Smoke detectors & Summary of UL Requirements

Page 8

WI1424A 1/06

Smoke Detectors, 4-Wire:

1.ESL 445AT, 445C, 445CT, 445CR, 445CRT

2.Hochiki America SLG-12 with YBC-RL4-RA Base

3.System Sensor 2312/24T; 1412; 1412TH; 2412TH

Subtract total smoke-detector alarm current from available standby current.

Note: Any normally-open devices that do not require power from the control panel, such as pull stations and thermostats may be used if acceptable to the Authority having Jurisdiction.

UL Compatible Smoke Detectors (Providing UL Recognition or Listing)

Manufacturer

 

4-Wire

 

2-Wire

Smoke Detector

 

Smoke Detector

Smoke Detector *

Base

 

 

 

 

 

 

Napco

 

FW-4

 

FW-2

 

 

 

 

 

 

 

Sentrol

449AT

449CLT

712U

731U

701U

 

449C

449CSLT

722U

 

702U

 

449CRT

449CTE

732U

 

702RE

 

449CST

741U

711U

 

702RU

 

449CSRT

742U

721U

 

 

 

449CSRH

 

721UT

 

 

 

449CSST

 

 

 

 

 

 

 

 

 

 

System

1112

2112T

2100

1100

 

Sensor

2112

2112TSRB

2100T

 

 

 

 

 

 

 

 

Note: * Voltage Rating: 8.5-13.3 VDC, Maximum Number of Detectors: 10

SUMMARY OF UL REQUIREMENTS

Residential

Recognized Limited-Energy Cable for initiating, indicating and supplementary circuits.

Initiating loops supervised if longer than 3 feet

FT2200 End-of-Line Relay for Fire (if using 4-wire smoke detectors)

Minimum alarm timeout of 5 minutes

Maximum exit time: 60 seconds

Maximum entry time: 45 seconds

Do not program “Swinger Shutdown”, “Force Arming”, “Selective Bypass” or “50 ms Loop Response”

“Abort Delay” may not exceed 45 seconds

Program “Disable Callback Download”

Automatic dialer may not dial a police station number that has not been dedicated for such service

System must be tested at least weekly under AC/battery and Battery-Only conditions

Replace the rechargeable battery at least every 5 years

If the battery is heavily discharged, replace it or have it tested by a qualified technician

For silent panic, connect only to UL-listed holdup devices

All zones must be programmed for “Priority”

Do not program any zones for “Keyswitch Arming”

System must be serviced at least once every year

Residential Fire and Combination Residential Fire & Burglary must program “Residential Fire”

Keypad Expansion (EZM) Zones are not to be used as fire zones

Keypad Auxiliary is not to be selected

The GEM-K Series Keypads must have the indicators printed on the face label (Fire, Police and Auxiliary) covered by a supplied label if not in use.

