CuttingAA or extending the pipe

5. Check if you flared the pipe correctly (see examples of incorrectly flared pipes below).

Correct

Inclined

Damaged

Cracked

Uneven

 

 

Surface

 

Thickness

6.Align the pipes to connect them easily. Tighten the flare nuts first with your hands, and then with a torque wrench, applying the following torque:

Flare nut

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor outlet

 

pipe

 

 

 

 

 

Connecting pipe

Outer Diameter

Torque (kgf•cm)

ø6.35 mm

140~170

ø9.52 mm

250~280

ø12.70 mm

380~420

ø15.88 mm

440~480

ø19.05 mm

990~1210

ø22.23 mm

990~1210

• Excessive torque can be cause of gas leakage. In case brazing the pipe, the nitrogen gas must be blown into the

pipe (50 Pa). The joint must be accessible and serviceable.

7. For further details on how to connect to the outdoor unit and purge the air, refer to page 36~37.

• Tighten the flare nut with torque wrench according to specified method.

If the flare nut is over-tightened, the flare may break and cause refrigerant gas leakage.

Installing and connecting the drain hose of the indoor unit

When installing the drain hose for the indoor unit, check if condensation draining is adequate. When passing the drain hose through the 65-mm hole drilled in the wall, check the followings:

Wall

Indoor unit

Drain hose

The drain hose must not be bent.

The drain hose must NOT slant upwards.

5cm

less

Keep a clearance of at least 5cm between the end of the drain hose and the ground.

The end of the drain hose must NOT be placed under water.

Ditch

Do not place the end of the drain hose in a hollow.

34

MAX4 AQ&AST&U_IB&IM_DB98-34063A_E.indd 34

2013-3-18 15:46:39

Image 34
Contents English Contents Follow directions SafetAA y precautionsImportant safety symbols and precautions Wall socketFor Using For Cleaning ChecAA king before use Operation rangesMain parts  AQ/AS 30/32/36T  PowerChecAA king the name of the parts Display  AQ/AS 30/32/36TChecAA king the remote controller Remote controller buttonsStoring the remote controller Remote controller displayBattery changing time Inserting the batteriesBasicAA function Press the button to adjust the temperature Press the button to set the desired fan speedAdjusA ting the air flow direction Using the Turbo functionPress the Air swing button on the remote controller Vertical air flowPress the Time Up or Time Down button to set the time AA modePress the button on the remote controller Press the Set button to active it onPress the On Timer/Off Timer button SettinAA g the On/Off timerAdditional options available in On timer mode If the air conditioner is on If the air conditioner is off Using the Smart Saver functionFrom the moment you have set the timer Turn off automaticallyWhen the air conditioner is turned on UsingAA the Auto Clean functionUsing the Quiet function 30/32/36T 30/32/36UOpening the panel Cleaning the indoor unitCleaning the outdoor unit heat exchanger Heat exchangerRemoving the Air filter CleanAA ing the air conditionerCleaning the air filter Open the panel and put the Air filter outBio filter AACleaning the air conditionerBio filter sky-blue Deodorizing filter Deodorizing filter blackMainAA taining the air conditioner Periodical checksTroubleshootingAA Flow movement changes. It is normal ConnectionSafety precautions General informationPower supply line, fuse or circuit breaker Choosing the installation locationInstalling the unit  a place where the air filter can be replaced easilyWhere sulfide gas exists ChooAA sing the installation locationOutdoor Unit  Figure Description When installing more than 1 outdoor unitWhen the air outlet is towards the wall Top view Side viewAccessories in the indoor unit case AccessoriesAccessories in the outdoor unit case Tools required for installation General Tools Fixing the installation plateOptional accessories Tools for test operationsCable specification Connecting the assembly cableConnecting the cable Each wire is labeled with the corresponding terminal number Extend the assembly cable if necessaryInstallation Smooth the cut edges Cut off the remaining foam insulationUnscrew the caps at the end of each pipe AAPurging the indoor unitCutting or extending the pipe Put a flare nut slightly into the pipe and modify the flareCuttingAA or extending the pipe Outer DiameterHose tight Drain hose installationTwo hoses are firmly connected, there is no water leakage Check for leakage on both side of the drain outletPurging the connected pipes AQseriesIf you use a pipe shorter than 4 30/32 or 5 36 m Adding RefrigerantAdd refrigerant charge according to table below Purge time is normalPerfoAA rming the gas leak tests Fixing the indoor unit in placeAppropriate support wall or ground Outdoor unit installed on the wall by rackFixing the outdoor unit in place ModelFinalAA Check and Trial Operation Press the Power button and check the followingPress the Power button to stop the operation Check the followingsAfter tube contraction work is completed, wrap it with Apply heat to the contraction tube to contract itInsulation tape to finish AATechnical Specifications AS36UGBUMG AS30UGBUMGEnglish Questions or COMMENTS? EgyptAir Conditioner