OmniTek 839-1340 How to Use the Vent Graph, Venting Guidelines, Vertical Distance, Elbow

Page 11

D. How to Use the Vent Graph

1.Measure the vertical distance from the center line of the flue pipe to the center of the 90° elbow. On the graph below, draw a horizontal line from that measurement on the vertical axis across until it intersects with the slanted line.

2.From the point of this intersection, draw a vertical line to the bottom of the graph.

3.The point at which this line meets the bottom line of the graph is the maximum length of the horizontal run.

EXAMPLE 1: If the vertical dimension from the center line of the flue vent to the center of the 90° elbow is 7 ft. (2m), the horizontal run to the outer wall flange must not exceed 16 ft. (5m).

EXAMPLE 2: If the vertical dimension from the center line of the flue vent is 21ft. (6m), the horizontal run to the outer wall flange must not exceed 12 ft. 10 in. (4m).

4.Each 90° elbow is equivalent to 3 ft. (914mm) of vent pipe and each 45° elbow is equivalent to 1ft. (305mm) of vent pipe, and must be subtracted from the vent pipe run. A single horizontal to vertical 90° elbow is already calculated into the allowable 20 ft. (6m) run. Each additional 90° elbow reduces the maximum horizontal distance by 3 ft. (914mm).

EXAMPLE: The use of 3 elbows would reduce the allowable horizontal run to 9 ft. (3 -1 = 2 elbows x 3 ft. = 6 ft.; 20 ft. max. - 6 ft. = 14 ft. max.).

E. Venting Guidelines

NOTES

The maximum horizontal vent run is 20 ft. (6m) when the vertical vent rise is 10 ft. (3m).

The minimum horizontal vent run is 6 in. (152mm) Horizontal sections require a 1/4 in. (6mm) rise for every 12 in. (305mm) of horizontal travel.

Exterior Vent Diameter = 6-5/8 in. (168mm); Inner Vent Diameter = 4 in. (102mm).

Horizontal sections require noncombustible support every 3 ft. (914mm), e.g. wall straps.

For any vertical termination a minimum of 6 ft. (2m) vertical must be used.

EXCEPTIONS FOR HORIZONTAL INSTALLATIONS: *When installing the Topaz in a rear vent configuration with no vertical rise, a Snorkel Kit must be used.

*The maximum horizontal vent run is 3 ft. (914mm). *The maximum horizontal vent run with a 45° elbow is 2 ft. (609mm).

*The minimum horizontal vent run is 6 in. (152mm).

INDIVIDUALINSTALLATIONS MAYVARY. PERCENTAGE CLOSED BASED ON FULL RANGE OF DAMPER TRAVEL.

NOTE: If your installation falls within the gray-shaded area on graph, see information on VERTICAL DAMPER ADJUSTMENT in Section 8.

*In the Commonwealth of Massachusetts, the word damper shall be replaced with the words flue restrictor.

40 ft. (12m)

40'

Maximum Vertical

39'

38'

 

37'

36' 35' 34'

32'

 

30'

 

 

 

 

 

 

 

 

 

 

 

 

28'

Damper position

 

 

 

 

 

 

 

 

 

26'

 

 

 

 

 

 

 

 

 

more CLOSED in

 

 

 

 

 

 

 

 

 

24'

 

this area

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Example 2

22'

 

 

 

 

 

 

 

 

 

 

 

 

20'

 

 

 

 

 

 

 

 

 

 

 

VERTICAL DISTANCE

18'

 

 

 

 

 

 

 

 

 

 

 

16'

 

 

Damper position

 

 

 

 

 

 

FROM APPLIANCE TO

14'

 

 

 

more OPEN in

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90° ELBOW

12'

 

 

 

this area

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Example 1

8'

 

 

 

 

 

 

 

 

 

 

 

 

6'

 

 

No damper

 

 

 

 

 

 

 

 

4'

 

 

in this area

 

 

 

 

 

 

 

 

2'

 

 

 

 

 

 

 

 

 

 

 

6 in. (152mm) Minimum

2'

4'

6 '

8'

10'

12'

14' 15' 16'

17'

18'

19'

20'

 

 

 

3 ft. (914mm) Maximum Horizontal run with no

Vertical Termination

 

 

 

 

C

 

 

 

 

vertical pipe and with 1/4 in (6mm) rise per foot.

