D9412GV3/D7412GV3 Operation and Installation Guide

3.0

Overview

 

 

 

3.3.7Keypads

Up to 32 unsupervised keypads can be connected to the system. The available power, number of supervised keypads, and number of areas covered affect the total number of keypads that can be connected.

The system can supervise up to sixteen D1255 keypads (all models), and up to eight D1260 keypads (all models). The control panel sends a Serial Device Trouble Report, SDI FAILURE in the Modem IIIa2 format or Expansion Module Failure (333) in Contact ID format, if it loses communication with a supervised keypad.

More than 16 keypads can be added, but the system can only supervise up to 16 keypads. Table 4 on page 13 shows the keypads that are compatible with the D9412GV3 and D7412GV3 Control Panels. Refer to Keypad in the D9412GV3/D7412GV3 Program Entry Guide (P/N: F01U170807) for complete details on programming keypad options.

UL requires all Fire System keypads to be supervised.

Table 4:

Compatible Keypads

 

 

 

 

 

 

Model

Display

Application

D1255/

16-character

Fire/Burglary/Access

D1255B/D

alphanumeric

 

1255RB

 

 

D1256/

16-character

Fire

D1256RB

alphanumeric

 

D1257/

16-character

Fire

D1257RB

alphanumeric

 

D1260/

4-line by 20-

Fire/Burglary

D1260B

character

 

D720/

8 LED

Fire/Burglary

D720B

 

 

3.3.8Keyswitch

Maintained or momentary closure devices such as keyswitches allow any of the available areas to be armed or disarmed. Point programming determines the loop responses and which area a keyswitch controls.

3.3.9Access Control

The D9412GV3 can control eight access doors (each requiring the optional D9210B Wiegand Control Interface Module) with up to 996 uniquely identified cards or tokens. The D7412GV3 can control two access doors with up to 396 uniquely identified cards or tokens. Any of the following can grant access:

Wiegand-style access control device (card reader) connected to the D9210B Access Control Interface Module

Request to enter (RTE) or request to exit (REX) input

Unlock command on a keypad

The access control features of the D9412GV3 and D7412GV3 can deny access during armed periods. The control panel can also grant access only to certain authorized users depending on whether the area is master armed, perimeter armed, or disarmed. Programming for automatic disarming when designated authorized users are granted access is also possible.

3.3.10 Event Memory

The control panel retains point alarm and trouble events in memory for each area. A D1255 (any model) or a D1260 (any model) can be used to view event memory by using COMMAND 40. The control panel clears the previous events for an area from the event memory when the area is armed.

3.3.11 Event Log

The system stores 800 events from all areas in its event log. For example, the system adds at least two items to the log each time an area is armed or disarmed, the open (or close) event that also contains the previous arming state.

All events can be stored even if the control panel does not send a report for them. The log can be viewed at a keypad, printed locally using the D9131A Parallel Printer Interface Module and a parallel printer, or uploaded using Remote Programming Software (RPS).

For a list of the log events, refer to the appendix in the user’s guide for the keypad.

3.3.12 Ground Fault Detection

The Earth Ground Terminal on the control panels is electrically isolated from all other terminals to allow the D9412GV3 and the D7412GV3 to detect ground fault conditions. A Ground Fault Detect Enable switch (S4) is located just under Terminal 10, Earth Ground, on the control panel. Refer to Section 4.5.2 Ground Fault Detect Enable on page 15 for information on operating this function.

