Installation Inspection

Step 4.1 Performing the gas leak tests

1Before inspecting the leakage, use a torque wrench to close the cap for the stop valve. (Comply with a tightening torque for each size of the diameter, and tighten the cap firmly to prevent any leakage.)

Tightening torque for body cap (Refer to the table)

Test parts for the indoor unit

Installation

Spindle

Charging core

R-22: Thread of the screw - 7/16-2OUNF

R-410A: Thread of the screw -1/2-2OUNF

Tightening torque for charging port cap (Refer to the table)

Outer diameter

 

Tightening torque

 

 

 

(mm)

Body cap

Charging port cap (N•m)

 

(N•m)

 

 

 

 

ø 6.35

20 to 25

 

 

 

 

 

 

ø 9.52

20 to 25

 

 

 

 

 

 

ø 12.70

25 to 30

 

10 to 12

 

 

 

 

ø 15.88

30 to 35

 

 

 

 

 

 

Over ø 19.05

35 to 40

 

 

 

 

 

 

( 1 N•m = 10 kgf•cm )

2Insert inert gas into the pipes connected to indoor and outdoor units.

3Test leakage on the connection parts of the indoor and outdoor units with soap lather or liquid.

Test parts for the indoor unit

Step 4.2 Performing final check and trial operation

1Check the following:

Strength of the installation site

Tightness of pipe connection to detect gas leak

Electric wiring connection

Heat-resistant insulation of the pipe

Drainage

Grounding conductor connection

Correct operation (Take the following steps.)

2Press the (Power) button on the remote control to check the following:

The indicator on the indoor unit lights up.

The airflow blade opens and the fan gears up for operation.

3Press the (Mode) button to select Cool or Heat mode. Then take the following sub-steps:

In Cool mode, use the Temperature button to set the set temperature to 16 °C.

In Heat mode, use the Temperature button to set the set temperature to 30 °C.

Check whether, approximately 3 to 5 minutes later, the outdoor unit starts, and a cool or warm air blows out.

After 12 minutes of stationary condition, check the indoor unit air treatment.

4Press the (Air swing) button to check whether the airflow blades work properly.

5Press the (Power) button to stop the trial operation.

Pumping down refrigerant

Pump-down is an operation intended to collect all the system refrigerant in the outdoor unit. This operation must be carried out before disconnecting the refrigerant tubing in order to avoid refrigerant loss to the atmosphere.

46English

Image 47
Contents Questions or COMMENTS? Air conditioner Contents Installation For Installation Safety InformationSafety Information For Power Supply For Using Safety Information Safety Information For Cleaning Correct disposal of batteries in this product 09/12/18 24/30 Indoor Unit OverviewDisplay Two 1.5V AAA type batteries Remote Control OverviewOperation modes Remote Control OperationControlling temperature Horizontal air flow manual Controlling fan speedControlling air flow direction Step cooling function Cool modeCooling Operation Dehumidifying Operation Dry modeHeating Operation Heat modeFan mode Quick Smart FeaturesAuto mode Comfort function Fast functionQuiet function Beep sound functionSingle user function Energy-Saving OperationIs off Timed on/Timed off functionTo 23 C Good’sleep functionTo 27 C Heat, Fan Cleaning at a GlanceRunning Auto clean Auto HeatMild detergent Cleaning the filterVacuum cleaner Soft brush Minutes Troubleshooting Cleaning and Maintenance Cleaning and Maintenance Cleaning and Maintenance General information Safety Information on InstallationInstallation of the unit Power supply line, fuse, or circuit breaker Preparation Choosing the installation locationOverview of installation location requirements When installing 1 outdoor unit 6 cases Unit mmAccessories in the indoor unit package Checking and preparing accessories and toolsAccessories When installing more than 1 outdoor unit 5 cases Unit mmTools Optional accessoriesAccessories in the outdoor unit package Drilling a hole through the wallDrill the hole Be sure to drill only one hole Taping the pipes, cables, and drain hosePower & Communication cable shall not exceed 30m Indoor Unit InstallationApply heat to the contraction tube to contract it Optional Extending the power cablePrepare a compressor and the following tools Electric shock or a fire Installing and connecting the drain hoseInstall the drain hose Optional Extending the drain hoseOptional Changing the direction of the drain hose Shortening or extending the refrigerant pipes assembly pipe When fixing the indoor unit on a gypsum board Fixing the installation plateWhen fixing the indoor unit on a wall When fixing the indoor unit on a window frameOptional Fixing the outdoor unit to a wall with a rack Outdoor Unit InstallationUsing anchor bolts Fixing the outdoor unit in placeEvacuating the air Adding refrigerant Pumping down refrigerant Installation InspectionPerforming the gas leak tests Performing final check and trial operationPumping down for removing the product