 

 

 

 

Must use Snorkel cap.

 

 

 

 

L

 

 

 

 

 

 

 

 

CL For rear vent or top of

6 in. (152mm) Minimum starter pipe

appliance for top vent

 

Figure 5.2

Quadra-Fire • Topaz • 7009-113 Rev. J • 12/11

11

Image 11
Contents Hot glass will cause burns Do DiscardnotWelcome to the Quadra-Fire Family Table of Contents 1Listing and Code Approvals Gas Equipment Venting System not Provided Requirements for the Commonwealth of MassachusettsManufacturer Requirements Gas Equipment Venting System ProvidedTools and Supplies Needed Design & Installation ConsiderationsGetting Started Inspect Appliance & ComponentsDesign Purposes only Selecting Appliance LocationClearances Vent Termination Minimum Clearances 4Termination LocationsAlcove Applications Measuring Standards Vent InformationVenting Components Use of ElbowsFrom Appliance to How to Use the Vent GraphVenting Guidelines Vertical DistanceStep Type a Up & Out Installations for Top Vent ConfigurationsType B Rear Installations for Use with Rear Vent Kit Horizontal TerminationTop Vent Touching the hot cap Step Vertical TerminationDirect Vent Pipe Ceiling Joists Framing 2 in mm Long Wood Screws Twist-lock the vent cap and seal Cathedral Ceiling Class a Metal Chimney Existing Masonry Chimney Fire Risk Explosion Risk Retro Connector Converting to LP Gas Gas InformationFuel Conversions Propane Natural GAS Valve Regulator ReplacementPressure Gas PressuresCheck for GAS Leaks Gas ConnectionWire Size Max. Length Recommendation for WireConnecting to the Appliance Standing Pilot Ignition System WiringON/OFF Switch Red 28Thermocouple Gas Pilot Ignitor Thermopile Ignitor Red 28 711mmTop to Rear Vent Conversion Appliance SetupRemove Shipping Materials Leg Leveling System AccessoriesFor Both Quartet and Solitaire Fronts Front Installation Fronts shipped attached to faceBrick Installation Qty Description Positioning the LogsMineral Wool Blower Installation Glass Door Assembly ReplacementWhite Make adjustment Damper AdjustmentShutter Adjustment For TOP or Rear Vent InstallationsControls Operating InstructionsBefore Lighting Appliance Lighting Appliance For Your Safety Read Before LightingAfter Appliance is Lit Frequently Asked QuestionsInitial Break-in Procedure Symptom Possible Cause Corrective Action TroubleshootingBe Placed in this Opening After servicing Maintaining and Servicing Your ApplianceNecessary. USE Caution When CLEANING/HANDLING Ceramic Burner Maintenance Tasks InspectReference Materials Appliance Dimension DiagramMm inner pipe 6-5/8 in mm outer pipe Vent Components DiagramDura-Vent Vent Components ListDescription SimpsonTermination Caps & Kits HHT SLPSimpson Description Dura-VentDirect Vent Gas Stove RD. Service Parts ListLog Set Assembly Part number list on following Description Comments Part Number Service Parts ListStocked At DepotSIDE-TPZ-POR BRNR-TOPAZSIDE-TPZ-MBK TOUCHUP-CWL TOUCHUP-CSBStocked Fasteners Description Comments Part Number AccessoriesBK-GAS WSLG-CSBLimited Lifetime Warranty Limited Lifetime WarrantyWarranty Conditions Dealer Telephone TopazContact Information