Napco Security Technologies GEM-P1664 WI1424A 1/06 53 , Programming Address, Location

Page 53

WI1424A 1/06

 

Page 53 

 

 

 

CP-01 Quick Reference Chart--SIA False Alarm Reduction

 

 

 

 

Feature Description

Programming Address

 

Location

CP-01 FEATURES are enabled with one global selection in the panel.

Enabled in EZ Programming

 

 

Exit Delay. Minimum allowed programmable Exit Delay time is 45 seconds. Default is 60 seconds. If an attempt is made to

0000 (Pre-existing)

change the Exit Delay time to less than 45 seconds the time will be entered as 60 seconds. The maximum programmable time

 

 

is 255 seconds. The panel uses the existing programmable by zone feature "Entry/ Exit 1" to comply with CP-01. At least one

 

 

Entry/Exit zone must be programmed for each area. The factory program enables Zone 1 as Entry/Exit and the option to pro-

 

 

gram any zone as Entry/Exit is given in the Easy Program Menu. The existing programmable Entry and Exit delay times are

 

 

also used. The factory program sets the Exit Time Delay as 60 seconds and Entry Time Delay as 30 seconds. These same

 

 

times are entered when "Enable CP-01 Features" is selected in the Easy Program Menu.

 

 

When "Enable CP-01 Limits" (Address 2053, Bit 3) is enabled, the panel will sound an audible egress sequence when it is

2053, Bit 3 (see Note 1)

armed Away (with interior zones not bypassed). The keypad mini-sounder will beep once every second during the beginning

(2053

· · · 4 · · · ·)*

exit delay and beep rapidly the last 10 seconds of exit delay to indicate exit urgency. If the panel is armed Stay (with interior

(2053 · 8 )**

zones bypassed) the keypad mini-sounder is silent and the exit time is double the programmed time. If "Enable CP-01 Lim-

 

 

its" (Address 2053, Bit 3) is NOT enabled, the panel will NOT sound an audible egress sequence. Note: This feature affects

 

 

the operation of "Zone ANDing" as follows: If "Enable CP-01 Limits" is enabled, any Zone in a Group will only activate an alarm

 

 

and send a report ONCE. After the Zone has reported, it will remain in the Group and may still initiate the Zone ANDing se-

 

 

quence.

 

 

Exit Time Restart. This option allows for the following scenario before the end of the Exit Time: a violation of an entry/exit

2053, Bit 0 (see Note 1)

zone, a restore, and a second violation of an entry/exit zone restarts the Exit Time. The panel does not allow the Exit Time to

(2053

1 · · · · · · ·)*

be restarted more than once. The default setting for this option is enabled. Restart is event logged.

(2053 · 1 )**

 

 

Sound Alarm On Exit Error. An Exit Error sequence is initiated if an entry/exit zone is violated at the expiration of the Exit

2053, Bit 1 (see Note 1)

Time. "Exit Error" Central Station Reporting Code is located at address 0706.

(2053

· 2 · · · · · ·)*

 

(2053 · 2 )**

Unvacated Premises. Convert from Away to Stay based on no egress through exit door …default is enabled. (GEM-P1664

 

1424, Bit 0

panel--This feature is Automatic Interior Bypass/ Easy Exit).

(1424

1 · · · · · · ·)*

The panel uses the existing programmable feature "Auto Interior Bypass/Easy Exit". This feature must be enabled in CP-01

(1424 · 1 )**

installations. This feature is enabled in the factory program and it is also enabled when "Enable CP-01 Features" is selected in

 

 

the Easy Program Menu.

 

 

Report Digital Dialer Exit Error/Recent Closing. A Recent Closing transmission is sent if an alarm occurs within two (2) min-

2053, Bit 2 (see Note 4)

utes after the expiration of the Exit Time. If the user number is available, it is included in the Recent Closing transmission.

(2053

· · 3 · · · · ·)*

"Recent Close" Central Station Reporting Code is located at address 0349. Note: Address 2053, bit 1 must also be set to en-

(2053 · 4 )**

able this feature.

 

 

Entry Delay. Entry Delay time is 30 second minimum, default is 30 seconds. If an attempt is made to change the Entry Delay

0001, 0002

time to less than 30 seconds the time will be entered as 30 seconds. The maximum programmable time is 255 seconds. The

(Pre-existing feature)

panel uses the existing programmable by zone feature "Entry/ Exit 1" to comply with CP-01. At least one Entry/Exit zone must

 

 

be programmed for each area. The factory program enables Zone 1 as Entry/Exit and the option to program any zone as En-

 

 

try/Exit is given in the Easy Program Menu. The existing programmable Entry and Exit delay times are also used. The factory

 

 

program sets the Exit Time Delay as 60 seconds and Entry Time Delay as 30 seconds. These same times are entered when

 

 

"Enable CP-01 Features" is selected in the Easy Program Menu.

