Electrical Work
The electrical work should be performed by a specialist qualified for the work.
Use the single phase power supply, and be sure to install the sub power distributing board for exclusive use with the unit (separately purchased by the user).
※Avoid multiple connecting wiring as it can cause a drop in voltage, thus resulting in poor performance of the automatic control circuit.
Be sure to install circuit breaker (separately purchased by the user).
Be sure to connect the grounding wire.
The indoor unit is powered by the outdoor unit by means of a H07
1.Remove the screw on the electrical component box and remove the cover plate.
2.Route the connection cord through the side of the indoor unit and connect the cable to terminals.
3.Route the other end of the cable to the outdoor unit through the ceiling & the hole on the wall.
4.Reassemble the electrical component box cover, carefully tightening the screw.
Wiring Standard
ITEM | SPEC | ||
|
|
| |
Power | Single phase 220V~, 60Hz | ||
|
|
| |
Circuit Breaker | Earth Leakage Circuit Breaker(ELCB) 30A | ||
|
|
| |
Electric wire | Below 20m | 2.5mm2 | |
Below 50m | 4mm2 | ||
| |||
|
|
| |
Allowable voltage | 198V~242V | ||
|
| ||
Min. size of electric wires from/to the indoor/ | 0.75mm2 | ||
outdoor units |
| ||
|
|
|
You must compress the solderless ring to the cable and then connect it to the main power terminal.
Solderless ring selection
Thickness of cable(mm2) | B(mm) | d2(mm) | Silver solder |
2.5 | Less than 9.5 | More than 4.5 |
|
4 | Less than 9.5 | More than 4.5 |
|