Samsung AR30MSFTBWKNTV, AR24MSFTBWKNTV, AR12MSFTBWKNTV, AR09MSFTBWKNTV manual Evacuating the air

Page 45

Control box Remove the screw for the control box cover

Remove the gas and liquid

For connecting the

service port caps

refrigerant pipes

1Leave the system in the standby mode.

WARNING

Do not turn on the system! This is necessary for better vacuum operation (full OPEN position of Electronic Expansion Valve).

2Connect the charging hose of the low pressure side of manifold gauge to a gas service port as seen in the picture.

Installation

Gas service port <Low pressure>

Liquid service port

Connect the gas and liquid

<High pressure>

refrigerant pipes

Step 3.3 Evacuating the air

The outdoor unit is loaded with sufficient R-410A refrigerant. Do not vent R-410A into atmosphere: it is a fluorinated greenhouse gas, covered by Kyoto Protocol, with a Global Warming Potential (GWP) = 2088. You should evacuate the air in the indoor unit and in the pipe. If air remains in the refrigerant pipes, it affects the compressor. It may cause reduction of cooling capacity and malfunction. Use a vacuum pump.

CAUTION

When installing, make sure there is no leakage. When recovering the refrigerant, ground the compressor first before removing the connection pipe. If the refrigerant pipe is not properly connected and the compressor works with the stop valve open, the pipe inhales the air and it makes the pressure inside of the refrigerant cycle abnormally high. It may cause explosion and injury.

3

Valve

15 minutes

4

Vacuum

Pump

(Backward flowing prevention)

Liquid service port <Low pressure>

5

Liquid service port <High pressure>

3Open the valve of the low pressure side of manifold gauge anticlockwise.

4Evacuate the air in the connected pipes using the vacuum pump for about 15 minutes.

Make sure that pressure gauge shows -0.1 MPa (-76 cmHg, 5 torr) after about 10 minutes. This procedure is very important to avoid a gas leak.

Close the valve of the low pressure side of manifold gauge clockwise.

Turn off the vacuum pump.

Check for 2 minutes if there is any pressure change.

Remove the hose of the low pressure side of manifold gauge.

5Set a valve cork of liquid and gas service port to the open position.

44English

Image 45
Contents Questions or COMMENTS? Air conditioner Contents Installation For Installation Safety InformationSafety Information For Power Supply For Using Safety Information Safety Information For Cleaning Correct disposal of batteries in this product Indoor Unit Overview Display09/12/18 24/30 Two 1.5V AAA type batteries Remote Control OverviewRemote Control Operation Controlling temperatureOperation modes Controlling fan speed Controlling air flow directionHorizontal air flow manual Cool mode Cooling OperationStep cooling function Dehumidifying Operation Dry modeHeating Operation Heat modeQuick Smart Features Auto modeFan mode Comfort function Fast functionQuiet function Beep sound functionSingle user function Energy-Saving OperationIs off Timed on/Timed off functionGood’sleep function To 27 CTo 23 C Running Auto clean Cleaning at a GlanceAuto Heat Heat, FanCleaning the filter Vacuum cleaner Soft brush MinutesMild detergent Troubleshooting Cleaning and Maintenance Cleaning and Maintenance Cleaning and Maintenance Safety Information on Installation Installation of the unitGeneral information Power supply line, fuse, or circuit breaker Overview of installation location requirements Choosing the installation locationWhen installing 1 outdoor unit 6 cases Unit mm PreparationAccessories Checking and preparing accessories and toolsWhen installing more than 1 outdoor unit 5 cases Unit mm Accessories in the indoor unit packageAccessories in the outdoor unit package Optional accessoriesDrilling a hole through the wall ToolsDrill the hole Be sure to drill only one hole Taping the pipes, cables, and drain hosePower & Communication cable shall not exceed 30m Indoor Unit InstallationOptional Extending the power cable Prepare a compressor and the following toolsApply heat to the contraction tube to contract it Install the drain hose Installing and connecting the drain hoseOptional Extending the drain hose Electric shock or a fireOptional Changing the direction of the drain hose Shortening or extending the refrigerant pipes assembly pipe When fixing the indoor unit on a wall Fixing the installation plateWhen fixing the indoor unit on a window frame When fixing the indoor unit on a gypsum boardUsing anchor bolts Outdoor Unit InstallationFixing the outdoor unit in place Optional Fixing the outdoor unit to a wall with a rackEvacuating the air Adding refrigerant Performing the gas leak tests Installation InspectionPerforming final check and trial operation Pumping down refrigerantPumping down for removing the product