Napco Security Technologies GEM-P1664 installation instructions WI1424A 1/06 37 

Page 37

WI1424A 1/06

Page 37 

JP1: Cut to enable Keypad Tamper.

JP3: Note different zone terminal wiring required as shown in wiring diagram.

W1 & W3: Cut both to disable touch pad backlighting.

W2: Cut to disable LCD backlighting.

Keypad Jumpers (GEM-RP2ASe2 / GEM-K2AS)

Refer to label LA1390 on the circuit board fishpaper for jumper locations and a summary of settings. See Section 3: Configuring the GEM-RP2ASe2 Keypad for jumper selection.

Keypad Jumpers (GEM-RP3DGTL / GEM-K3DGTL)

Refer to label LA2090 on the circuit board fishpaper for jumper locations and a summary of settings. See Section 3: Configuring the GEM-RP2ASe2 Keypad for jumper selection.

Keypad Jumpers (GEM-RP4 Series / GEM-K4 Series)

Refer to label LA2103 on the circuit board fishpaper for jumper locations and a summary of settings. See Section 3: Configuring the GEM-RP2ASe2 Keypad for jumper selection.

Keypad Features

The following programmed system features will activate only if they have also been enabled at the keypad.

Ambush

Easy Arming

Access Control

Keypad (Police) Panic

Keypad Auxiliary Panic

Keypad Fire Panic

Keypad: GEM-K Series Keypads

Panel automatically detects the difference between the "Classic" and the K-Series ("STAY" and "AWAY") style keypads. Keypad #1 will determine this keypad type for the panel.

Keypad Panic See Panic Zone

Keypad Sounder on Alarm

If a programmed zone goes into alarm, the keypad sounder will activate and will remain activated until the Cbutton is pressed or the system is disarmed.

Keypad Tamper See Tamper

Keypad Zone Directory

The GEM-RP1CAe2/GEM-K1 keypads will support the display of the Keypad Zone Directory. Press Aor Runtil "DISPLAY ZN DIRECTORY Y/N" is displayed and press [NEXT/YES]. Scroll through the zone directory by pressing [NEXT/YES] / [PRIOR/NO].

Keyswitch Arming; Maintained-Key Input Arming

The area will arm/disarm when the programmed zone is momentarily shorted (momentary keyswitch). To supervise the keyswitch, program the zone for Day Zone on Open. Keyswitch Arming will be reported as User 68. Keyswitch must be provided with EOL resistor. Maintained-key input arming will arm when shorted and disarm when opened.

Line-Reversal Module, M278

The Line-Reversal Module allows the panel to be monitored by a central station through leased lines. On alarm, the module reverses normal line-voltage polarity. For details, refer to the instructions furnished with the module.

Loop Response See Zone Response Time

Low Battery; Wireless Low Battery; Keyfob Low Battery

A low-battery system trouble will annunciate at the keypad when the battery terminal voltage drops below normal. This condition may signal a local sounding device, report to a central station (program Panel Low Bat Report Code), or both. If a battery is installed and low terminal voltage is detected, a restore will not occur until the battery is recharged to its specified level and passes a dynamic test. The dynamic test may be initiated manually by pressing the Cbutton, or it will be initiated automatically, every four hours, by the panel. In wireless installations, when displaying RF transmitter status, a "LoBatt" indication denotes a low-battery condition at the transmitter.

