Samsung AR09MSFTBWKNTV Indoor Unit Installation, Power & Communication cable shall not exceed 30m

Page 38

Indoor Unit Installation

Step 2.1 Connecting the power and communication cables (assembly cable)

Control box

Before

 

 

 

connecting

 

 

 

Correct

Upside down

Damaged

Non-circular

After

 

 

 

connecting

 

 

 

Correct

Correct

Upside down

Non-fitted

(Front view)

(Side view)

<Circular terminal>

1(L)2(N) F1 F2

Fasten the screws for the wire holders.

When performing electrical and earthing works, be sure to comply with the 'technical standards of electrical installations' and the 'wiring regulations' in the local regulations.

Tighten the terminal block screw to 1.2-1.8 N•m (12- 18 kgf•cm).

NOTE

Each wire is labelled with the corresponding terminal number.

Use shield cable (Category 5; less than 50pF/m) for noisy environmental site.

Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord. (Code designation IEC: 60245 IEC 66/ CENELEC: H07RN-F, IEC: 60245 IEC 57/CENELEC: H05RN-F)

Power & Communication cable shall not exceed 30m.

CAUTION

For the terminal block wiring, use a wire with a ring terminal socket only. Regular wires without a ring terminal socket may become a hazard due to overheating of the electrical contact during installation.

If you need to extend the pipe, be sure to extend the cable too. The maximum length of each of the cable and pipe used should not exceed 15(09/12)

/30(18/24/30) metres.

Do not connect two or more different cables to extend the length. This connection may cause fire.

Each circular terminal must match the size of its corresponding screw in the terminal block.

After connecting the cables, make sure that terminal numbers on the indoor and outdoor units match.

Ensure that power and communication cables are separated, they must not be in the same cable.

Model

Power cable

Outdoor-to-

indoor power

cable

Communication

cable

Type GL

09/12

18/24/30

 

 

3G X 1.5 mm²,

3G X 2.5 mm²,

H05VV-F

H07RN-F

 

 

3G X 1.0 mm²,

3G X 1.0 mm²,

H07RN-F

H07RN-F

 

 

2G X 0.75 mm²,

2G X 0.75 mm²,

H05RN-F

H05RN-F

20A

25A

WARNING

Connect the wires firmly so that wires cannot be pulled out easily. (If they are loose, it could cause burn-out of the wires.)

Tighten the Holder Wire Clamp screw to 0.8~1.0 N•m (8~10 kgf•cm)

Installation

English 37

Image 38
Contents Questions or COMMENTS? Air conditioner Contents Installation Safety Information For InstallationSafety Information For Power Supply For Using Safety Information Safety Information For Cleaning Correct disposal of batteries in this product 09/12/18 24/30 Indoor Unit OverviewDisplay Remote Control Overview Two 1.5V AAA type batteriesOperation modes Remote Control OperationControlling temperature Horizontal air flow manual Controlling fan speedControlling air flow direction Step cooling function Cool modeCooling Operation Dry mode Dehumidifying OperationHeat mode Heating OperationFan mode Quick Smart FeaturesAuto mode Fast function Comfort functionBeep sound function Quiet functionEnergy-Saving Operation Single user functionTimed on/Timed off function Is offTo 23 C Good’sleep functionTo 27 C Auto Heat Cleaning at a GlanceRunning Auto clean Heat, FanMild detergent Cleaning the filterVacuum cleaner Soft brush Minutes Troubleshooting Cleaning and Maintenance Cleaning and Maintenance Cleaning and Maintenance General information Safety Information on InstallationInstallation of the unit Power supply line, fuse, or circuit breaker When installing 1 outdoor unit 6 cases Unit mm Choosing the installation locationOverview of installation location requirements PreparationWhen installing more than 1 outdoor unit 5 cases Unit mm Checking and preparing accessories and toolsAccessories Accessories in the indoor unit packageDrilling a hole through the wall Optional accessoriesAccessories in the outdoor unit package ToolsTaping the pipes, cables, and drain hose Drill the hole Be sure to drill only one holeIndoor Unit Installation Power & Communication cable shall not exceed 30mApply heat to the contraction tube to contract it Optional Extending the power cablePrepare a compressor and the following tools Optional Extending the drain hose Installing and connecting the drain hoseInstall the drain hose Electric shock or a fireOptional Changing the direction of the drain hose Shortening or extending the refrigerant pipes assembly pipe When fixing the indoor unit on a window frame Fixing the installation plateWhen fixing the indoor unit on a wall When fixing the indoor unit on a gypsum boardFixing the outdoor unit in place Outdoor Unit InstallationUsing anchor bolts Optional Fixing the outdoor unit to a wall with a rackEvacuating the air Adding refrigerant Performing final check and trial operation Installation InspectionPerforming the gas leak tests Pumping down refrigerantPumping down for removing the product