Samsung AP30M0ANUMG, AP30M0ANXSG, AP30M0AXUMG manual Power supply line, fuse or circuit breaker

Page 33

After completing the installation, always carry out a functional test and provide the instructions on how to operate the air conditioner to the user.

Do not use the air conditioner in environments with hazardous substances or close to equipment that release free flames to avoid the occurrence of fires, explosions or injuries.

Our units must be installed in compliance with the spaces indicated in the manual to ensure either accessibility from both sides or ability to perform routine maintenance and repairs. The units’ components must be accessible and that can be disassembled in conditions of complete safety either for people or things. For this reason, where it is not observed as indicated into the manual, the cost necessary to reach and repair the unit (in safety, as required by current regulations in force) with slings, trucks, scaffolding or any other means of elevation won’t be considered in-warranty and charged to end user.

Power supply line, fuse or circuit breaker

Always make sure that the power supply is compliant with current safety standards. Always install the air conditioner in compliance with current local safety standards.

Always verify that a suitable grounding connection is available.

Verify that the voltage and frequency of the power supply comply with the specifications and that the installed power is sufficient to ensure the operation of any other domestic appliance connected to the same electric lines.

Always verify that the cut-off and protection switches are suitably dimensioned.

Verify that the air conditioner is connected to the power supply in accordance with the instructions provided in the wiring diagram included in the manual.

Always verify that electric connections (cable entry, section of leads, protections…) are compliant with the electric specifications and with the instructions provided in the wiring scheme. Always verify that all connections comply with the standards applicable to the installation of air conditioners.

Make sure that you earth the cables.

-Do not connect the earth wire to the gas pipe, water pipe, lighting rod or telephone wire. If earthing is not complete, electric shock or fire may occur.

Install the circuit breaker.

-If the circuit breaker is not installed, electric shock or fire may occur.

Make sure that the condensed water dripping from the drain hose runs out properly and safely.

Install the power cable and communication cable of the indoor and outdoor unit at least 1m away from the electric appliance.

Install the indoor unit away from lighting apparatus using the ballast.

-If you use the wireless remote controller, reception error may occur due to the ballast of the lighting apparatus.

Do not install the air conditioner in following places.

-Place where there is mineral oil or arsenic acid.

Resin parts flame and the accessories may drop or water may leak.

The capacity of the heat exchanger may reduce or the air conditioner may be out of order.

-The place where corrosive gas such as sulfurous acid gas generates from the vent pipe or air outlet. The copper pipe or connection pipe may corrode and refrigerant may leak.

-The place where there is a machine that generates electromagnetic waves. The air conditioner may not operate normally due to control system.

-The place where there is a danger of existing combustible gas, carbon fiber or flammable dust. The place where thinner or gasoline is handled.

Gas may leak and it may cause fire.

installation part _33

Image 33
Contents DB98-33838A1 Air ConditionerStrong Turbo/Long Function Features of your new air conditionerLook for Everywhere Serial #Safety Information Safety informationImportant safety symbols and precautions DeathEnsure no water gets into the air conditioner Do not yank the power cable with handsPotential risk of injury or electric shock Do not open the front panel during operation Do not drink drain water coming out of the air conditionerDo not place any objects, especially containers with liquid Insufficient ventilation may result in poor performance Safety information Contents Checking the Indoor Unit and Display Viewing your air conditionerMain parts To open the panelControl Panel Checking the Remote controller Using the remote controller Remote controller displayInstalling the batteries Close the cover by place it back to its original positionPress the Power button on the remote controller Selecting Operation ModeOperating basic function Turning the AIR Conditioner on and OFFCool Dry Fan Set the fan speed FanUsing advanced functions Using the Turbo functionTo deactivate Turbo function To deactivate Long function Using the Long FunctionAdjusting the AIR Flow Direction Vertical air flowAir flow can be directed to your desired position Horizontal air flow Setting Timer To deactivate the On TimerOn Timer Off Timer To deactivate the Off TimerCombining On Timer and Off Timer To deactivate the timer combinationPreset time of On Timer is shorter than Off Preset time of On Timer is longer than OffUsing the AIR Conditioner with the Control Panel Locking the Control Panel When the air conditioner is on or offCleaning the Exterior Cleaning and maintaining the air conditionerCleaning the Filter Air filterPeriodical checks Maintaining Your AIR ConditionerType Description Every Once a MonthsInternal protections via the unit control system Storing the remote controllerType Description Air conditioner does not start operating immediatelyAppendix TroubleshootingCondensation may occur on the indoor unit Operation Ranges21˚C to 54˚C On the floorSafety Precautions Power supply line, fuse or circuit breaker Part Name Accessory Parts ListTop view Selection of Installation PlaceElectric wire Below 20m 5mm Below 50m 4mm Allowable voltage PowerElectrical Work Circuit BreakerIndoor unit Outdoor UnitScrew Tightening torque kgf cm Installation Procedures Installation MethodAnchor bolt fixing dimensions Outdoor UnitIndoor unit Outdoor Unit Indoor unitCut the pipe using the pipe cutter Connection of Refrigerant PipingOuter DiameterD Amm  Drill a hole of 60mm in diameter to the outside Drilling a Hole in the WallDrain Hose Fixing the Indoor UnitInsulation Foamed Polyethylene ※ Be sure that all valve cocks are closed Air PurgeVacuum PumpRefrigerant Charging Outside temperature 35CRefill the refrigerant slowly checking the pressure Stop operationCheck and Test Operation CheckIs grounding properly made? Test Operation Pump Down Procedure When removing the productIndoor unit Packing and Unpacking GuideCushion-top  Packing case  Outdoor unit  Insulation tape Howto connectyour extended power cables021-8255 Questions or COMMENTS?183-2255 444 77 Samsung