Napco Security Technologies GEM-P1664 installation instructions Specifications

Page 6

Specifications

Page 6

WI1424A 1/06

SPECIFICATIONS

GEM-P1664

Operating Temperature: 0-49°C(32-120°F)

Input Power: 16.5-18.0 VAC via CLASS 2 Plug-In 20VA, 40VA or 50VA Transformer

Loop Voltage: 10-13Vdc

Loop Current: 3mA without Zone Doubling, 2.4mA with Zone Doubling using a 2.2K Ohm end-of-line resistor (Model EOL2.2K); 5mA for 2-wire smoke-detector zones; 1.4 mA using a 3.9K Ohm resistor (Model EOL3.9K) with Zone Doubling; 3mA with Se- ries Zone with Loop Supervision and 3mA with Series Zone Doubling with Loop Supervision

Loop Resistance: 300 Ohm max.; 50 Ohm for 2-wire smoke-detector zones

Alarm Voltage Output: 1

Programmable Negative Outputs: 2

Auxiliary Power Output: 11.7-12.5 VDC

Remote Power Output: 12 VDC regulated (for keypads)

Combined Standby Current (Remote Power + Aux. Power + Fire Power): See following charts.

RESIDENTIAL BURGLARY & COMMERCIAL BURGLARY**

16.5VAC

BATTERY

STANDBY

ALARM

STANDBY

TRANSFORMER

(12 VDC)

CURRENT

CURRENT

TIME

 

 

 

 

 

40VA/50VA

7 AH

550 mA

550 mA(1)

4 Hours

20VA*

7 AH

500 mA

2.0 A

4 Hours

 

 

 

 

 

20VA*

7 AH

500 mA

2.0 A

6 Hours

 

 

 

 

 

 

 

 

 

COMBINATION RESIDENTIAL FIRE & RESIDENTIAL BURGLARY

 

 

 

 

 

 

16.5VAC

BATTERY

STANDBY

ALARM

STANDBY

TRANSFORMER

(12 VDC)

CURRENT

CURRENT

TIME

 

 

 

 

 

40VA/50VA

7 AH

120 mA

520 mA(1)

24 Hours

40VA/50VA *

Two 7 AH

360 mA

280 mA(1)

24 Hours

20VA *

7 AH

120 mA

360 mA(1)

24 Hours

20VA *

Two 7 AH

360 mA

120 mA(1)

24 Hours

NOTE: (1) Alarm current can be increased by reducing standby current by the same amount.

*Not evaluated by UL.

**Commercial Burglary specifications not evaluated by UL.

FOR ALL UL INSTALLATIONS

"ENABLE RESIDENTIAL FIRE" (ADDRESS 1422) MUST BE PROGRAMMED

The feature "Enable Residential Fire" (address 1422, option 4 / bit 3) must be programmed for ALL UL installations. To program, please refer to the GEM-P1664 Programming Instructions (WI1422 and WI1423) for further information.

EZM Module: GEM-EZM816: Input, 50mA

Keypad Current: GEM-RP1CAe2: 100mA; 35mA if back lighting is disabled (cut W1, W2 & W3).

PGM Output: 5mA, 12V Special Application

Maximum Number of Keypads: 7

Maximum Wiring Length for each run (#22AWG): 1000' divided by total number of keypads and

EZMs on run

Keypad Dimensions: 4” x 5” x 1” (HWD); 11.1cm x 14.9cm x 2.7cm (HWD)