Glossary

LNAPCO Security Systems

X GEM-P1664 Installation Instructions

Image 37
Contents System Ready 09/01/05 1200 AM Napco WI1424A 1/06Changes from Previous Edition Important NoticeTable of Contents GEM-P1664 Installation Instructions Lnapco Security Systems FeaturesIntroduction Page WI1424A 1/06WI1424A 1/06 5  Communicator FeaturesGEM-P1664 SpecificationsOrdering Information Optional Accessories and PeripheralsOrdering Information System ComponentsSmoke detectors & Summary of UL Requirements Smoke Detectors, 4-WireSummary of UL Requirements ResidentialMounting InstallationControl Panel GroundingWiring WiringWireless Systems Adding Expansion ZonesSignal Strength Testing/Wireless Systems Testing the SystemWI1424A 1/06 11  SIREN/BELL Power Wiring ConnectionsAuxiliary Power PGM OutputsRemote BUS Wiring Connections Remote Bus & Earth GroundEarth Ground WI1424A 1/06 13 EZ Zone Doublingtm Configuration WI1424A 1/06 15  Wire Smoke DetectorsTelephone Lines Wiring Connections Telephone LinesKeypad Installation Keypad Configuration ModeConfiguring the Keypads ModeCompatibility Number Not Applicable Keypad Configuration ModeEZM Address Zone ResponseDisable Sounder Keypad ConfigurationKeypad Address Touchpad Back LightBasic Operation Basic OperationUser Codes & Zone Descriptions Arming Arming and Disarming the SystemAuto Arming Not for UL Installations Display ZN Faults Alarm IndicationWI1424A 1/06 23  Bypassing ZonesReset System Trbl Display Fire AlarmDisplay ZN Bypassed Display ZN DirectoryEnable User Mode Enable Dealer ModeActivate Program Activate DownloadKeypad Messages Keypad MessagesGlossary AC Failure AC-Fail Report DelayGlossary WI1424A 1/06 27 Ambush Keypad Ambush Ambush Codes Enable Global Ambush Alarm OutputsAreas Zone Area 1-Zone Area 4 Priority Area Arming Backup Report on Telco 1/Telco Auto Status DisableBattery WI1424A 1/06 29 Chirp Output on Keyfob Arm/Disarm Chime ZoneCold Start Data FormatDate/Time WI1424A 1/06 31 Digital Dialer Report Enter/Exit Test Mode Dial-Tone Detection Disable Auto Dial-Tone DetectionDisable Call Waiting Touch-tone Dialing Only Disable Call Waiting on 1st AttemptWI1424A 1/06 33  Enable TCP/IP Communications Enable CP-01 LimitsEnable Telephone Line Fault Test Exit/Entry FollowerWI1424A 1/06 35  Interior Stay Bypass KeyFob Arm/Disarm chirp of Alarm OutputKeyFob Control of Relay Groups 1 Keypad Area AssignmentsWI1424A 1/06 37  Pre-Dial Delay Power-Up DelayMemory Failure Never Arm Do not use for primary Burglary protectionWI1424A 1/06 39  Select Alarm Output for Keyfob Chirp Report Digital Dialer Exit Error/Recent ClosingRelay Follows Zone Report Telco 1 Report Telco 3 Double or Split ReportingWI1424A 1/06 41  Temperature Display at Keypad Not evaluated by UL Tamper EZM Tamper Keypad Tamper RF Tamper Wireless TamperSwinger Shutdown WI1424A 1/06 43  Trouble on Open Trouble on Short Not for UL installations WI1424A 1/06 45  Wire, 4-Wire Smoke Detectors See Smoke Detectors Hour ZoneZone Status Battery Calculation Worksheet STANDBY-BATTERY Calculation WorksheetStandby WI1424A 1/06 47  Wiring LegendKeypad Programming Modes Function Mode49  Keypad Programming Modes Dealer ModeB456 123 D Keypad Programming Modes Easy Menu ModeWI1424A 1/06 51  Keypad Programming Modes User ModeKeypad Programming Modes Keypad Configuration Mode Keypad Configuration ModeProgramming Address WI1424A 1/06 53 Location Is selected in the Easy Program Menu WI1424A 1/06 55  GEM-P1664 Factory Default DescriptionOut of Box Panel Operation Out of Box Panel Operation Prior to CP-01 Changes WI1424A 1/06 57  FCC StatementPage GEM-P1664 Wiring Diagram GEM-P1664 Wiring Diagram59  Napco Limited Warranty

GEM-P1664 specifications

Napco Security Technologies has long been a leader in the security industry, recognized for its innovative solutions that enhance safety and monitoring capabilities. One of its standout products is the GEM-P1664, a versatile and robust control panel designed for both residential and commercial security applications. This advanced system combines user-friendly features with cutting-edge technology, making it an ideal choice for those looking to bolster their security measures.

The GEM-P1664 boasts a 16-zone configuration, allowing users to monitor multiple areas within a property simultaneously. Each zone can be independently programmed, providing flexibility in how security is managed. This feature is particularly valuable for larger facilities or homes with multiple entry points, as it ensures that all areas are adequately protected. The panel supports both hardwired and wireless zones, delivering versatility to suit various installation preferences.

One of the core technologies integrated into the GEM-P1664 is the use of Event Management and Reporting tools. The panel can automatically log security events, sending alerts via email or SMS in real-time. This capability is essential for maintaining awareness of security status, allowing users to respond promptly to any unauthorized access or unusual activity.

The user interface of the GEM-P1664 is designed with simplicity in mind. Its intuitive layout and navigation make it easy for both trained professionals and everyday users to operate the system without extensive technical knowledge. Additionally, the panel supports multiple user codes, allowing different levels of access for family members or staff, enhancing both security and convenience.

Another notable characteristic of the GEM-P1664 is its compatibility with various Napco peripherals and add-ons, including motion detectors, door/window sensors, and surveillance cameras. This interoperability enables users to create a comprehensive security ecosystem tailored to their specific needs. Furthermore, the GEM-P1664 is also compatible with mobile applications, allowing clients to monitor their security systems remotely via smartphones or tablets.

Lastly, the GEM-P1664 is built with future-proofing in mind. It is designed to be easily upgradable, ensuring that users can incorporate the latest technological advancements and security features as they become available. This forward-thinking approach ensures that the investment in the GEM-P1664 remains relevant and effective over time.

In summary, the Napco Security Technologies GEM-P1664 control panel is a powerful and flexible solution for anyone looking to enhance their security infrastructure. With its robust zone configuration, user-friendly interface, advanced reporting capabilities, and compatibility with a range of devices, the GEM-P1664 stands out as a top choice in the security technology landscape.