Napoleon Fireplaces GDS60N manual Installation Preparation Model GDS60, Orifice Replacement

Page 23

Example 8:

 

 

V1

= 1.5 FT

 

 

V2

= 5 FT

 

 

V

T

= V

1

+ V = 1.5 + 1 + 5 = 6.5 FT

 

 

 

2

 

 

H1

= 1 FT

 

 

H2

= 1 FT

 

 

H3

= 10.75 FT

 

HR

= H1

+ H2

+ H3 = 1 + 1 + 10.75 = 12.75 FT

90°

HO

= .03 (four 90° elbows + one 45° elbow - 90°)

 

 

= .03 (360° + 45° - 90°) = 6.75 FT

H2

HT

= HR

+ HO

= 12.75 + 6.75 = 19.5 FT

45°

HT

+ VT

= 19.5 + 6.5 = 26 FT

 

Formula 1:

 

V1

 

 

H

 

< 3 V

 

 

 

T

3 VTT = 3 x 6.5 = 19.5 FT

H1

19.5 = 19.5

 

90°

Formula 2:

FIGURE 3.11e

HT + VT < 40 FT

 

26 < 40

 

Since both formulas are met, this vent configuration is acceptable.

23

V2

H3 90°

18.2_3

4.0 INSTALLATION PREPARATION - MODEL GDS60

4.1 ORIFICE REPLACEMENT

REAR VENT TERMINATION:

In rear exit installations with no vertical vent run, the BTU input must be reduced to 21,000 BTU by changing the orifice.

In order to access the orifice, the log support secured by two screws, must be removed.

Care should be taken not to damage the gas pipe. When removing

FIGURE 4.1a

the orifice, using a 9/16" socket wrench, a 7/8" back-up wrench must

 

be used on the manifold, located below the housing, to ensure that

 

the aluminum tubing does not twist or kink.

 

FIGURE 4.1b

W415-0788 / A / 09.22.09

Image 23
Contents GDS60N & GS60N Table of Contents Installation Installation OverviewIntroduction General Instructions DimensionsGeneral Information We suggest that our gasModel Natural GAS/GAZ Natural Rating PlateShippingbracket Latch Care of GlassShipping Bracket Glass Door RemovalVenting Model GDS60 Refer to the section applicable to your installationPart Supplier Website Venting Lengths and ComponentsTOP Vent Minimum Feet Maximum Rear Vent Typical Vent InstallationsMinimum Feet Maximum Minimum Plus Rise PlusRise To Grade Minimum Special Vent Installations 3.3.1 Periscope TerminationCorner Termination GradeVent Terminal Clearances Installations CanadaRear Exit Venting Application Flow Chart TOP ExitFeet Inches DefinitionsElbow Vent Length Values HT VT TOP Exit Horizontal TerminationFormula 1 HT VT Formula 2 HT + VT 40 FT Horizontal Vent RUN Plus Offset in Feet HT Rear Exit Horizontal Termination10c 11a TOP or Rear Exit Vertical Termination11c Rear Vent Termination Installation Preparation Model GDS60Orifice Replacement Changing a TOP Vent to a Rear Vent Maintain These Minimum Clearances to Combustibles InstallationMinimum Clearance to Combustibles Wall and Ceiling Protection Horizontal InstallationHorizontal AIR Terminal Installation Model GDS60 Vertical InstallationInner Pipe Vertical AIR Terminal Installation Model GDS60High Temperature Sealant Inner Flex Pipe Roof SupportAppliance Vent Connection Model GDS60 Mobile Home Installation Model GDS60GAS Installation High Temperature SealantWire Size MAX. Length Optional Wall Switch / ThermostatVent Specifics Model GS60 5.7.1 Chimney Installation Combustion AIR Installing B VentMore MIN Flat Roof Wall Adding Vent SectionsCaulking Storm Collar Weather Sealant Flashing Installing Flashing and Storm CollarReturn Flange Glass Door Installation and RemovalFinishing Front Cast RemovalLOG Placement Glass / Door ReplacementLogo Placement Access Cover Plate Switch and Bracket InstallationSlot Removed Screws Optional Blower InstallationWiring Diagram Model GS60 only Venting Action Check OperationOperating Instructions Lighting Instructions Anti Condensation SwitchFlame Characteristics AdjustmentPilot Burner Adjustment Venturi AdjustmentMaintenance Common Components ReplacementsGS60 Components Roof Terminal Kits 49 50 Symptom Problem Trouble ShootingSymptom Problem Test Solution GS600 only HOTGDS600 only Glass Embers onlyConditions and Limitations WarrantyAppliance Service History Service History