5. Check if you flared the pipe correctly (see examples of incorrectly flared pipes below).

Correct

Inclined

Damaged

Cracked

Uneven

 

 

Surface

 

Thickness

6.Align the pipes to connect them easily. Tighten the flare nuts first with your hands, and then with a torque wrench, applying the following torque:

ENGLISH

Flare nut

 

 

 

 

 

 

 

 

 

 

 

Indoor outlet

 

pipe

 

 

 

 

 

Connecting pipe

Outer Diameter

Torque (kgf•cm)

ø6.35 mm

140~170

ø9.52 mm

250~280

ø12.70 mm

380~420

ø15.88 mm

440~480

ø19.05 mm

990~1210

ø22.23 mm

990~1210

• Excessive torque can be cause of gas leakage. In case brazing the pipe, the nitrogen gas must be blown into the

pipe (50 Pa). The joint must be accessible and serviceable.

7. For further details on how to connect to the outdoor unit and purge the air, refer to page 38~39.

• Tighten the flare nut with torque wrench according to specified method.

If the flare nut is over-tightened, the flare may break and cause refrigerant gas leakage.

Installing and connecting the drain hose of the indoor unit

When installing the drain hose for the indoor unit, check if condensation draining is adequate.

When passing the drain hose through the 65-mm hole drilled in the wall, check the followings:

Wall

Indoor unit

Drain hose

The drain hose must NOT

The end of the drain hose must NOT

slant upwards.

be placed under water.

The drain hose must not be bent.

5cm

less

Keep a clearance of at least 5cm between the end of the drain hose and the ground.

Ditch

Do not place the end of the drain hose in a hollow.

Drain hose installation

1.If necessary, connect the 2-meter extension drain hose to the drain hose.

2.If you use the extension drain hose, insulate the inside of the extension drain hose with a shield.

3. Fit the drain hose into 1 of 2 drain hose holes, then fix the end of the drain hose tightly with a clamp.

35

 

UMG_AQ&AS18V@_IBIM_34038A_E--P14P18���������.indd 35

2013-3-18 11:00:18

Image 35
Contents English Contents Wall socket SafetAA y precautionsImportant safety symbols and precautions Follow directionsFor Using For Cleaning Operation ranges ChecAA king before useChecAA king the name of the parts Mode indicator Auto clean indicatorSet temperature Mode indicator Room temperatureRemote controller buttons ChecAA king the remote controllerInserting the batteries Remote controller displayBattery changing time Storing the remote controllerBasicAA function Press the button to set the desired fan speed Press the button to adjust the temperatureVertical air flow Using the Turbo functionPress the Air swing button on the remote controller AdjusA ting the air flow directionSet Off timer AA modePress the button on the remote controller Press the Set/Cancel button to active it onPress the On Timer/Off Timer button to set the time SettinAA g the On/Off timerPress the On Timer/Off Timer button Turn off automatically From the moment you have set the timerIf the air conditioner is on If the air conditioner is off Using the dlight Cool function Using the Smart Saver functionUsing the Virus Doctor function Runs UsingAA the Auto Clean functionUsing the Quiet function When the air conditioner is turned onHeat exchanger Cleaning the indoor unitCleaning the outdoor unit heat exchanger Opening the panelDry the Air filter in a ventilated area Cleaning the air filterRemoving the Air filter Open the panel and put the Air filter outClose the front panel Deodorizing and Bio filterPeriodical checks MainAA taining the air conditionerTroubAA leshooting Connection TroubleshootingFlow movement changes. It is normal General information Safety precautions a place where the air filter can be replaced easily Choosing the installation locationInstalling the unit Power supply line, fuse or circuit breakerModel Where sulfide gas existsOutdoor Unit  Figure Description ChoosingAA the installation locationWhen installing more than 1 outdoor unit When the air outlet is towards the wallAccessories in the outdoor unit case AccessoriesAccessories in the indoor unit case Tools for test operations Fixing the installation plateOptional accessories Tools required for installation General ToolsConnecting the cable Connecting the assembly cableCable specification Each wire is labeled with the corresponding terminal number Extend the assembly cable if necessaryCut off the remaining foam insulation Smooth the cut edgesPut a flare nut slightly into the pipe and modify the flare PurgiAA ng the indoor unitCutting or extending the pipe Unscrew the caps at the end of each pipeOuter Diameter Drain hose installationChanging direction of the drain hose Ensure that condensation draining is adequate Purging the connected pipesAQseries Connect a drain hose to the drain plugIf you use a pipe shorter than 4 or 5m Gas service port as seen in the pictureAdding Refrigerant Fixing the indoor unit in place PerfoAA rming the gas leak testsFixinAA g the outdoor unit in place Outdoor unit installed on the wall by rackPress the Air swing button and check the following Press the Mode button to select Cool modePress the Power button to stop the operation Check the followingsInsulation tape to finish AAHow to connect your extended power cablesApply heat to the contraction tube to contract it After tube contraction work is completed, wrap it withAQ18VBFUMG AQ24VBFUMG TechnAA ical SpecificationsQuestions or COMMENTS? Air Conditioner