WARNING
•After installing the product, be sure to perform leak tests on the piping connections. Before pumping down refrigerant to inspect or relocate the outdoor unit, be sure to stop the compressor and then remove the connected pipes.
––Do not operate the compressor while a valve is open due to refrigerant leakage from a pipe or an unconnected or incorrectly connected pipe. Failure to do so may cause air to flow into the compressor and too a high pressure to develop inside the refrigerant circuit, leading to an explosion or product malfunction.
1Shut off the liquid valve with the Allen wrench.
2Turn on the air conditioner in cooling with fan operating at high velocity. (Compressor will immediately start, provided 3 minutes have elapsed since the last stop.)
3After 2 minutes of operation, shut the suction valve with the same wrench.
4Turn off the air conditioner and switch mains supply off.
5Disconnect tubing. After disconnection, protect valves and tubing ends from dust.
CAUTION
•Compressor damage may occur if the compressor is run at a negative suction pressure.
Pumping down for removing the product
1Hold down the (Power) button on the indoor unit for 5 seconds. Beep sounds immediately to indicate that the product is ready for pump down procedure.
2Let the compressor run for more than 5 minutes.
3Release the valve caps on High and Low pressure side.
4Use
5After approximately 1 minute, close the valve on the low pressure side.
6Stop operation of the air conditioner by pressing
the (Power) button on the indoor unit or remote control.
7Disconnect the pipes.
| 1 |
| 1 minute |
Liquid service port | Gas service port |
<High pressure> | <Low pressure> |
2
Off
Installation
English 47