D9412GV3/D7412GV3 Operation and Installation Guide Specifications

Specifications

Table 26: Specifications

 

 

 

 

 

 

 

 

Voltage Input

 

Primary:

Terminals 1

16.5 VAC 40 VA class 2 plug-in transformer (D1640)

 

(Power

 

 

and 2

 

 

 

Supply)

 

Secondary:

Terminals 4

Sealed lead-acid rechargeable battery (12.0 VDC, 7 Ah or 12.0 VDC, 17.2 or 18

 

 

 

 

and 5

Ah). The control panel supports up to two 12.0 VDC, 7 Ah batteries using the

 

 

 

 

 

D122 Dual Battery Harness or two D1218 (12.0 VDC, 17.2 or 18 Ah) batteries

 

 

 

 

 

using a D122.

 

Current

 

Control Panel: Idle 225 mA; Alarm 300 mA

 

 

Requirements

 

Refer to the Current Rating Chart for Standby Battery Calculations section in the D9412GV3/D7412GV3 Approved

 

 

 

 

Applications Compliance Guide (P/N: F01U143069) for the current draw requirements of other system components.

 

 

Power

 

All external connections are power-limited except battery terminals.

 

Outputs*

 

 

 

 

 

 

 

Continuous

Terminals 3,

1.4 A maximum at 12.0 VDC nominal (continuous supply) total for all devices and

 

 

 

 

 

 

Power

24, and 32

outputs supplied at Terminals 3, 24, and 32 and at the accessory and

 

 

 

Outputs

 

programming connectors.

 

 

 

Alarm Power

Terminals 6

2.0 A maximum at 12.0 VDC nominal output. Output can be steady or one of

 

 

 

Output

and 7

three pulsed patterns depending on programming. Refer to Relays in the

 

 

 

 

 

D9412GV3/D7412GV3 Program Entry Guide (P/N: F01U170807).

 

 

 

Switched Aux

Terminal 8

1.4 A maximum at 12.0 VDC nominal output. Continuous output is interrupted by

 

 

 

Power

 

Sensor Reset or alarm verification depending on programming. Refer to Relays

 

 

 

 

 

in the D9412GV3/D7412GV3 Program Entry Guide (P/N: F01U170807).

 

 

 

Fire and

To comply with

UL 985 and 864 listing standards for fire alarm systems (effective March 1, 1989),

 

 

 

Fire/Burglary

the total combined continuous and alarm current draw for the system during alarm conditions must

 

 

 

Systems

be limited to 1.4 A provided by the primary power supply (rectified AC). If current draw for the

 

 

 

 

system exceeds 1.4 A, remove connected devices until the current draw falls below 1.4 A. Then,

 

 

 

 

connect the removed devices to a D8132 Battery Charger Module or to an external power supply

 

 

 

 

(refer to Figure 29 on page 58).

*For UL 864 applications, refer to Table 3 on page 11 for compatible devices.

Minimum

Operating

Voltage

SDI Bus

Telephone Connections

Battery

Discharge/

Recharge

Schedule

Environmental

Arming

Stations

Point

Thresholds

Compatible Enclosures

 

10.2 VDC

 

 

 

 

 

 

SDI Bus A (+):

 

9 VDC 4572 m (15000 ft) maximum

 

 

 

 

 

SDI Bus B (-):

 

9 VDC 4572 m (15000 ft) maximum

 

 

Connection:

 

RJ31X or RJ38X jack can connect the control panels.

 

 

Two Telco

 

Bosch Security Systems, Inc. D928 Dual Phone Line Module required for two phone line service.

 

 

lines:

 

Supervision supplied by the control panel.

 

 

Discharge

 

13.9 VDC

 

Charging float level.

 

 

Cycle

 

13.8 VDC

 

Charging status LED on.

 

 

 

 

 

12.1 VDC

 

Low Battery and AC Fail Reports if programmed. Low Battery LED on.

 

 

 

 

 

10.2 VDC

 

Minimum operational voltage

 

 

 

 

 

10.0 VDC

 

Battery load shed (processing functions continue if AC is present).

 

 

Recharge

 

AC ON

 

Load shed relay resets, battery charging begins, Battery Trouble and AC

 

 

Cycle

 

 

 

Restoral Reports sent.

 

 

 

 

 

13.7 VDC

 

Battery Restoral Report sent, Low Battery LED off.

 

 

 

 

 

13.9 VDC

 

Charging status LED off, battery float charged.

 

 

Temperature:

 

 

0°C to +50°C (+32°F to +122°F)

 

 

 

 

 

 

 

 

 

 

Relative

 

 

Maximum 93% non-condensing

 

 

Humidity:

 

 

 

 

 

 

 

D720/D720B Keypads, D1255/D1255B/D1255RB Keypads, D1256/D1256RB Fire Keypads; D1257/D1257RB Fire

 

 

Alarm Annunciators; D1260/D1260B Keypads; Keyswitch

 

 

On-board

 

 

Open

Greater than 3.7 VDC, but less than 5.0 VDC.

 

 

Points 1 to 8

 

 

Normal

Greater than 2.0 VDC, but less than 3.0 VDC.

 

 

 

 

 

Short

Greater than 0.0 VDC, but less than 1.3 VDC.

