Installing and connecting the drain hose of the indoor unit
• If you do not use the other drain hose hole, block it with a rubber stopper.
4. When extending the Drain Hose, hold the end of Drain Hose and Extended Hose, |
| |
rotate and insert the drain hose into Extended hose for 15~20 mm. Make sure | Drain hose hole | |
the two hoses are firmly connected, there is no water leakage. | ||
|
5.Connect the Drain Hose after using Foam Insulation to wrap the Extended Hose. Then, Use vinyl tape to wrap the each side of connection by 20mm .
|
| 15~20 mm | 20mm | 20mm | |
|
| or more | or more | ||
| Drain hose Extension | Drain hose | Extension |
|
|
| drain hose |
|
| ||
|
|
| drain hose | Vinyl Tape | Foam Insulation |
|
|
|
| ||
6. | Pass the drain hose under the refrigerant pipe, keeping the drain | Shield |
| ||
| hose tight. |
|
|
| |
|
|
|
|
| |
7. | Pass the drain hose through the hole in the wall. Check if it slants |
|
| ||
| downwards as seen in the picture. |
|
|
|
|
8. | Using natural drainage method, check the drainage is normal. | Drain hose | Extension drain hose | ||
• The hose will be fixed permanently into position after finishing the installation and the gas leak test; refer to page
40 for further details.
• Make sure the installed direction of the drain hose is correct. Inadequate installation may cause condensate water leakage.
• If the drain hose is routed inside the room, insulate the hose so that dripping condensation does not damage the furniture or floors.
•DO NOT WALL UP THE DRAIN HOSE CONNECTION !
Drain hose connection must be easy accessible and serviceable.
Changing direction of the drain hose
Change the direction only when it is necessary.
1. | Detach the rubber cap with the plier. | Screw hole |
2. | Detach the drain hose by pulling it and turning to the left. | Screw |
| ||
3. | Insert the drain hose by fixing it with the screw into the groove of the drain | Drain hose |
| hose and the outlet of the drain pan. | |
|
| |
4. | Attach the rubber cap with a screwdriver by turning it to the right until it |
|
| fixes to the end of the groove. | Drain pan outlet |
|
|
5. Check for leakage on both side of the drain outlet. |
| |
Pour the water in direction of arrow. | Direction of the drained water | Rubber cap |
|
| |
•Make sure the indoor unit is in upright position when you pour water to check for leakage.
Make sure that the water does not overflow onto the electrical part.
36
![]()
P18���������![]()
.indd