Howto connectyour extended power cables

Items to prepare

(compressor and insulation tape should be prepared by an installation technician.)

Tools

Crimping plier

Connection sleeve (mm)

Insulation tape

Contraction tube (mm)

Spec

MH-14

20xØ7.0(HxOD)

Width 18mm

50xØ8.0(LxOD)

Shape

 

 

 

 

1.As shown in the figure, peel off the shields from the rubber/wire of the power cable.

- Peel off 20 mm of the wire shields of the tube installed already.

After peeling off the tube wire, you must insert a contraction tube.

2.Insert both sides of core wire of the power cable into the connection sleeve.

3.Using a compressor, compress the two points and flip it over and compress another two points in the same location.

-The compression dimension should be 8.0.

-After compressing it, pull both sides of the wire to make sure it is firmly pressed.

(Unit: mm)

Power cable (provided by us)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

 

20

 

20

60 120

180

Wire tube power cable

20

Connection sleeve

Comp. dim.

Compress it 4 times

5mm

4.Wrap it with the insulation tape twice and position your contraction tube in the middle of the insulation tape.

5.Apply heat to the contraction tube to contract it.

6.After tube contraction work is completed, wrap it with the insulation tape to finish.

Insulation tape

40mm Contraction tube

Insulation tape

In case of extending the electric wire, please DO NOT use a round-shaped pressing socket.

- Incomplete wire connections can cause electric shock or a fire

installation part _49

Image 49
Contents DB98-33838A1 Air ConditionerStrong Turbo/Long Function Features of your new air conditionerLook for Everywhere Serial #Safety Information Safety informationImportant safety symbols and precautions DeathEnsure no water gets into the air conditioner Do not yank the power cable with handsPotential risk of injury or electric shock Do not drink drain water coming out of the air conditioner Do not open the front panel during operationDo not place any objects, especially containers with liquid Insufficient ventilation may result in poor performance Safety information Contents Checking the Indoor Unit and Display Viewing your air conditionerMain parts To open the panelControl Panel Checking the Remote controller Using the remote controller Remote controller displayInstalling the batteries Close the cover by place it back to its original positionPress the Power button on the remote controller Selecting Operation ModeOperating basic function Turning the AIR Conditioner on and OFFCool Dry Fan Set the fan speed FanUsing the Turbo function Using advanced functionsTo deactivate Turbo function To deactivate Long function Using the Long FunctionVertical air flow Adjusting the AIR Flow DirectionAir flow can be directed to your desired position Horizontal air flow To deactivate the On Timer Setting TimerOn Timer Off Timer To deactivate the Off TimerCombining On Timer and Off Timer To deactivate the timer combinationPreset time of On Timer is shorter than Off Preset time of On Timer is longer than OffUsing the AIR Conditioner with the Control Panel Locking the Control Panel When the air conditioner is on or offCleaning the Exterior Cleaning and maintaining the air conditionerCleaning the Filter Air filterPeriodical checks Maintaining Your AIR ConditionerType Description Every Once a MonthsInternal protections via the unit control system Storing the remote controllerType Description Air conditioner does not start operating immediatelyAppendix TroubleshootingCondensation may occur on the indoor unit Operation Ranges21˚C to 54˚C On the floorSafety Precautions Power supply line, fuse or circuit breaker Part Name Accessory Parts ListTop view Selection of Installation PlaceElectric wire Below 20m 5mm Below 50m 4mm Allowable voltage PowerElectrical Work Circuit BreakerOutdoor Unit Indoor unitScrew Tightening torque kgf cm Installation Procedures Installation MethodAnchor bolt fixing dimensions Outdoor UnitIndoor unit Outdoor Unit Indoor unitConnection of Refrigerant Piping Cut the pipe using the pipe cutterOuter DiameterD Amm  Drill a hole of 60mm in diameter to the outside Drilling a Hole in the WallFixing the Indoor Unit Drain HoseInsulation Foamed Polyethylene ※ Be sure that all valve cocks are closed Air PurgeVacuum PumpRefrigerant Charging Outside temperature 35CRefill the refrigerant slowly checking the pressure Stop operationCheck Check and Test OperationIs grounding properly made? Test Operation Pump Down Procedure When removing the productIndoor unit Packing and Unpacking GuideCushion-top  Packing case  Outdoor unit  Insulation tape Howto connectyour extended power cables021-8255 Questions or COMMENTS?183-2255 444 77 Samsung