Samsung AR18NVPXCWK/MG Evacuating the air, Cooling capacity and malfunction. Use a vacuum pump

Page 49

Control box

Remove the screw for the control box cover

Remove the gas and liquid

For connecting the

service port caps

refrigerant pipes

Gas service port <Low pressure>

CAUTION

When installing, make sure there is no leakage.

When recovering the refrigerant, ground the compressor first before removing the connection pipe. If the refrigerant pipe is not properly connected and the compressor works with the stop valve open, the pipe inhales the air and it makes the pressure inside of the refrigerant cycle abnormally high. It may cause explosion and injury.

1Leave the system in the standby mode.

WARNING

Do not turn on the system! This is necessary for better vacuum operation (full OPEN position of Electronic Expansion Valve).

2Connect the charging hose of the low pressure side of manifold gauge to a gas service port as seen in the picture.

Liquid service port

Connect the gas and liquid

<High pressure>

refrigerant pipes

Step 3.3 Evacuating the air

The outdoor unit is loaded with sufficient R-410A refrigerant. Do not vent R-410A into atmosphere: it is a fluorinated greenhouse gas, covered by Kyoto Protocol, with a Global Warming Potential (GWP) = 2088. You should evacuate the air in the indoor unit and in the pipe. If air remains in the refrigerant pipes, it affects the compressor. It may cause reduction

of cooling capacity and malfunction. Use a vacuum pump.

3

Valve

15 minutes

4

Vacuum

Pump

(Backward ￿owing prevention)

Liquid service port <Low pressure>

5

Liquid service port <High pressure>

Installation

English 49

Image 49
Contents Airconditioner Contents Correct disposal of batteries in this product This may result in electric shock or fire Failing to do so may result in electric shock or fireFor Power Supply This may result in electric shock Do not touch the circuit breakerwith wet handsThis may result in electric shock or burns This may result in children seriously injuring themselvesDo not operate the appliance with wet hands Do not place objects or devices under the indoor unitDo not drink the water from the air conditioner Do not touch the pipes connected with the productDo not clean the inside of the air conditioner by yourself For CleaningIndoor Unit Overview Room temperature sensor Inside IonizerDisplay Inserting batteries Remote Control OverviewControlling temperature Remote Control OperationOperation modes Controlling air flow direction Controlling fan speedCooling Operation Cool modeStep cooling function ComfortableWind-Free Cooling function Dehumidifying Operation Dry modeAir Purifying Operation Ionizer functionAuto mode Quick Smart FeaturesFan mode Fast functionBeep sound function Comfort functionSelect Beep Display lighting function Quiet functionWi-Fi function Samsung Connect App Electricity consumption check Energy-Saving OperationSingle userfunction Operation Select UsageTimed on/Timed off function Good’sleep function Cool modeTo deactivate the Auto clean function Running Auto cleanTo cancel the Auto clean operation MethodResetting the filter-cleaning reminder Cleaning the filterDo not clean the display by using alkaline detergent Gently push the air flow blade Hold and pull both sides Tip on cleaning the Wind-Free panelGently push the air flow blade With your handProblem Solution TroubleshootingCheck whether the drains are clean. Clean them regularly Indicator blinksAn error is indicated Sure to pass the error code to the service centre27˚C Technical Specifications19˚C 35˚CConnecting the wireless IP routerwith an air conditioner Connecting networkThis Wi-Fi Aircon support only below three encryption Downloading the Samsung Connect appRegistering Samsung account SpecificationsLog in with a Samsung account Registering your air conditioner to the Samsung Connect appControlling the air conditionerwith Samsung Connect App Open Source Announcement TroubleshootingGeneral information Safety Information on InstallationInstall the unit in a place where water can drain smoothly Power supply line, fuse, or circuit breakerPreparation Choosing the installation locationMinimum clearances for the outdoor unit CasesUnit mm Packing and UnpackingIndoor unit Outdoor unitAccessories in the indoor unit package AccessoriesOptional accessories Drilling a hole through the wall Accessories in the outdoor unit packageTools General tools Tools for test operationTaping the pipes, cables, and drain hose Installation plate Indoor Unit InstallationDisassembling the cover panel Remove the cap screws, then the screwsConnecting the Power and communication cables assembly cable Optional Extending the power cable Install the drain hose Installing and connecting the drain hoseOptional Extending the drain hose FireOptional Changing the direction of the drain hose Each pipe when facing the wallPass the pipe through the hole in the wall Shortening or extending the refrigerant pipes assembly pipe When fixing the indoor unit on a wall 10 Fixing the installation plate When fixing the indoor unit on a window frame When fixing the indoor unit on a gypsum board 11 Fixing the indoor unit to the installation plateFix the installation plate without inclining to one side 12 Assembling the cover panelFixing the outdoor unit in place Outdoor Unit InstallationRefrigerant pipes Optional Fixing the outdoor unit to a wall with a rackCooling capacity and malfunction. Use a vacuum pump Evacuating the airSiphon Adding refrigerantRunning the Smart Install mode Installation InspectionPerforming the gas leak tests Power cable or communication Error betweenMotor Connector Remove foreign substance. Check Blocking error OpenPerforming final check and trial operation Check the following Strength of the installation sitePumping down for removing the product Disconnect the pipesQuestions or COMMENTS?