Installation

3Open the valve of the low pressure side of manifold gauge anticlockwise.

4Evacuate the air in the connected pipes using the vacuum pump for about 15 minutes.

Make sure that pressure gauge shows -0.1 MPa (-76 cmHg, 5 torr) after about 10 minutes. This procedure is very important to avoid a gas leak.

Close the valve of the low pressure side of manifold gauge clockwise.

Turn off the vacuum pump.

Check for 2 minutes if there is any pressure change.

Remove the hose of the low pressure side of manifold gauge.

5Set a valve cork of liquid and gas service port to the open position.

Step 3.4 Adding refrigerant

If you use a pipe longer than the length specified in the piping codes and standards, you must add 15g of refrigerant R-410A for each extra metre. If you use a pipe shorter than the length specified in the piping codes and standards, the evacuating time is normal. Refer to the Service Manual for further details.

CAUTION

The remaining air in the Refrigeration cycle, which contains moisture, may cause malfunction of the compressor.

Always contact the service centre or a professional installation agency for product installation.

R-410A is a mixed type of refrigerant. It is necessary for recharging under conditions of liquid. When recharging refrigerant from the refrigerant cylinder to the equipment, take the following instructions:

Before recharging, check whether the cylinder has a siphon or not. There are two ways to recharge the refrigerant:

 

 

Siphon

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Charge the refrigerant

Charge the refrigerant turning

standing the cylinder upright.

the cylinder upside down.

<Cylinder with siphon>

<Cylinder without siphon>

NOTE

If R-410A refrigerant is charged with gas, the composition of the charged refrigerant changes and the characteristics of the equipment vary.

During the measuring operation of refrigerant quantity added, use electronic scales. If cylinder doesn't have siphon, upset it.

50English

Image 50
Contents Airconditioner Contents Correct disposal of batteries in this product Failing to do so may result in electric shock or fire This may result in electric shock or fireFor Power Supply This may result in electric shock or burns Do not touch the circuit breakerwith wet handsThis may result in electric shock This may result in children seriously injuring themselvesDo not drink the water from the air conditioner Do not place objects or devices under the indoor unitDo not operate the appliance with wet hands Do not touch the pipes connected with the productFor Cleaning Do not clean the inside of the air conditioner by yourselfDisplay Room temperature sensor Inside IonizerIndoor Unit Overview Remote Control Overview Inserting batteriesOperation modes Remote Control OperationControlling temperature Controlling fan speed Controlling air flow directionStep cooling function Cool modeCooling Operation ComfortableWind-Free Cooling function Air Purifying Operation Dry modeDehumidifying Operation Ionizer functionFan mode Quick Smart FeaturesAuto mode Fast functionSelect Beep Comfort functionBeep sound function Quiet function Display lighting functionWi-Fi function Samsung Connect App Single userfunction Energy-Saving OperationElectricity consumption check Operation Select UsageTimed on/Timed off function Cool mode Good’sleep functionTo cancel the Auto clean operation Running Auto cleanTo deactivate the Auto clean function MethodDo not clean the display by using alkaline detergent Cleaning the filterResetting the filter-cleaning reminder Gently push the air flow blade Tip on cleaning the Wind-Free panelGently push the air flow blade Hold and pull both sides With your handTroubleshooting Problem SolutionAn error is indicated Indicator blinksCheck whether the drains are clean. Clean them regularly Sure to pass the error code to the service centre19˚C Technical Specifications27˚C 35˚CThis Wi-Fi Aircon support only below three encryption Connecting networkConnecting the wireless IP routerwith an air conditioner Downloading the Samsung Connect appLog in with a Samsung account SpecificationsRegistering Samsung account Registering your air conditioner to the Samsung Connect appControlling the air conditionerwith Samsung Connect App Troubleshooting Open Source AnnouncementSafety Information on Installation General informationPower supply line, fuse, or circuit breaker Install the unit in a place where water can drain smoothlyMinimum clearances for the outdoor unit Choosing the installation locationPreparation CasesIndoor unit Packing and UnpackingUnit mm Outdoor unitOptional accessories AccessoriesAccessories in the indoor unit package Tools General tools Accessories in the outdoor unit packageDrilling a hole through the wall Tools for test operationTaping the pipes, cables, and drain hose Disassembling the cover panel Indoor Unit InstallationInstallation plate Remove the cap screws, then the screwsConnecting the Power and communication cables assembly cable Optional Extending the power cable Optional Extending the drain hose Installing and connecting the drain hoseInstall the drain hose FireEach pipe when facing the wall Optional Changing the direction of the drain hoseShortening or extending the refrigerant pipes assembly pipe Pass the pipe through the hole in the wallWhen fixing the indoor unit on a window frame 10 Fixing the installation plateWhen fixing the indoor unit on a wall Fix the installation plate without inclining to one side 11 Fixing the indoor unit to the installation plate When fixing the indoor unit on a gypsum board 12 Assembling the cover panelRefrigerant pipes Outdoor Unit InstallationFixing the outdoor unit in place Optional Fixing the outdoor unit to a wall with a rackEvacuating the air Cooling capacity and malfunction. Use a vacuum pumpAdding refrigerant SiphonPerforming the gas leak tests Installation InspectionRunning the Smart Install mode Motor Connector Remove foreign substance. Check Error betweenPower cable or communication Blocking error OpenPumping down for removing the product Check the following Strength of the installation sitePerforming final check and trial operation Disconnect the pipesQuestions or COMMENTS?