Samsung AS24VBFNUMG, AS18VBFNUMG manual Purging the connected pipes, AQseries

Page 37

AAInstalling and connecting the drain hose of the outdoor unit

(AQseries)

While heating, ice may accumulate. During the process of defrosting, check if condensation draining is adequate. For adequate draining, do the following:

1. Insert the drain plug into the drain hole on the underside of the outdoor unit.

• To avoid drain plug from contacting the ground, secure gap between the ground and the bottom surface of the outdoor unit.

 

Drain hole

Drain plug

 

 

2. Connect a drain hose to the drain plug.

Bottom surface of outdoor unit

 

Drain hole

 

 

Drain plug

Drain hose

3. Ensure that condensation draining is adequate.

 

Snow-proof hood

 

 

• In areas with heavy snow fall, piled snow could block the air intake.

 

 

To avoid this incident, install a frame that is higher than estimated snow

 

 

fall. In addition, install a snow-proof hood to avoid snow from piling on the

 

outdoor unit.

Estimated

 

snow fall Frame

 

 

Ground

Purging the connected pipes

The outdoor unit is loaded with sufficient R-22 refrigerant .You should purge the air in the indoor unit and in the pipe.If air remains in the refrigerant pipes, it affects the compressor. It may cause reduction of cooling capacity and malfunction.

• When installing, make sure there is no leakage. When recovering the refrigerant, ground the compressor first before removing the connection pipe. If the refrigerant pipe is not properly connected and the compressor works with the service valve open, the pipe inhales the air and it makes the pressure inside of the refrigerant cycle abnormally high. It may cause explosion and injury.

ENGLISH

1.Connect each assembly pipe to the appropriate valve on the outdoor unit and tighten the flare nut.

2.Tighten the flare nut first with your hands, and then with a torque wrench, applying the following torque:

• Excessive torque can be cause of gas leakage.

• Make the electrical connection and leave the system into“stand by mode”. Do not turn on the system!

This is necessary for better vacuum operation (full OPEN position of Electronic Expansion Valve - EEV -).

Outdoor unit

Indoor unit

 

Gas pipe side

 

Liquid pipe side

Outer Diameter

Torque (kgf•cm)

ø6.35 mm

140~170

ø9.52 mm

250~280

ø12.70 mm

380~420

ø15.88 mm

440~480

ø19.05 mm

990~1210

ø22.23 mm

990~1210

37

UMG_AQ&AS18V@_IBIM_34038A_E--P14P18���������.indd 37

2013-3-18 11:00:19

Image 37
Contents English Contents Important safety symbols and precautions SafetAA y precautionsFollow directions Wall socketFor Using For Cleaning Operation ranges ChecAA king before useSet temperature Mode indicator Auto clean indicatorMode indicator Room temperature ChecAA king the name of the partsRemote controller buttons ChecAA king the remote controllerBattery changing time Remote controller displayStoring the remote controller Inserting the batteriesBasicAA function Press the button to set the desired fan speed Press the button to adjust the temperaturePress the Air swing button on the remote controller Using the Turbo functionAdjusA ting the air flow direction Vertical air flowPress the button on the remote controller AA modePress the Set/Cancel button to active it on Set Off timerPress the On Timer/Off Timer button SettinAA g the On/Off timerPress the On Timer/Off Timer button to set the time If the air conditioner is on If the air conditioner is off From the moment you have set the timerTurn off automatically Using the dlight Cool function Using the Smart Saver functionUsing the Virus Doctor function Using the Quiet function UsingAA the Auto Clean functionWhen the air conditioner is turned on RunsCleaning the outdoor unit heat exchanger Cleaning the indoor unitOpening the panel Heat exchangerRemoving the Air filter Cleaning the air filterOpen the panel and put the Air filter out Dry the Air filter in a ventilated areaClose the front panel Deodorizing and Bio filterPeriodical checks MainAA taining the air conditionerTroubAA leshooting Flow movement changes. It is normal TroubleshootingConnection General information Safety precautionsInstalling the unit Choosing the installation locationPower supply line, fuse or circuit breaker  a place where the air filter can be replaced easilyOutdoor Unit Where sulfide gas existsModel When installing more than 1 outdoor unit ChoosingAA the installation locationWhen the air outlet is towards the wall  Figure DescriptionAccessories in the indoor unit case AccessoriesAccessories in the outdoor unit case Optional accessories Fixing the installation plateTools required for installation General Tools Tools for test operationsCable specification Connecting the assembly cableConnecting the cable Each wire is labeled with the corresponding terminal number Extend the assembly cable if necessaryCut off the remaining foam insulation Smooth the cut edgesCutting or extending the pipe PurgiAA ng the indoor unitUnscrew the caps at the end of each pipe Put a flare nut slightly into the pipe and modify the flareOuter Diameter Drain hose installationChanging direction of the drain hose AQseries Purging the connected pipesConnect a drain hose to the drain plug Ensure that condensation draining is adequateAdding Refrigerant Gas service port as seen in the pictureIf you use a pipe shorter than 4 or 5m Fixing the indoor unit in place PerfoAA rming the gas leak testsFixinAA g the outdoor unit in place Outdoor unit installed on the wall by rackPress the Power button to stop the operation Press the Mode button to select Cool modeCheck the followings Press the Air swing button and check the followingApply heat to the contraction tube to contract it AAHow to connect your extended power cablesAfter tube contraction work is completed, wrap it with Insulation tape to finishAQ18VBFUMG AQ24VBFUMG TechnAA ical SpecificationsQuestions or COMMENTS? Air Conditioner