 

 

Progress Annunciation. Entry urgency annunciation must be different than the alarm mini-sounder. Requires Keypad

Feature in EZ Programming

Sounder on Alarm on all non-fire zones. Locations 0941, 1005, 1069, 1133, 1197, 1261, 1325 and 1389.

 

 

Disarm. The panel will silence the keypad entry delay tones and alarm annunciation on the first press of a keypad

New Panel Operation

digit for 2.5 seconds.

 

 

 

 

Select Alarm Output for Keyfob Chirp. Normally the chirp on a keyfob arm/disarm is transmitted to the PGM output.

1423, Bit 7 (see Note 3)

Selecting "CHIRP BURG BELL OUTPUT" causes the "Bell" to chirp instead of the PGM on remote Arming.

(1423

· · · · · · ·8 )*

The panel uses the existing programmable feature "Chirp Output on Keyfob Arm/Disarm " (Address 1422, bit 6). This fea-

(1423 8 · )**

ture must be programmed in a CP-01 installation if a GEM-KEYF is used in the system. The feature is selected in the factory

 

 

program and is enabled if "Enable CP-01--Enabled" is selected in the Easy Programming Menu.

 

 

Enable CP-01 Limits. When address 2053 bit 3 is enabled, three time limits are enabled as per the SIA CP-01 standards: (1)

2053, Bit 3 (see Note 1)

If the Exit Delay time is programmed for less than 45 seconds, the enabled Exit Delay time will be set to 60 seconds; (2) If the

(2053

· · · 4 · · · ·)*

Entry Delay time is programmed for less than 30 seconds, the enabled Entry Delay time will be set to 30 seconds; and (3) If an

(2053 · 8 )**

attempt is made to change the Abort Delay to less than 15 seconds or more than 45 seconds the time will be entered

 

 

as 30 seconds. (4) Enables Exit Delay sounder. (5) Doubles Exit Delay time when arming Stay due to Silent Exit.

 

 

Abort Window Disarm. The panel will silence the keypad entry delay tones and alarm annunciation on the first press of a

New Panel/Keypad Feature

keypad digit for 2.5 seconds.

 

 

Abort Annunciation after Disarming. Default is enabled. If the panel is disarmed during Abort Delay, the keypad will enunci-

New Panel/Keypad Feature

ate abort. "Alarm Cancelled" is displayed on keypad LCD for RP1/K1 and RP2/K2, and "C" in the 7-segment display for the

 

 

RP3/K3.

 

 

Report Cancel Window. When the system is in alarm and the user disarms in an attempt to Cancel within a minimum of 5

Address 2055

minutes after abort timeout, a Cancel Report will be sent. If Cancel Report is enabled by entering a cancel time (and Abort De-

 

 

lay by zone) Cancel will enunciate on the keypad if the system is disarmed during the Cancel Window. The existing program-

 

 

mable option Report Cancel Window must be programmed for at least 5 minutes in a CP-01 installation. When "Enable CP-01"

 

 

Features is selected in the easy program menu, this time is set to 7 minutes.

 

 

Duress Feature. The existing programmable option "Enable Global Ambush" must not be enabled in CP-01 installations. It

Pre-existing feature

is not enabled in the factory program and is not enabled when Enable CP-01 Feature is selected in the Easy Program Menu.

 

 

