InstallAA ing and connecting the assembly pipe of the indoor unit

Connect indoor and outdoor units with field-supplied copper pipes by means of flare connections. Use insulated seamless refrigeration grade pipe only, (Cu DHP type according to ISO1337), degreased and deoxidized, suitable for operating pressures of at least 4200 kPa and for burst pressure of at least 20700 kPa. Under no circumstances must sanitary type copper pipe be used.

There are 2 refrigerant pipes of different diameters:

The smaller one is for the liquid refrigerant

The larger one is for the gas refrigerant

A short pipe is already fitted to the air conditioner. You may need to extend the pipe using the assembly pipe (optional).

The connection procedure for the refrigerant pipe varies

 

 

according to the exit position of the pipe when facing the wall:

A

B

• Right(A)

 

 

• Left(B)

 

C

• Underside(C)

 

 

 

• Rear

 

 

ENGLISH

1.Cut out the appropriate knock-out piece (A, B, C) on the rear of the indoor unit unless you connect the pipe directly from the rear.

2.Smooth the cut edges.

3.Remove the protection caps of the pipes and connect the assembly pipe to each pipe. Tighten the nuts first with your hands, and then with a torque wrench, applying the following torque:

• If you want to shorten or extend the pipes, refer to page35~36.

4.Cut off the remaining foam insulation.

5.If necessary, bend the pipe to fit along the bottom of the indoor unit. Then pull it out through the appropriate hole.

The pipe should not project from the rear of the indoor unit.

The bending radius should be 100 mm or more.

Outer Diameter

Torque (kgf•cm)

 

 

ø6.35 mm

140~170

ø9.52 mm

250~280

ø12.70 mm

380~420

ø15.88 mm

440~480

ø19.05 mm

990~1210

ø22.23 mm

990~1210

6.Pass the pipe through the hole in the wall.

7.For further details on how to connect to the outdoor unit and purge the air, refer to page 38~39.

• The pipe will be insulated and fixed permanently into position after finishing the installation and the gas leak test;

refer to page 40 for further details.

• Tighten the flare nut with torque wrench according to specified method.

If the flare nut is over-tightened, the flare may break and cause refrigerant gas leakage.

DO NOT WALL UP THE PIPE CONNECTION !

All refrigerant pipe connection must be easy accessible and serviceable.

33

UMG_AQ&AS18V@_IBIM_34038A_E--P14P18���������.indd 33

2013-3-18 11:00:18

Image 33
Contents English Contents Important safety symbols and precautions SafetAA y precautionsFollow directions Wall socketFor Using For Cleaning Operation ranges ChecAA king before useSet temperature Mode indicator Auto clean indicatorMode indicator Room temperature ChecAA king the name of the partsRemote controller buttons ChecAA king the remote controllerBattery changing time Remote controller displayStoring the remote controller Inserting the batteriesBasicAA function Press the button to set the desired fan speed Press the button to adjust the temperaturePress the Air swing button on the remote controller Using the Turbo functionAdjusA ting the air flow direction Vertical air flowPress the button on the remote controller AA modePress the Set/Cancel button to active it on Set Off timerSettinAA g the On/Off timer Press the On Timer/Off Timer buttonPress the On Timer/Off Timer button to set the time From the moment you have set the timer If the air conditioner is on If the air conditioner is offTurn off automatically Using the dlight Cool function Using the Smart Saver functionUsing the Virus Doctor function Using the Quiet function UsingAA the Auto Clean functionWhen the air conditioner is turned on RunsCleaning the outdoor unit heat exchanger Cleaning the indoor unitOpening the panel Heat exchangerRemoving the Air filter Cleaning the air filterOpen the panel and put the Air filter out Dry the Air filter in a ventilated areaClose the front panel Deodorizing and Bio filterPeriodical checks MainAA taining the air conditionerTroubAA leshooting Troubleshooting Flow movement changes. It is normalConnection General information Safety precautionsInstalling the unit Choosing the installation locationPower supply line, fuse or circuit breaker  a place where the air filter can be replaced easilyWhere sulfide gas exists Outdoor UnitModel When installing more than 1 outdoor unit ChoosingAA the installation locationWhen the air outlet is towards the wall  Figure DescriptionAccessories Accessories in the indoor unit caseAccessories in the outdoor unit case Optional accessories Fixing the installation plateTools required for installation General Tools Tools for test operationsConnecting the assembly cable Cable specificationConnecting the cable Each wire is labeled with the corresponding terminal number Extend the assembly cable if necessaryCut off the remaining foam insulation Smooth the cut edgesCutting or extending the pipe PurgiAA ng the indoor unitUnscrew the caps at the end of each pipe Put a flare nut slightly into the pipe and modify the flareOuter Diameter Drain hose installationChanging direction of the drain hose AQseries Purging the connected pipesConnect a drain hose to the drain plug Ensure that condensation draining is adequateGas service port as seen in the picture Adding RefrigerantIf you use a pipe shorter than 4 or 5m Fixing the indoor unit in place PerfoAA rming the gas leak testsFixinAA g the outdoor unit in place Outdoor unit installed on the wall by rackPress the Power button to stop the operation Press the Mode button to select Cool modeCheck the followings Press the Air swing button and check the followingApply heat to the contraction tube to contract it AAHow to connect your extended power cablesAfter tube contraction work is completed, wrap it with Insulation tape to finishAQ18VBFUMG AQ24VBFUMG TechnAA ical SpecificationsQuestions or COMMENTS? Air Conditioner