Samsung AR18NVPXCWK/MG manual Optional Changing the direction of the drain hose

Page 44

Step 2.7 Optional: Changing the direction of the drain hose

Drain pan outlet

Rubber cap

Pour water in the direction of arrow.

<Front view>

Direction of the drained water

Step 2.8 Installing and connecting the assembly pipes to the refrigerant pipes (assembly pipe)

Connect indoor and outdoor units with field-supplied copper pipes by means of flare connections. Use insulated seamless refrigeration grade pipe only, (Cu DHP type according to ISO1337), degreased and deoxidized, suitable for operating pressures of at least 4200 kPa and for burst pressure of at least 20700 kPa. Under no circumstances must sanitary type copper pipe be used.

There are 2 refrigerant pipes of different diameters:

The smaller one is for the liquid refrigerant

The larger one is for the gas refrigerant

A short liquid refrigerant pipe and a short gas refrigerant pipe are already fitted to the air conditioner. The connection procedure for the refrigerant pipes varies according to the exit position

of each pipe when facing the wall:

Installation

<Side view>

CAUTION

Make sure that the indoor unit is in upright position when you pour water to check for leakage. Make sure that the water does not overflow onto the electrical part.

Left

Right

Underside

<Front view>

Rear right or left

<Side view>

1Cut out the appropriate knock-out piece (A, B, C) on the rear of the indoor unit unless you connect the pipe directly from the rear.

2Smooth the cut edges.

3Remove the protection caps of the pipes and connect the assembly pipe to each pipe. Tighten the nuts first with your hands, and then with a torque wrench, applying the following torque:

44English

Image 44
Contents Airconditioner Contents Correct disposal of batteries in this product Failing to do so may result in electric shock or fire This may result in electric shock or fireFor Power Supply Do not touch the circuit breakerwith wet hands This may result in electric shockThis may result in electric shock or burns This may result in children seriously injuring themselvesDo not place objects or devices under the indoor unit Do not operate the appliance with wet handsDo not drink the water from the air conditioner Do not touch the pipes connected with the productFor Cleaning Do not clean the inside of the air conditioner by yourselfDisplay Room temperature sensor Inside IonizerIndoor Unit Overview Remote Control Overview Inserting batteriesOperation modes Remote Control OperationControlling temperature Controlling fan speed Controlling air flow directionCool mode Cooling OperationStep cooling function ComfortableWind-Free Cooling function Dry mode Dehumidifying OperationAir Purifying Operation Ionizer functionQuick Smart Features Auto modeFan mode Fast functionSelect Beep Comfort functionBeep sound function Quiet function Display lighting functionWi-Fi function Samsung Connect App Energy-Saving Operation Electricity consumption checkSingle userfunction Operation Select UsageTimed on/Timed off function Cool mode Good’sleep functionRunning Auto clean To deactivate the Auto clean functionTo cancel the Auto clean operation MethodDo not clean the display by using alkaline detergent Cleaning the filterResetting the filter-cleaning reminder Tip on cleaning the Wind-Free panel Gently push the air flow blade Hold and pull both sidesGently push the air flow blade With your handTroubleshooting Problem SolutionIndicator blinks Check whether the drains are clean. Clean them regularlyAn error is indicated Sure to pass the error code to the service centreTechnical Specifications 27˚C19˚C 35˚CConnecting network Connecting the wireless IP routerwith an air conditionerThis Wi-Fi Aircon support only below three encryption Downloading the Samsung Connect appSpecifications Registering Samsung accountLog in with a Samsung account Registering your air conditioner to the Samsung Connect appControlling the air conditionerwith Samsung Connect App Troubleshooting Open Source AnnouncementSafety Information on Installation General informationPower supply line, fuse, or circuit breaker Install the unit in a place where water can drain smoothlyChoosing the installation location PreparationMinimum clearances for the outdoor unit CasesPacking and Unpacking Unit mmIndoor unit Outdoor unitOptional accessories AccessoriesAccessories in the indoor unit package Accessories in the outdoor unit package Drilling a hole through the wallTools General tools Tools for test operationTaping the pipes, cables, and drain hose Indoor Unit Installation Installation plateDisassembling the cover panel Remove the cap screws, then the screwsConnecting the Power and communication cables assembly cable Optional Extending the power cable Installing and connecting the drain hose Install the drain hoseOptional Extending the drain hose FireEach pipe when facing the wall Optional Changing the direction of the drain hoseShortening or extending the refrigerant pipes assembly pipe Pass the pipe through the hole in the wallWhen fixing the indoor unit on a window frame 10 Fixing the installation plateWhen fixing the indoor unit on a wall 11 Fixing the indoor unit to the installation plate When fixing the indoor unit on a gypsum boardFix the installation plate without inclining to one side 12 Assembling the cover panelOutdoor Unit Installation Fixing the outdoor unit in placeRefrigerant pipes Optional Fixing the outdoor unit to a wall with a rackEvacuating the air Cooling capacity and malfunction. Use a vacuum pumpAdding refrigerant SiphonPerforming the gas leak tests Installation InspectionRunning the Smart Install mode Error between Power cable or communicationMotor Connector Remove foreign substance. Check Blocking error OpenCheck the following Strength of the installation site Performing final check and trial operationPumping down for removing the product Disconnect the pipesQuestions or COMMENTS?