LNAPCO Security Systems

X GEM-P1664 Installation Instructions

Image 53
Contents System Ready 09/01/05 1200 AM Napco WI1424A 1/06Changes from Previous Edition Important NoticeTable of Contents GEM-P1664 Installation Instructions Lnapco Security Systems FeaturesIntroduction Page WI1424A 1/06WI1424A 1/06 5  Communicator FeaturesGEM-P1664 SpecificationsOrdering Information Optional Accessories and PeripheralsOrdering Information System ComponentsSmoke detectors & Summary of UL Requirements Smoke Detectors, 4-WireSummary of UL Requirements ResidentialMounting InstallationControl Panel GroundingWiring WiringWireless Systems Adding Expansion ZonesWI1424A 1/06 11  Testing the SystemSignal Strength Testing/Wireless Systems SIREN/BELL Power Wiring ConnectionsAuxiliary Power PGM OutputsRemote BUS Wiring Connections Remote Bus & Earth GroundEarth Ground WI1424A 1/06 13 EZ Zone Doublingtm Configuration WI1424A 1/06 15  Wire Smoke DetectorsTelephone Lines Wiring Connections Telephone LinesKeypad Installation Keypad Configuration ModeConfiguring the Keypads ModeCompatibility Number Not Applicable Keypad Configuration ModeEZM Address Zone ResponseDisable Sounder Keypad ConfigurationKeypad Address Touchpad Back LightUser Codes & Zone Descriptions Basic OperationBasic Operation Arming Arming and Disarming the SystemAuto Arming Not for UL Installations Display ZN Faults Alarm IndicationWI1424A 1/06 23  Bypassing ZonesReset System Trbl Display Fire AlarmDisplay ZN Bypassed Display ZN DirectoryEnable User Mode Enable Dealer ModeActivate Program Activate DownloadKeypad Messages Keypad MessagesGlossary AC Failure AC-Fail Report DelayGlossary WI1424A 1/06 27 Areas Zone Area 1-Zone Area 4 Priority Area Arming Alarm OutputsAmbush Keypad Ambush Ambush Codes Enable Global Ambush Backup Report on Telco 1/Telco Auto Status DisableBattery WI1424A 1/06 29 Chirp Output on Keyfob Arm/Disarm Chime ZoneCold Start Data FormatDate/Time WI1424A 1/06 31 Digital Dialer Report Enter/Exit Test Mode Dial-Tone Detection Disable Auto Dial-Tone DetectionDisable Call Waiting Touch-tone Dialing Only Disable Call Waiting on 1st AttemptWI1424A 1/06 33  Enable TCP/IP Communications Enable CP-01 LimitsEnable Telephone Line Fault Test Exit/Entry FollowerWI1424A 1/06 35  Interior Stay Bypass KeyFob Arm/Disarm chirp of Alarm OutputKeyFob Control of Relay Groups 1 Keypad Area AssignmentsWI1424A 1/06 37  Pre-Dial Delay Power-Up DelayMemory Failure Never Arm Do not use for primary Burglary protectionWI1424A 1/06 39  Select Alarm Output for Keyfob Chirp Report Digital Dialer Exit Error/Recent ClosingRelay Follows Zone Report Telco 1 Report Telco 3 Double or Split ReportingWI1424A 1/06 41  Swinger Shutdown Tamper EZM Tamper Keypad Tamper RF Tamper Wireless TamperTemperature Display at Keypad Not evaluated by UL WI1424A 1/06 43  Trouble on Open Trouble on Short Not for UL installations Zone Status Wire, 4-Wire Smoke Detectors See Smoke Detectors Hour ZoneWI1424A 1/06 45  Standby STANDBY-BATTERY Calculation WorksheetBattery Calculation Worksheet WI1424A 1/06 47  Wiring LegendKeypad Programming Modes Function Mode49  Keypad Programming Modes Dealer ModeB456 123 D Keypad Programming Modes Easy Menu ModeWI1424A 1/06 51  Keypad Programming Modes User ModeKeypad Programming Modes Keypad Configuration Mode Keypad Configuration ModeLocation WI1424A 1/06 53 Programming Address Is selected in the Easy Program Menu Out of Box Panel Operation GEM-P1664 Factory Default DescriptionWI1424A 1/06 55  Out of Box Panel Operation Prior to CP-01 Changes WI1424A 1/06 57  FCC StatementPage 59  GEM-P1664 Wiring DiagramGEM-P1664 Wiring Diagram Napco Limited Warranty

GEM-P1664 specifications

Napco Security Technologies has long been a leader in the security industry, recognized for its innovative solutions that enhance safety and monitoring capabilities. One of its standout products is the GEM-P1664, a versatile and robust control panel designed for both residential and commercial security applications. This advanced system combines user-friendly features with cutting-edge technology, making it an ideal choice for those looking to bolster their security measures.

The GEM-P1664 boasts a 16-zone configuration, allowing users to monitor multiple areas within a property simultaneously. Each zone can be independently programmed, providing flexibility in how security is managed. This feature is particularly valuable for larger facilities or homes with multiple entry points, as it ensures that all areas are adequately protected. The panel supports both hardwired and wireless zones, delivering versatility to suit various installation preferences.

One of the core technologies integrated into the GEM-P1664 is the use of Event Management and Reporting tools. The panel can automatically log security events, sending alerts via email or SMS in real-time. This capability is essential for maintaining awareness of security status, allowing users to respond promptly to any unauthorized access or unusual activity.

The user interface of the GEM-P1664 is designed with simplicity in mind. Its intuitive layout and navigation make it easy for both trained professionals and everyday users to operate the system without extensive technical knowledge. Additionally, the panel supports multiple user codes, allowing different levels of access for family members or staff, enhancing both security and convenience.

Another notable characteristic of the GEM-P1664 is its compatibility with various Napco peripherals and add-ons, including motion detectors, door/window sensors, and surveillance cameras. This interoperability enables users to create a comprehensive security ecosystem tailored to their specific needs. Furthermore, the GEM-P1664 is also compatible with mobile applications, allowing clients to monitor their security systems remotely via smartphones or tablets.

Lastly, the GEM-P1664 is built with future-proofing in mind. It is designed to be easily upgradable, ensuring that users can incorporate the latest technological advancements and security features as they become available. This forward-thinking approach ensures that the investment in the GEM-P1664 remains relevant and effective over time.

In summary, the Napco Security Technologies GEM-P1664 control panel is a powerful and flexible solution for anyone looking to enhance their security infrastructure. With its robust zone configuration, user-friendly interface, advanced reporting capabilities, and compatibility with a range of devices, the GEM-P1664 stands out as a top choice in the security technology landscape.