X GEM-P1664 Installation Instructions

LNAPCO Security Systems

Image 6
Contents Napco WI1424A 1/06 System Ready 09/01/05 1200 AMImportant Notice Changes from Previous EditionTable of Contents Introduction FeaturesGEM-P1664 Installation Instructions Lnapco Security Systems Page WI1424A 1/06Communicator Features WI1424A 1/06 5 Specifications GEM-P1664Ordering Information Optional Accessories and PeripheralsOrdering Information System ComponentsSummary of UL Requirements Smoke Detectors, 4-WireSmoke detectors & Summary of UL Requirements ResidentialControl Panel InstallationMounting GroundingWireless Systems WiringWiring Adding Expansion ZonesTesting the System Signal Strength Testing/Wireless SystemsWI1424A 1/06 11  Auxiliary Power Wiring ConnectionsSIREN/BELL Power PGM OutputsEarth Ground Wiring Connections Remote Bus & Earth GroundRemote BUS WI1424A 1/06 13 EZ Zone Doublingtm Configuration Wire Smoke Detectors WI1424A 1/06 15 Wiring Connections Telephone Lines Telephone LinesConfiguring the Keypads Keypad Configuration ModeKeypad Installation ModeEZM Address Keypad Configuration ModeCompatibility Number Not Applicable Zone ResponseKeypad Address Keypad ConfigurationDisable Sounder Touchpad Back LightBasic Operation Basic OperationUser Codes & Zone Descriptions Arming and Disarming the System ArmingAuto Arming Not for UL Installations WI1424A 1/06 23  Alarm IndicationDisplay ZN Faults Bypassing ZonesDisplay ZN Bypassed Display Fire AlarmReset System Trbl Display ZN DirectoryActivate Program Enable Dealer ModeEnable User Mode Activate DownloadKeypad Messages Keypad MessagesGlossary AC Failure AC-Fail Report DelayGlossary WI1424A 1/06 27 Alarm Outputs Ambush Keypad Ambush Ambush Codes Enable Global AmbushAreas Zone Area 1-Zone Area 4 Priority Area Arming Battery Auto Status DisableBackup Report on Telco 1/Telco WI1424A 1/06 29 Cold Start Chime ZoneChirp Output on Keyfob Arm/Disarm Data FormatWI1424A 1/06 31  Date/TimeDisable Call Waiting Touch-tone Dialing Only Dial-Tone Detection Disable Auto Dial-Tone DetectionDigital Dialer Report Enter/Exit Test Mode Disable Call Waiting on 1st AttemptWI1424A 1/06 33  Enable Telephone Line Fault Test Enable CP-01 LimitsEnable TCP/IP Communications Exit/Entry FollowerWI1424A 1/06 35  KeyFob Control of Relay Groups 1 KeyFob Arm/Disarm chirp of Alarm OutputInterior Stay Bypass Keypad Area AssignmentsWI1424A 1/06 37  Memory Failure Power-Up DelayPre-Dial Delay Never Arm Do not use for primary Burglary protectionWI1424A 1/06 39  Relay Follows Zone Report Digital Dialer Exit Error/Recent ClosingSelect Alarm Output for Keyfob Chirp Report Telco 1 Report Telco 3 Double or Split ReportingWI1424A 1/06 41  Tamper EZM Tamper Keypad Tamper RF Tamper Wireless Tamper Temperature Display at Keypad Not evaluated by ULSwinger Shutdown WI1424A 1/06 43  Trouble on Open Trouble on Short Not for UL installations Wire, 4-Wire Smoke Detectors See Smoke Detectors Hour Zone WI1424A 1/06 45 Zone Status STANDBY-BATTERY Calculation Worksheet Battery Calculation WorksheetStandby Wiring Legend WI1424A 1/06 47 Function Mode Keypad Programming ModesKeypad Programming Modes Dealer Mode 49 Keypad Programming Modes Easy Menu Mode B456 123 DKeypad Programming Modes User Mode WI1424A 1/06 51 Keypad Configuration Mode Keypad Programming Modes Keypad Configuration ModeWI1424A 1/06 53  Programming AddressLocation Is selected in the Easy Program Menu GEM-P1664 Factory Default Description WI1424A 1/06 55 Out of Box Panel Operation Out of Box Panel Operation Prior to CP-01 Changes FCC Statement WI1424A 1/06 57 Page GEM-P1664 Wiring Diagram GEM-P1664 Wiring Diagram59  Napco Limited Warranty

GEM-P1664 specifications

Napco Security Technologies has long been a leader in the security industry, recognized for its innovative solutions that enhance safety and monitoring capabilities. One of its standout products is the GEM-P1664, a versatile and robust control panel designed for both residential and commercial security applications. This advanced system combines user-friendly features with cutting-edge technology, making it an ideal choice for those looking to bolster their security measures.

The GEM-P1664 boasts a 16-zone configuration, allowing users to monitor multiple areas within a property simultaneously. Each zone can be independently programmed, providing flexibility in how security is managed. This feature is particularly valuable for larger facilities or homes with multiple entry points, as it ensures that all areas are adequately protected. The panel supports both hardwired and wireless zones, delivering versatility to suit various installation preferences.

One of the core technologies integrated into the GEM-P1664 is the use of Event Management and Reporting tools. The panel can automatically log security events, sending alerts via email or SMS in real-time. This capability is essential for maintaining awareness of security status, allowing users to respond promptly to any unauthorized access or unusual activity.

The user interface of the GEM-P1664 is designed with simplicity in mind. Its intuitive layout and navigation make it easy for both trained professionals and everyday users to operate the system without extensive technical knowledge. Additionally, the panel supports multiple user codes, allowing different levels of access for family members or staff, enhancing both security and convenience.

Another notable characteristic of the GEM-P1664 is its compatibility with various Napco peripherals and add-ons, including motion detectors, door/window sensors, and surveillance cameras. This interoperability enables users to create a comprehensive security ecosystem tailored to their specific needs. Furthermore, the GEM-P1664 is also compatible with mobile applications, allowing clients to monitor their security systems remotely via smartphones or tablets.

Lastly, the GEM-P1664 is built with future-proofing in mind. It is designed to be easily upgradable, ensuring that users can incorporate the latest technological advancements and security features as they become available. This forward-thinking approach ensures that the investment in the GEM-P1664 remains relevant and effective over time.

In summary, the Napco Security Technologies GEM-P1664 control panel is a powerful and flexible solution for anyone looking to enhance their security infrastructure. With its robust zone configuration, user-friendly interface, advanced reporting capabilities, and compatibility with a range of devices, the GEM-P1664 stands out as a top choice in the security technology landscape.