Testing Your System | |
|
|
EN 29
10.4Fire Walk Test
This test confirms that smoke detectors report alarms to the keypads. The Fire Walk Test tests all fire zones, including verified fire and waterflow.
This test requires you to manually alarm each zone.
If programmed, a Fire Walt Test report is sent to the central station at the start of a Fire Walk Test. Fire alarm reports are not sent to the central station during the Fire Walk Test. A Fire Walk Test restoral is sent upon completion of the Fire Walk Test.
The Fire Walk Test runs for 20 minutes once it is started. The test time is extended to 20 minutes every time you test another zone.
When you test a fire zone, any output programmed to follow that zone is activated for 5 seconds.
Table 28: Fire Walk Test
|
|
|
|
Type of Test | Command Sequence | What Happens | What To Do |
|
|
|
|
Fire Walk Test | [PIN][#][9][1] | • “Fire Test” is displayed followed by the number | • Test each zone as |
|
| of any zones that are untested. * | instructed by your |
|
| • The LEDs of any untested zones flash. ** | installing company. |
|
| • “Fire Testing” is displayed followed by the | • Exit the Fire Walk Test |
|
| number of the zone currently being tested. * | using [PIN][#]. |
|
| • The LED for the zone currently being tested |
|
|
| turns on steady. ** |
|
|
| • As each zone is tested, the “Fire Test” message |
|
|
| appears followed by the remaining untested |
|
|
| zones. * |
|
|
| • As each zone is tested, its LED turns off. ** |
|
*Text keypad only ** LED keypad only
A Fire Walk Test prevents the system from sending any Fire Reports during the test.