X GEM-P1664 Installation Instructions

LNAPCO Security Systems

Image 8
Contents Napco WI1424A 1/06 System Ready 09/01/05 1200 AMImportant Notice Changes from Previous EditionTable of Contents Features GEM-P1664 Installation Instructions Lnapco Security SystemsIntroduction Page WI1424A 1/06Communicator Features WI1424A 1/06 5 Specifications GEM-P1664Optional Accessories and Peripherals Ordering InformationOrdering Information System ComponentsSmoke Detectors, 4-Wire Smoke detectors & Summary of UL RequirementsSummary of UL Requirements ResidentialInstallation MountingControl Panel GroundingWiring WiringWireless Systems Adding Expansion ZonesWI1424A 1/06 11  Testing the SystemSignal Strength Testing/Wireless Systems Wiring Connections SIREN/BELL PowerAuxiliary Power PGM OutputsWiring Connections Remote Bus & Earth Ground Remote BUSEarth Ground WI1424A 1/06 13 EZ Zone Doublingtm Configuration Wire Smoke Detectors WI1424A 1/06 15 Wiring Connections Telephone Lines Telephone LinesKeypad Configuration Mode Keypad InstallationConfiguring the Keypads ModeKeypad Configuration Mode Compatibility Number Not ApplicableEZM Address Zone ResponseKeypad Configuration Disable SounderKeypad Address Touchpad Back LightUser Codes & Zone Descriptions Basic OperationBasic Operation Arming and Disarming the System ArmingAuto Arming Not for UL Installations Alarm Indication Display ZN FaultsWI1424A 1/06 23  Bypassing ZonesDisplay Fire Alarm Reset System TrblDisplay ZN Bypassed Display ZN DirectoryEnable Dealer Mode Enable User ModeActivate Program Activate DownloadKeypad Messages Keypad MessagesAC Failure AC-Fail Report Delay GlossaryGlossary WI1424A 1/06 27 Areas Zone Area 1-Zone Area 4 Priority Area Arming Alarm OutputsAmbush Keypad Ambush Ambush Codes Enable Global Ambush Auto Status Disable Backup Report on Telco 1/TelcoBattery WI1424A 1/06 29 Chime Zone Chirp Output on Keyfob Arm/DisarmCold Start Data FormatWI1424A 1/06 31  Date/TimeDial-Tone Detection Disable Auto Dial-Tone Detection Digital Dialer Report Enter/Exit Test ModeDisable Call Waiting Touch-tone Dialing Only Disable Call Waiting on 1st AttemptWI1424A 1/06 33  Enable CP-01 Limits Enable TCP/IP CommunicationsEnable Telephone Line Fault Test Exit/Entry FollowerWI1424A 1/06 35  KeyFob Arm/Disarm chirp of Alarm Output Interior Stay BypassKeyFob Control of Relay Groups 1 Keypad Area AssignmentsWI1424A 1/06 37  Power-Up Delay Pre-Dial DelayMemory Failure Never Arm Do not use for primary Burglary protectionWI1424A 1/06 39  Report Digital Dialer Exit Error/Recent Closing Select Alarm Output for Keyfob ChirpRelay Follows Zone Report Telco 1 Report Telco 3 Double or Split ReportingWI1424A 1/06 41  Swinger Shutdown Tamper EZM Tamper Keypad Tamper RF Tamper Wireless TamperTemperature Display at Keypad Not evaluated by UL WI1424A 1/06 43  Trouble on Open Trouble on Short Not for UL installations Zone Status Wire, 4-Wire Smoke Detectors See Smoke Detectors Hour ZoneWI1424A 1/06 45  Standby STANDBY-BATTERY Calculation WorksheetBattery Calculation Worksheet Wiring Legend WI1424A 1/06 47 Function Mode Keypad Programming ModesKeypad Programming Modes Dealer Mode 49 Keypad Programming Modes Easy Menu Mode B456 123 DKeypad Programming Modes User Mode WI1424A 1/06 51 Keypad Configuration Mode Keypad Programming Modes Keypad Configuration ModeLocation WI1424A 1/06 53 Programming Address Is selected in the Easy Program Menu Out of Box Panel Operation GEM-P1664 Factory Default DescriptionWI1424A 1/06 55  Out of Box Panel Operation Prior to CP-01 Changes FCC Statement WI1424A 1/06 57 Page 59  GEM-P1664 Wiring DiagramGEM-P1664 Wiring Diagram Napco Limited Warranty

GEM-P1664 specifications

Napco Security Technologies has long been a leader in the security industry, recognized for its innovative solutions that enhance safety and monitoring capabilities. One of its standout products is the GEM-P1664, a versatile and robust control panel designed for both residential and commercial security applications. This advanced system combines user-friendly features with cutting-edge technology, making it an ideal choice for those looking to bolster their security measures.

The GEM-P1664 boasts a 16-zone configuration, allowing users to monitor multiple areas within a property simultaneously. Each zone can be independently programmed, providing flexibility in how security is managed. This feature is particularly valuable for larger facilities or homes with multiple entry points, as it ensures that all areas are adequately protected. The panel supports both hardwired and wireless zones, delivering versatility to suit various installation preferences.

One of the core technologies integrated into the GEM-P1664 is the use of Event Management and Reporting tools. The panel can automatically log security events, sending alerts via email or SMS in real-time. This capability is essential for maintaining awareness of security status, allowing users to respond promptly to any unauthorized access or unusual activity.

The user interface of the GEM-P1664 is designed with simplicity in mind. Its intuitive layout and navigation make it easy for both trained professionals and everyday users to operate the system without extensive technical knowledge. Additionally, the panel supports multiple user codes, allowing different levels of access for family members or staff, enhancing both security and convenience.

Another notable characteristic of the GEM-P1664 is its compatibility with various Napco peripherals and add-ons, including motion detectors, door/window sensors, and surveillance cameras. This interoperability enables users to create a comprehensive security ecosystem tailored to their specific needs. Furthermore, the GEM-P1664 is also compatible with mobile applications, allowing clients to monitor their security systems remotely via smartphones or tablets.

Lastly, the GEM-P1664 is built with future-proofing in mind. It is designed to be easily upgradable, ensuring that users can incorporate the latest technological advancements and security features as they become available. This forward-thinking approach ensures that the investment in the GEM-P1664 remains relevant and effective over time.

In summary, the Napco Security Technologies GEM-P1664 control panel is a powerful and flexible solution for anyone looking to enhance their security infrastructure. With its robust zone configuration, user-friendly interface, advanced reporting capabilities, and compatibility with a range of devices, the GEM-P1664 stands out as a top choice in the security technology landscape.