Bosch Security Systems, Inc. 10/10 F01U143070-03

13

Image 13
Contents D9412GV3/D7412GV3 Certifications and Approvals TrademarksListings and Approvals Federal Communications Commission FCC RulesFCC Registration Number Service Center in USARinger Equivalence 0.0B Contents Appendix a System Wiring Diagrams, Issue a Programmer and Accessory ConnectionsAppendix B Point Address Charts Tables Related Documentation IntroductionLightning Strikes Precautions during InstallationEffects Features D9412GV3 D7412GV3 Configuration and PartsOverview GV3 Series Control Panel DifferencesAssembly Parts ListLiterature Pack Parts Available by Separate OrderCompatible Accessories1 AccessoriesModel Title Fire Intrusion Features in the D9412GV3 and D7412GV3 Access Control KeyswitchGround Fault Detection KeypadsInstallation Preparation InstallationEnclosure Options Mounting EnclosureConnecting Earth Ground Installing the Control PanelGround Fault Detect Enable TerminalGround Fault Specifications Enabling Ground Fault DetectionGround Fault Impedance Specifications Locking the Reset PinProgramming the Control Panel Completing the InstallationTesting the System Installing the Point Chart LabelService Walk Test Service Walk Test ProcedureD9412GV3/D7412GV3 Operation and Installation Guide Test a device Bosch Security Systems, Inc /10 F01U143070-03Text displays for 60 seconds D7412GV3 Service Walk Test Flow Chart Primary Power Terminals 1 Power SupplySecondary Power Terminals Non-Power-Limited Wiring D8132 Boost Battery Backup Adding a D8132 Replacing the Battery Charging and Battery LEDsInvestigate Low Battery reports immediately If Battery Charging CircuitCharging Status and Low Battery LEDs Battery Discharge and Recharge ScheduleDischarge Cycle Recharge CycleTotal Available Power Power OutputsContinuous Power Output Terminals 3, 8, 24, Circuit ProtectionVerification and Reset Relay Programmable Power Output Terminals 6, 7,A  NSC current = Alarm current Required Step Available Voltage Output at Terminals 6, 7,Registration Telephone ConnectionsNotification LocationOperation Monitor LED Green Phone LED RedDialing Format Telephone Line MonitorDescription 11 D928 Dual Phone Line SwitcherTerminals 11 to 22 Description On-Board PointsPoint Sensor Loops Point Parameters Point ParametersLoop Voltage Range Point Response Time 64 mm 1/4 Minimum distance Comm Point Zonex Bus D9412GV3 Terminals and D7412GV3 Off-Board PointsError Condition Result Additional Information Off-Board Point ErrorsD8125 and D9127 Popit Modules 5 D9412GV3/D7412GV3 Responses to Missing Point ConditionsConnecting the D8125 Popex to the D9412GV3 Control Panel Connecting the D8125 Popex to the D7412GV3 Control Panel Installing the D8125 Popex Module Popit Sensor Loops Wiring Data Expansion Loops to Popex ModulesPopit Module Point Assignments Program Record SheetProgram Record Sheet Popit Labels D8128D OctoPOPIT ModuleD8128D OctoPOPIT Layout Requirements for Fire Initiation ApplicationsSetting the OctoPOPIT Switches InstallationAddress Switches D8128D OctoPOPIT Switch Settings for D9412GV3 and D7412GV3Using the Terminal Strip Wiring OctoPOPITsMounting OctoPOPITs Terminal Strip ConnectionsConnecting D8128D OctoPOPITs to the D9412GV3 Connecting D8128D OctoPOPITs to the D7412GV3 Wiring Multiple D8128Ds Using Molex Connectors Using Molex ConnectorsOctoPOPIT Sensor Loops Testing Off-Board Points10.1 D8129 OctoRelay Off-Board RelaysD8129 OctoRelay Switch Settings Configuring the D8129 OctoRelayRelay Outputs 10.2 D811 Arm Status Relay Module Wiring ConnectionsNumber of D8128Ds Used with D8129s D811 Module Wiring to the D9412GV3 D811 Module Wiring to the D7412GV3 Arming Devices Keypad Address SettingsDescription Keypad Terminals 29 toExtra Power for More Keypads Wire Limits for Individual DevicesD9412GV3 Keypad D7412GV3 Function Wire Terminal Color Keypad Connections11.3 D279A Independent Zone Control KeyswitchOperation Maintained Contact Silencing the Bell Momentary ContactSDI Devices Installation12.3 D9131A Parallel Printer Interface Module SDI Addresses 88 12.4 D9210B Wiegand Control Interface ModuleNetwork Interface Modules Address SettingsSupervision Programmer Connector Programmer and Accessory ConnectionsInstaller Keypad and Local Programmers Mode Programmer Access ReportsAccessory connector Programming connector Accessory Connector14.1 D9412GV3 Faceplate FaceplatesD7412GV3 Faceplate 14.2 D7412GV3 FaceplateD9412GV3 Control Panel Appendix a System Wiring Diagrams, Issue aD9412GV3 D9412GV3, SDI Devices System Wiring System Wiring D7412GV3 Control Panel D7412GV3, Power Supply Side System WiringD7412GV3 D7412GV3, SDI Devices System Wiring Zonex 1 Point Address Chart Appendix B Point Address ChartsZonex 2, Points 129 to 247 D9412GV3 Only Zonex 2 Point Address ChartPower Supply SpecificationsD9412GV3/D7412GV3 Operation and Installation Guide Notes Bosch Security Systems, Inc
Related manuals
Manual 154 pages 49.97 Kb

D9412GV3, D7412GV3 specifications

The Bosch Appliances D9412GV3 is a perfect blend of functionality and innovation, designed to meet the needs of modern households. This dishwasher is part of Bosch's reputation for creating high-quality, energy-efficient home appliances. With a sleek design and advanced technology, the D9412GV3 stands out in the crowded market of dishwashers.

One of the main features of the D9412GV3 is its remarkable efficiency. With an Energy Star rating, this model is designed to minimize water and energy consumption while still delivering exceptional cleaning performance. The EcoSense technology optimizes water usage, ensuring every wash cycle is both effective and economical, making it a responsible choice for energy-conscious consumers.

The dishwasher offers a spacious interior, capable of accommodating large loads. Its flexible rack system includes adjustable tines and folding platforms, making it easy to fit various dish sizes, from pots and pans to delicate glassware. Additionally, the third rack feature provides extra space for utensils and smaller items, enhancing its capacity and versatility.

In terms of cleaning power, the D9412GV3 is equipped with the PrecisionWash system. This cutting-edge technology features intelligent sensors that continuously scan and check the load, adjusting the wash cycle as needed for optimal results. Coupled with the 40 dBA noise level, it ensures that the dishwasher operates quietly in the background, so you can enjoy your home without disruptive sounds.

Another standout characteristic is the PureDry technology, an integrated drying system that uses a condensation process to gently dry dishes without the need for extra heat. This not only protects sensitive items but also saves energy, further enhancing the appliance's eco-friendly nature.

Ease of use is a priority for Bosch, as seen in the D9412GV3's user-friendly controls. The intuitive interface allows for selecting various wash cycles and options, including Heavy, Auto, and Quick options, catering to different cleaning needs. Additionally, the Time Delay feature provides the flexibility to set the dishwasher to run at a later time, great for aligning with your schedule.

In summary, the Bosch D9412GV3 combines innovative technologies with a user-centered design to deliver a top-tier dishwasher experience. Its energy-efficient operation, spacious interior, and advanced cleaning features make it an excellent choice for any kitchen, ensuring spotless dishes with minimal effort. With Bosch's commitment to quality, the D9412GV3 stands as a reliable and stylish addition to any modern home.