 

D8103 Universal Enclosure, D8109 Fire Enclosure, D8108A Attack Resistant Enclosure, BATB-40 Battery Box

Bosch Security Systems, Inc. 10/10 F01U143070-03

74

Image 74
Contents D9412GV3/D7412GV3 Listings and Approvals TrademarksCertifications and Approvals Federal Communications Commission FCC RulesRinger Equivalence 0.0B Service Center in USAFCC Registration Number Contents Appendix B Point Address Charts Programmer and Accessory ConnectionsAppendix a System Wiring Diagrams, Issue a Tables Introduction Related DocumentationEffects Precautions during InstallationLightning Strikes Overview Configuration and PartsFeatures D9412GV3 D7412GV3 GV3 Series Control Panel DifferencesLiterature Pack Parts ListAssembly Parts Available by Separate OrderModel Title Fire Intrusion AccessoriesCompatible Accessories1 Features in the D9412GV3 and D7412GV3 Ground Fault Detection KeyswitchAccess Control KeypadsEnclosure Options InstallationInstallation Preparation Mounting EnclosureGround Fault Detect Enable Installing the Control PanelConnecting Earth Ground TerminalGround Fault Impedance Specifications Enabling Ground Fault DetectionGround Fault Specifications Locking the Reset PinCompleting the Installation Programming the Control PanelService Walk Test Installing the Point Chart LabelTesting the System Service Walk Test ProcedureD9412GV3/D7412GV3 Operation and Installation Guide Text displays for 60 seconds Bosch Security Systems, Inc /10 F01U143070-03Test a device D7412GV3 Service Walk Test Flow Chart Secondary Power Terminals Power SupplyPrimary Power Terminals 1 Non-Power-Limited Wiring Investigate Low Battery reports immediately If Replacing the Battery Charging and Battery LEDsD8132 Boost Battery Backup Adding a D8132 Battery Charging CircuitDischarge Cycle Battery Discharge and Recharge ScheduleCharging Status and Low Battery LEDs Recharge CycleContinuous Power Output Terminals 3, 8, 24, Power OutputsTotal Available Power Circuit ProtectionA  NSC current = Alarm current Required Step Available Programmable Power Output Terminals 6, 7,Verification and Reset Relay Voltage Output at Terminals 6, 7,Notification Telephone ConnectionsRegistration LocationDialing Format Phone LED RedOperation Monitor LED Green Telephone Line Monitor11 D928 Dual Phone Line Switcher DescriptionPoint Sensor Loops On-Board PointsTerminals 11 to 22 Description Loop Voltage Range Point ParametersPoint Parameters Point Response Time 64 mm 1/4 Minimum distance Comm Off-Board Points Point Zonex Bus D9412GV3 Terminals and D7412GV3D8125 and D9127 Popit Modules Off-Board Point ErrorsError Condition Result Additional Information 5 D9412GV3/D7412GV3 Responses to Missing Point ConditionsConnecting the D8125 Popex to the D9412GV3 Control Panel Connecting the D8125 Popex to the D7412GV3 Control Panel Installing the D8125 Popex Module Popit Module Point Assignments Wiring Data Expansion Loops to Popex ModulesPopit Sensor Loops Program Record SheetD8128D OctoPOPIT Module Program Record Sheet Popit LabelsRequirements for Fire Initiation Applications D8128D OctoPOPIT LayoutAddress Switches InstallationSetting the OctoPOPIT Switches D8128D OctoPOPIT Switch Settings for D9412GV3 and D7412GV3Mounting OctoPOPITs Wiring OctoPOPITsUsing the Terminal Strip Terminal Strip ConnectionsConnecting D8128D OctoPOPITs to the D9412GV3 Connecting D8128D OctoPOPITs to the D7412GV3 Using Molex Connectors Wiring Multiple D8128Ds Using Molex ConnectorsTesting Off-Board Points OctoPOPIT Sensor LoopsOff-Board Relays 10.1 D8129 OctoRelayRelay Outputs Configuring the D8129 OctoRelayD8129 OctoRelay Switch Settings Number of D8128Ds Used with D8129s Wiring Connections10.2 D811 Arm Status Relay Module D811 Module Wiring to the D9412GV3 D811 Module Wiring to the D7412GV3 Description Keypad Address SettingsArming Devices Keypad Terminals 29 toD9412GV3 Keypad D7412GV3 Function Wire Terminal Color Wire Limits for Individual DevicesExtra Power for More Keypads Keypad ConnectionsOperation Maintained Contact Keyswitch11.3 D279A Independent Zone Control Momentary Contact Silencing the Bell12.3 D9131A Parallel Printer Interface Module InstallationSDI Devices 12.4 D9210B Wiegand Control Interface Module SDI Addresses 88Supervision Address SettingsNetwork Interface Modules Installer Keypad and Local Programmers Mode Programmer and Accessory ConnectionsProgrammer Connector Programmer Access ReportsAccessory Connector Accessory connector Programming connectorFaceplates 14.1 D9412GV3 Faceplate14.2 D7412GV3 Faceplate D7412GV3 FaceplateAppendix a System Wiring Diagrams, Issue a D9412GV3 Control PanelD9412GV3 D9412GV3, SDI Devices System Wiring System Wiring D7412GV3, Power Supply Side System Wiring D7412GV3 Control PanelD7412GV3 D7412GV3, SDI Devices System Wiring Appendix B Point Address Charts Zonex 1 Point Address ChartZonex 2 Point Address Chart Zonex 2, Points 129 to 247 D9412GV3 OnlySpecifications Power SupplyD9412GV3/D7412GV3 Operation and Installation Guide Notes Bosch Security Systems, Inc