Electrical Work

The electrical work should be performed by a specialist qualified for the work.

Use the single phase power supply, and be sure to install the sub power distributing board for exclusive use with the unit (separately purchased by the user).

Avoid multiple connecting wiring as it can cause a drop in voltage, thus resulting in poor performance of the automatic control circuit.

Be sure to install circuit breaker (separately purchased by the user).

Be sure to connect the grounding wire.

The indoor unit is powered by the outdoor unit by means of a H07 RN-F connection cable (or a more power model), with insulation in synthetic rubber and jacket in polychloroprene(neoprene), in accordance with the requirements of standard IEC 60335-2-40.

1.Remove the screw on the electrical component box and remove the cover plate.

2.Route the connection cord through the side of the indoor unit and connect the cable to terminals.

3.Route the other end of the cable to the outdoor unit through the ceiling & the hole on the wall.

4.Reassemble the electrical component box cover, carefully tightening the screw.

Wiring Standard

ITEM

SPEC

 

 

 

Power

Single phase 220V~, 60Hz

 

 

 

Circuit Breaker

Earth Leakage Circuit Breaker(ELCB) 30A

 

 

 

Electric wire

Below 20m

2.5mm2

Below 50m

4mm2

 

 

 

 

Allowable voltage

198V~242V

 

 

Min. size of electric wires from/to the indoor/

0.75mm2

outdoor units

 

 

 

 

You must compress the solderless ring to the cable and then connect it to the main power terminal.

Solderless ring selection

Thickness of cable(mm2)

B(mm)

d2(mm)

Silver solder

2.5

Less than 9.5

More than 4.5

 

4

Less than 9.5

More than 4.5

 

36_ installation part

Image 36
Contents Air Conditioner DB98-33838A1Features of your new air conditioner Strong Turbo/Long FunctionLook for Everywhere Serial #Safety information Safety InformationImportant safety symbols and precautions DeathDo not yank the power cable with hands Ensure no water gets into the air conditionerPotential risk of injury or electric shock Do not open the front panel during operation Do not drink drain water coming out of the air conditionerDo not place any objects, especially containers with liquid Insufficient ventilation may result in poor performance Safety information Contents Viewing your air conditioner Checking the Indoor Unit and DisplayMain parts To open the panelControl Panel Checking the Remote controller Remote controller display Using the remote controllerInstalling the batteries Close the cover by place it back to its original positionSelecting Operation Mode Press the Power button on the remote controllerOperating basic function Turning the AIR Conditioner on and OFFCool Dry Fan Fan Set the fan speedUsing advanced functions Using the Turbo functionTo deactivate Turbo function Using the Long Function To deactivate Long functionAdjusting the AIR Flow Direction Vertical air flowAir flow can be directed to your desired position Horizontal air flow Setting Timer To deactivate the On TimerOn Timer To deactivate the Off Timer Off TimerTo deactivate the timer combination Combining On Timer and Off TimerPreset time of On Timer is shorter than Off Preset time of On Timer is longer than OffUsing the AIR Conditioner with the Control Panel When the air conditioner is on or off Locking the Control PanelCleaning and maintaining the air conditioner Cleaning the ExteriorCleaning the Filter Air filterMaintaining Your AIR Conditioner Periodical checksType Description Every Once a MonthsStoring the remote controller Internal protections via the unit control systemType Description Air conditioner does not start operating immediatelyTroubleshooting AppendixOperation Ranges Condensation may occur on the indoor unit21˚C to 54˚C On the floorSafety Precautions Power supply line, fuse or circuit breaker Accessory Parts List Part NameSelection of Installation Place Top viewPower Electric wire Below 20m 5mm Below 50m 4mm Allowable voltageElectrical Work Circuit BreakerIndoor unit Outdoor UnitScrew Tightening torque kgf cm Installation Method Installation ProceduresAnchor bolt fixing dimensions Outdoor UnitIndoor unit Indoor unit Outdoor UnitCut the pipe using the pipe cutter Connection of Refrigerant PipingOuter DiameterD Amm Drilling a Hole in the Wall  Drill a hole of 60mm in diameter to the outsideDrain Hose Fixing the Indoor UnitInsulation Foamed Polyethylene Air Purge ※ Be sure that all valve cocks are closedVacuum PumpOutside temperature 35C Refrigerant ChargingRefill the refrigerant slowly checking the pressure Stop operationCheck and Test Operation CheckIs grounding properly made? Pump Down Procedure When removing the product Test OperationPacking and Unpacking Guide Indoor unitCushion-top  Packing case  Outdoor unit  Howto connectyour extended power cables Insulation tapeQuestions or COMMENTS? 021-8255183-2255 444 77 Samsung