| 19 |
3.10 REAR EXIT HORIZONTAL TERMINATION |
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
| (HT) < (VT) |
|
|
|
|
|
|
|
|
|
Simple venting configuration | See graph to determine the required vertical rise VT for the required | ||||||||||||||||
|
| (only two 90° elbows) |
|
| horizontal run HT. |
|
|
|
| ||||||||
|
|
|
|
|
|
|
| 38.3 40 |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| REQUIRED | 30 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| VERTICAL | 20 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| RISE IN |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
| FIGURE 3.10a |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
| FEET VT | 10 |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| 1.6 | 0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 2.5 | 5 | 7.5 | 10 | 12.5 | 15 | 17.5 | 20 | |
|
|
|
|
|
|
|
|
|
| 1.6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| HORIZONTAL VENT RUN PLUS OFFSET IN FEET HT |
| ||||||||
|
|
|
|
|
|
|
| The shaded area within the lines represents acceptable values for HT | |||||||||
|
|
|
|
|
|
|
|
|
|
| and HT |
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| 90° |
|
|
|
For vent configurations requiring more than two 90° elbows, the following formulas apply: |
|
|
| H3 |
|
| |||||||||||
Formula 1: H | T | < V |
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
| T |
|
|
|
|
|
|
|
|
|
| |
Formula 2: HT | + VT < 40 feet |
|
|
|
|
|
|
|
|
|
| ||||||
Example 4: |
|
|
|
|
|
|
|
| 90° | V2 |
|
|
| ||||
V1 | = 9 FT |
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| H2 |
|
|
| ||||
V2 | = 6 FT |
| = 9 + 6 = 15 FT |
|
|
|
|
|
|
|
|
| |||||
V | T | = V + V | 2 |
|
|
|
|
|
|
|
|
|
| ||||
| 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
H1 | = 3 FT |
|
|
|
|
|
|
|
|
|
|
| 90° |
|
| ||
H2 | = 2 FT |
|
|
|
|
|
|
|
| V1 |
|
|
|
| |||
H3 | = 1.5 FT |
|
|
|
|
|
|
|
|
|
|
|
| ||||
+ H3 = 3 + 2 + 1.5 = 6.5 FT |
|
|
|
|
|
|
|
|
|
| |||||||
HR | = H1 | + H2 |
|
|
|
|
|
|
|
|
|
| |||||
H = .03 (four 90° elbows - 90°) = .03 (360° - 90°) = 8.1 FT |
|
|
|
|
|
|
|
|
| ||||||||
HTO | = HR | + HO = 6.5 + 8.1 = 14.6 FT |
|
|
| H1 |
|
|
|
|
|
| |||||
HT + VT | = 14.6 + 15 = 29.6 FT |
|
|
|
|
|
| 90° |
|
|
| ||||||
Formula 1: |
|
| HT < VT |
|
|
|
|
|
| FIGURE 3.10b |
| ||||||
|
|
|
|
|
|
| 14.6 < 15 |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Formula 2: |
|
| HT + VT < 40 FT |
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
| 29.6 < 40 |
|
|
|
|
|
|
|
|
|
|
Since both formulas are met, this vent configuration is acceptable. |
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| 16.3 |
|
|
|
|