer to page 36~37.

• The pipe will be insulated and fixed permanently into position after finishing the installation and the gas leak test;

refer to page 38 for further details.

• Tighten the flare nut with torque wrench according to specified method.

If the flare nut is over-tightened, the flare may break and cause refrigerant gas leakage.

DO NOT WALL UP THE PIPE CONNECTION !

All refrigerant pipe connection must be easy accessible and serviceable.

32

MAX4 AQ&AST&U_IB&IM_DB98-34063A_E.indd 32

2013-3-18 15:46:39

Image 32
Contents English Contents SafetAA y precautions Important safety symbols and precautionsFollow directions Wall socketFor Using For Cleaning ChecAA king before use Operation rangesPower ChecAA king the name of the partsMain parts  AQ/AS 30/32/36T  Display  AQ/AS 30/32/36TChecAA king the remote controller Remote controller buttonsRemote controller display Battery changing timeStoring the remote controller Inserting the batteriesBasicAA function Press the button to adjust the temperature Press the button to set the desired fan speedUsing the Turbo function Press the Air swing button on the remote controllerAdjusA ting the air flow direction Vertical air flowAA mode Press the button on the remote controllerPress the Time Up or Time Down button to set the time Press the Set button to active it onAdditional options available in On timer mode SettinAA g the On/Off timerPress the On Timer/Off Timer button Using the Smart Saver function From the moment you have set the timerIf the air conditioner is on If the air conditioner is off Turn off automaticallyUsingAA the Auto Clean function Using the Quiet functionWhen the air conditioner is turned on 30/32/36T 30/32/36UCleaning the indoor unit Cleaning the outdoor unit heat exchangerOpening the panel Heat exchangerCleanAA ing the air conditioner Cleaning the air filterRemoving the Air filter Open the panel and put the Air filter outBio filter sky-blue AACleaning the air conditionerBio filter Deodorizing filter Deodorizing filter blackMainAA taining the air conditioner Periodical checksTroubleshootingAA Flow movement changes. It is normal ConnectionSafety precautions General informationChoosing the installation location Installing the unitPower supply line, fuse or circuit breaker  a place where the air filter can be replaced easilyOutdoor Unit ChooAA sing the installation locationWhere sulfide gas exists When installing more than 1 outdoor unit When the air outlet is towards the wall Figure Description Top view Side viewAccessories in the outdoor unit case AccessoriesAccessories in the indoor unit case Fixing the installation plate Optional accessories Tools required for installation General Tools Tools for test operationsConnecting the cable Connecting the assembly cableCable specification Installation Extend the assembly cable if necessaryEach wire is labeled with the corresponding terminal number Smooth the cut edges Cut off the remaining foam insulationAAPurging the indoor unit Cutting or extending the pipeUnscrew the caps at the end of each pipe Put a flare nut slightly into the pipe and modify the flareCuttingAA or extending the pipe Outer DiameterDrain hose installation Two hoses are firmly connected, there is no water leakageHose tight Check for leakage on both side of the drain outletPurging the connected pipes AQseriesAdding Refrigerant Add refrigerant charge according to table belowIf you use a pipe shorter than 4 30/32 or 5 36 m Purge time is normalPerfoAA rming the gas leak tests Fixing the indoor unit in placeOutdoor unit installed on the wall by rack Fixing the outdoor unit in placeAppropriate support wall or ground ModelPress the Power button and check the following Press the Power button to stop the operationFinalAA Check and Trial Operation Check the followingsInsulation tape to finish Apply heat to the contraction tube to contract itAfter tube contraction work is completed, wrap it with AATechnical Specifications AS36UGBUMG AS30UGBUMGEnglish Questions or COMMENTS? EgyptAir Conditioner