Samsung AP30M0AXXSG manual Air Purge, ※ Be sure that all valve cocks are closed, Vacuum, Pump

Page 43

Air Purge

Be sure that all valve cocks are closed.

The air in the indoor unit and in the pipe must be purged. If air remains in the refrigeration pipes, it will affect the compressor, reduce to cooling capacity and could lead to a malfunction.

Use Vacuum Pump as shown at the figure.

1.Connect each assembly pipe to the appropriate valve on the outdoor unit and tighten the flare nut.

2.Connect the charging hose of low pressure side of manifold gauge to the packed valve having a service port as shown at the figure.

3.Open the valve of the low pressure side of manifold gauge counter-clockwise.

4.Purge the air from the system using vacuum pump for about 10 minutes.

-Close the valve of the low pressure side of manifold gauge clockwise.

-Turn off the vacuum pump.

-Make sure that pressure gauge show -0.1MPa(-76cmHg) after about 10 minutes.

-This procedure is very important in order to avoid gas leak.

-Remove the hose of the low pressure side of manifold gauge.

5.Set valve cork of both liquid side and gas side of packed valve to the open position.

6.Mount the cap and the needle valve cap to the valve (see the below illustration), and tighten them at the torque of 183kgf•cm with a torque wrench.

7.Check for gas leakage.

-At this time, especially check for gas leakage from the 3-way valve’s stem nuts, and from the service port cap.

Gas pipe

 

 

 

 

side

OUTDOOR UNIT

 

 

 

Liquid

 

 

Indoor unit

pipe side

A

 

 

 

 

 

 

B

 

Liquid pipe side

Gas pipe side

 

 

 

 

Flare nut

Vacuum

 

 

 

 

 

 

 

Valve cock

Pump

3-way valve

3-way valve

 

Cap

 

 

 

 

Needle valve

 

Outdoor unit

 

 

 

 

 

cap

 

 

 

installation part _43

Image 43
Contents DB98-33838A1 Air ConditionerSerial # Features of your new air conditionerStrong Turbo/Long Function Look for EverywhereDeath Safety informationSafety Information Important safety symbols and precautionsEnsure no water gets into the air conditioner Do not yank the power cable with handsPotential risk of injury or electric shock Do not drink drain water coming out of the air conditioner Do not open the front panel during operationDo not place any objects, especially containers with liquid Insufficient ventilation may result in poor performance Safety information Contents To open the panel Viewing your air conditionerChecking the Indoor Unit and Display Main partsControl Panel Checking the Remote controller Close the cover by place it back to its original position Remote controller displayUsing the remote controller Installing the batteriesTurning the AIR Conditioner on and OFF Selecting Operation ModePress the Power button on the remote controller Operating basic functionCool Dry Fan Set the fan speed FanUsing the Turbo function Using advanced functionsTo deactivate Turbo function To deactivate Long function Using the Long FunctionVertical air flow Adjusting the AIR Flow DirectionAir flow can be directed to your desired position Horizontal air flow To deactivate the On Timer Setting TimerOn Timer Off Timer To deactivate the Off TimerPreset time of On Timer is longer than Off To deactivate the timer combinationCombining On Timer and Off Timer Preset time of On Timer is shorter than OffUsing the AIR Conditioner with the Control Panel Locking the Control Panel When the air conditioner is on or offAir filter Cleaning and maintaining the air conditionerCleaning the Exterior Cleaning the FilterMonths Maintaining Your AIR ConditionerPeriodical checks Type Description Every Once aAir conditioner does not start operating immediately Storing the remote controllerInternal protections via the unit control system Type DescriptionAppendix TroubleshootingOn the floor Operation RangesCondensation may occur on the indoor unit 21˚C to 54˚CSafety Precautions Power supply line, fuse or circuit breaker Part Name Accessory Parts ListTop view Selection of Installation PlaceCircuit Breaker PowerElectric wire Below 20m 5mm Below 50m 4mm Allowable voltage Electrical WorkOutdoor Unit Indoor unitScrew Tightening torque kgf cm Outdoor Unit Installation MethodInstallation Procedures Anchor bolt fixing dimensionsIndoor unit Outdoor Unit Indoor unitConnection of Refrigerant Piping Cut the pipe using the pipe cutterOuter DiameterD Amm  Drill a hole of 60mm in diameter to the outside Drilling a Hole in the WallFixing the Indoor Unit Drain HoseInsulation Foamed Polyethylene Pump Air Purge※ Be sure that all valve cocks are closed VacuumStop operation Outside temperature 35CRefrigerant Charging Refill the refrigerant slowly checking the pressureCheck Check and Test OperationIs grounding properly made? Test Operation Pump Down Procedure When removing the productIndoor unit Packing and Unpacking GuideCushion-top  Packing case  Outdoor unit  Insulation tape Howto connectyour extended power cables444 77 Samsung Questions or COMMENTS?021-8255 183-2255