3.4 VENT TERMINAL CLEARANCES

FIGURE 3.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INSTALLATIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CANADA

U.S.A.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

12”

12”

Clearance above grade, veranda porch, deck or balcony.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

12”

9”

Clearance to windows or doors that open.

C

12” *

12” *

Clearance to permanently closed windows.

D

18” **

18” **

Vertical clearance to ventilated soffits located above the terminal within a horizontal distance of 2’ from

the centerline of the terminal.

 

 

 

E

12” **

12” **

Clearance to unventilated soffit.

F

0”

0”

Clearance to an outside corner wall.

G

0” ***

0” ***

Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney, etc.).

2” ***

2” ***

Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase, etc.).

 

H

3’

3’ ****

Clearance to each side of the centerline extended above the meter / regulator assembly to a maximum

vertical distance of 15’.

 

 

 

I

3’

3’ ****

Clearance to a service regulator vent outlet.

J

12”

9”

Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.

K

6’

3’ †

Clearance to a mechanical air supply inlet.

L

7’ ‡

7’ ****

Clearance above a paved sidewalk or paved driveway located on public property.

M

12” ††

12” ****

Clearance under a veranda, porch, deck or balcony.

N

16”

16”

Clearance above the roof.

O

2’ †*

2’ †*

Clearance from an adjacent wall including neighbouring buildings.

*

Recommended to prevent condensation on windows and thermal breakage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**

it is recommended to use a heat shield and to maximize the distance to vinyl clad soffits.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

***

The periscope requires a minimum 18 inches clearance from an inside corner.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

****

This is a recommended distance. For additional requirements check local codes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 feet above if within 10 feet horizontally.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

††

Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the floor.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

†*

Recommended to prevent recirculation of exhaust products. For additional requirements check local codes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: Clearances are in accordance with local installation codes and the requirements of the gas supplier.

12.1

W415-0788 / A / 09.22.09

Image 14
Contents GDS60N & GS60N Table of Contents Installation Overview InstallationIntroduction Dimensions General InstructionsWe suggest that our gas General InformationRating Plate Model Natural GAS/GAZ NaturalGlass Door Removal Care of GlassShipping Bracket Shippingbracket LatchRefer to the section applicable to your installation Venting Model GDS60Venting Lengths and Components Part Supplier WebsiteTOP Vent Minimum Feet Maximum Rear Vent Typical Vent InstallationsMinimum Feet Maximum Minimum Plus Rise PlusRise Grade Special Vent Installations 3.3.1 Periscope TerminationCorner Termination To Grade MinimumInstallations Canada Vent Terminal ClearancesVenting Application Flow Chart TOP Exit Rear ExitFeet Inches DefinitionsElbow Vent Length Values TOP Exit Horizontal Termination HT VTFormula 1 HT VT Formula 2 HT + VT 40 FT Rear Exit Horizontal Termination Horizontal Vent RUN Plus Offset in Feet HT10c TOP or Rear Exit Vertical Termination 11a11c Rear Vent Termination Installation Preparation Model GDS60Orifice Replacement Changing a TOP Vent to a Rear Vent Maintain These Minimum Clearances to Combustibles InstallationMinimum Clearance to Combustibles Horizontal Installation Wall and Ceiling ProtectionVertical Installation Horizontal AIR Terminal Installation Model GDS60Roof Support Vertical AIR Terminal Installation Model GDS60High Temperature Sealant Inner Flex Pipe Inner PipeHigh Temperature Sealant Mobile Home Installation Model GDS60GAS Installation Appliance Vent Connection Model GDS60Wire Size MAX. Length Optional Wall Switch / ThermostatVent Specifics Model GS60 5.7.1 Chimney Installation Installing B Vent Combustion AIRAdding Vent Sections More MIN Flat Roof WallInstalling Flashing and Storm Collar Caulking Storm Collar Weather Sealant FlashingFront Cast Removal Glass Door Installation and RemovalFinishing Return FlangeGlass / Door Replacement LOG PlacementLogo Placement Switch and Bracket Installation Access Cover PlateOptional Blower Installation Slot Removed ScrewsWiring Diagram Model GS60 only Venting Action Check OperationOperating Instructions Anti Condensation Switch Lighting InstructionsVenturi Adjustment AdjustmentPilot Burner Adjustment Flame CharacteristicsMaintenance Replacements Common ComponentsGS60 Components Roof Terminal Kits 49 50 Trouble Shooting Symptom ProblemSymptom Problem Test Solution Glass Embers only HOTGDS600 only GS600 onlyWarranty Conditions and LimitationsService History Appliance Service History