PerfoAA rming the gas leak tests

Make sure to check for gas leaks before completing the installation process (connecting the assembly pipe and hose between indoor unit and outdoor unit, insulating the cables, hose and pipe, and fixing the indoor unit to the installation plate).

A C

B

To check for gas leaks on the outdoor unit,

Check the valve A and B using a leak detector.

To check for gas leaks on the indoor unit,

Check the flare nut C and D using a leak detector.

D

Fixing the indoor unit in place

Perform the following work on the area where gas leak test was done priorly.

 

 

After checking for gas leaks in the system, insulate the pipe, hose and cables.

Insulation

 

Then place the indoor unit on the installation plate.

 

 

1.

To avoid condensation problems, wrap foam insulation (as shown in the figure) on

 

 

a part without insulation on the end of the pipes.

 

 

2.

Wind the pipe, assembly cable and drain hose with vinyl tape.

Pipes

 

3.

Place the bundle (the pipe, assembly cable and drain hose) in the lower part

 

 

 

of the indoor unit carefully so it does not project from the rear of the indoor

Installation

 

 

unit.

 

4.

Hook the indoor unit to the installation plate and move the unit to the right

plate

Connecting

Vinyl tape

pipes

 

and left until it is securely in place.

 

Connecting wires

 

 

 

 

 

• Make sure pipe does not move when you install the indoor unit on

Drain hose

 

 

an installation plate.

 

 

5.Wrap the rest of the pipe with vinyl tape.

6.Attach the pipe to the wall using clamps (optional).

38

MAX4 AQ&AST&U_IB&IM_DB98-34063A_E.indd 38

2013-3-18 15:46:40

Image 38
Contents English Contents Follow directions SafetAA y precautionsImportant safety symbols and precautions Wall socketFor Using For Cleaning ChecAA king before use Operation rangesMain parts  AQ/AS 30/32/36T  PowerChecAA king the name of the parts Display  AQ/AS 30/32/36TChecAA king the remote controller Remote controller buttonsStoring the remote controller Remote controller displayBattery changing time Inserting the batteriesBasicAA function Press the button to adjust the temperature Press the button to set the desired fan speedAdjusA ting the air flow direction Using the Turbo functionPress the Air swing button on the remote controller Vertical air flowPress the Time Up or Time Down button to set the time AA modePress the button on the remote controller Press the Set button to active it onAdditional options available in On timer mode SettinAA g the On/Off timerPress the On Timer/Off Timer button If the air conditioner is on If the air conditioner is off Using the Smart Saver functionFrom the moment you have set the timer Turn off automaticallyWhen the air conditioner is turned on UsingAA the Auto Clean functionUsing the Quiet function 30/32/36T 30/32/36UOpening the panel Cleaning the indoor unitCleaning the outdoor unit heat exchanger Heat exchangerRemoving the Air filter CleanAA ing the air conditionerCleaning the air filter Open the panel and put the Air filter outBio filter sky-blue AACleaning the air conditionerBio filter Deodorizing filter Deodorizing filter blackMainAA taining the air conditioner Periodical checksTroubleshootingAA Flow movement changes. It is normal ConnectionSafety precautions General informationPower supply line, fuse or circuit breaker Choosing the installation locationInstalling the unit  a place where the air filter can be replaced easilyOutdoor Unit ChooAA sing the installation locationWhere sulfide gas exists  Figure Description When installing more than 1 outdoor unitWhen the air outlet is towards the wall Top view Side viewAccessories in the outdoor unit case AccessoriesAccessories in the indoor unit case Tools required for installation General Tools Fixing the installation plateOptional accessories Tools for test operationsConnecting the cable Connecting the assembly cableCable specification Installation Extend the assembly cable if necessaryEach wire is labeled with the corresponding terminal number Smooth the cut edges Cut off the remaining foam insulationUnscrew the caps at the end of each pipe AAPurging the indoor unitCutting or extending the pipe Put a flare nut slightly into the pipe and modify the flareCuttingAA or extending the pipe Outer DiameterHose tight Drain hose installationTwo hoses are firmly connected, there is no water leakage Check for leakage on both side of the drain outletPurging the connected pipes AQseriesIf you use a pipe shorter than 4 30/32 or 5 36 m Adding RefrigerantAdd refrigerant charge according to table below Purge time is normalPerfoAA rming the gas leak tests Fixing the indoor unit in placeAppropriate support wall or ground Outdoor unit installed on the wall by rackFixing the outdoor unit in place ModelFinalAA Check and Trial Operation Press the Power button and check the followingPress the Power button to stop the operation Check the followingsInsulation tape to finish Apply heat to the contraction tube to contract itAfter tube contraction work is completed, wrap it with AATechnical Specifications AS36UGBUMG AS30UGBUMGEnglish Questions or COMMENTS? EgyptAir Conditioner