Check and Test Operation

Test Operation

After checking, read the owner’s instructions carefully, and perform a test operation. Then deliver the unit to the customer.

(When delivering the unit, be sure to read carefully and follow the contents of the owner’s instructions.)

Check if the indoor/outdoor unit’s connection wires are properly connected.

1.Turn on the air conditioner and select Cool mode. (Test is only available in cooling operation.)

-Check if the cool air comes out from the indoor unit.

-Check if the fan of outdoor unit rotates.

2.If the units don’t work as above, check if the indoor/outdoor unit’s connection wires are properly connected.

The connection wires should be properly connected to the correct terminal number.

1. Be sure to check whether the service valve is open before attempting to perform the test operation.

2. Be sure to perform the test operation after installation.

It is easy to start the test operation in winter if you increase the sensor temperature to 23°C ~ 25°C by holding the indoor temperature sensor. (Cooling operation)

When the outdoor temperature is below zero, do not test operation for more than 3 minutes. Otherwise, the compressor will be damaged.

Temperature sensor

Pump Down Procedure (When removing the product)

1.Turn on the air conditioner and select Cool mode to run the compressor for 3 minutes.

2.Release the valve caps on High and Low pressure side.

3.Use L wrench to close the valve on the high pressure side.

4.Approximately 2 minutes after, close the valve on the low pressure side.

5.Stop operation of the air conditioner.

6.Disconnect the pipes.

46_ installation part

Image 46
Contents Air Conditioner DB98-33838A1Look for Everywhere Features of your new air conditionerStrong Turbo/Long Function Serial #Important safety symbols and precautions Safety informationSafety Information DeathDo not yank the power cable with hands Ensure no water gets into the air conditionerPotential risk of injury or electric shock Do not drink drain water coming out of the air conditioner Do not open the front panel during operationDo not place any objects, especially containers with liquid Insufficient ventilation may result in poor performance Safety information Contents Main parts Viewing your air conditionerChecking the Indoor Unit and Display To open the panelControl Panel Checking the Remote controller Installing the batteries Remote controller displayUsing the remote controller Close the cover by place it back to its original positionOperating basic function Selecting Operation ModePress the Power button on the remote controller Turning the AIR Conditioner on and OFFCool Dry Fan Fan Set the fan speedUsing the Turbo function Using advanced functionsTo deactivate Turbo function Using the Long Function To deactivate Long functionVertical air flow Adjusting the AIR Flow DirectionAir flow can be directed to your desired position Horizontal air flow To deactivate the On Timer Setting TimerOn Timer To deactivate the Off Timer Off TimerPreset time of On Timer is shorter than Off To deactivate the timer combinationCombining On Timer and Off Timer Preset time of On Timer is longer than OffUsing the AIR Conditioner with the Control Panel When the air conditioner is on or off Locking the Control PanelCleaning the Filter Cleaning and maintaining the air conditionerCleaning the Exterior Air filterType Description Every Once a Maintaining Your AIR ConditionerPeriodical checks MonthsType Description Storing the remote controllerInternal protections via the unit control system Air conditioner does not start operating immediatelyTroubleshooting Appendix21˚C to 54˚C Operation RangesCondensation may occur on the indoor unit On the floorSafety Precautions Power supply line, fuse or circuit breaker Accessory Parts List Part NameSelection of Installation Place Top viewElectrical Work PowerElectric wire Below 20m 5mm Below 50m 4mm Allowable voltage Circuit BreakerOutdoor Unit Indoor unitScrew Tightening torque kgf cm Anchor bolt fixing dimensions Installation MethodInstallation Procedures Outdoor UnitIndoor unit Indoor unit Outdoor UnitConnection of Refrigerant Piping Cut the pipe using the pipe cutterOuter DiameterD Amm Drilling a Hole in the Wall  Drill a hole of 60mm in diameter to the outsideFixing the Indoor Unit Drain HoseInsulation Foamed Polyethylene Vacuum Air Purge※ Be sure that all valve cocks are closed PumpRefill the refrigerant slowly checking the pressure Outside temperature 35CRefrigerant Charging Stop operationCheck Check and Test OperationIs grounding properly made? Pump Down Procedure When removing the product Test OperationPacking and Unpacking Guide Indoor unitCushion-top  Packing case  Outdoor unit  Howto connectyour extended power cables Insulation tape183-2255 Questions or COMMENTS?021-8255 444 77 Samsung