D9412GV3/D7412GV3 Operation and Installation Guide

8.0

On-Board Points

 

 

 

8.4Point Response Time

The control panel scans on-board and off-board point sensor loops every 300 ms. The Debounce program item in the Point Assignment section of the software determines point response time by setting the number of times the control panel scans a point before generating an alarm.

The debounce count can range from 2 to 15; therefore, point response time ranges from 600 ms to

4.5sec. The Bosch Security Systems, Inc. default for debounce count is 2.

Increasing debounce might cause missed alarms. If you increase the debounce count, detection devices can enter alarm and reset without exceeding the point response time.

Use a debounce count of 2 for all points except:

Use 3 for Interior Follower points.

Use 4 for door points connected to a D9210B Access Control Interface Module.

8.5Wiring Information for Installations Using the Rothenbuhler 5110/4001-42 High Security Bell

Warning: Wear ear protection when installing and testing the Rothenbuhler High Security Bell.

Sound levels greater than 95 dBA at 3 m (10 ft) can occur.

1.Remove all power from the control panel.

2.Use six-conductor 1.2 mm (18 AWG) shielded stranded wire between the control panel and the 5110 Logic Board (located in the bell enclosure).

3.If you do not have a Silence switch, temporarily install a 1  resistor across TB1-1 and TB1-6 on the 5110 Logic Board. The resistor keeps the 5110’s bell silent during the installation and alignment procedures. Also place a temporary wire jumper across the TB1-6 Bell Relay and TB1-7. Refer to Figure 15 on page 35 for wiring a Silence switch.

4.Mount the D8108A’s 4001-42 External Balanced Line Module and wire it to the 5110 Logic Board using two-conductor 0.8 mm (22 AWG) cable.

5.Wire the 4001-42 to the control panel. Refer to Figure 15 on page 35 and the Rothenbuhler installation manual.

6.Before supplying AC and DC power to the control panel and bell, ensure you are wearing ear protection. The bell sounds for 2 sec and then silences during power up.

For additional information about bell requirements, refer to Bank Safe and Vault Applications in the D9412GV3/D7412GV3 Approved Applications and Compliance Guide (P/N: F01U143069).

Bosch Security Systems, Inc. 10/10 F01U143070-03

33

Image 33
Contents D9412GV3/D7412GV3 Certifications and Approvals TrademarksListings and Approvals Federal Communications Commission FCC RulesService Center in USA FCC Registration NumberRinger Equivalence 0.0B Contents Programmer and Accessory Connections Appendix a System Wiring Diagrams, Issue aAppendix B Point Address Charts Tables Related Documentation IntroductionPrecautions during Installation Lightning StrikesEffects Features D9412GV3 D7412GV3 Configuration and PartsOverview GV3 Series Control Panel DifferencesAssembly Parts ListLiterature Pack Parts Available by Separate OrderAccessories Compatible Accessories1Model Title Fire Intrusion Features in the D9412GV3 and D7412GV3 Access Control KeyswitchGround Fault Detection KeypadsInstallation Preparation InstallationEnclosure Options Mounting EnclosureConnecting Earth Ground Installing the Control PanelGround Fault Detect Enable TerminalGround Fault Specifications Enabling Ground Fault DetectionGround Fault Impedance Specifications Locking the Reset PinProgramming the Control Panel Completing the InstallationTesting the System Installing the Point Chart LabelService Walk Test Service Walk Test ProcedureD9412GV3/D7412GV3 Operation and Installation Guide Bosch Security Systems, Inc /10 F01U143070-03 Test a deviceText displays for 60 seconds D7412GV3 Service Walk Test Flow Chart Power Supply Primary Power Terminals 1Secondary Power Terminals Non-Power-Limited Wiring D8132 Boost Battery Backup Adding a D8132 Replacing the Battery Charging and Battery LEDsInvestigate Low Battery reports immediately If Battery Charging CircuitCharging Status and Low Battery LEDs Battery Discharge and Recharge ScheduleDischarge Cycle Recharge CycleTotal Available Power Power OutputsContinuous Power Output Terminals 3, 8, 24, Circuit ProtectionVerification and Reset Relay Programmable Power Output Terminals 6, 7,A  NSC current = Alarm current Required Step Available Voltage Output at Terminals 6, 7,Registration Telephone ConnectionsNotification LocationOperation Monitor LED Green Phone LED RedDialing Format Telephone Line Monitor Description 11 D928 Dual Phone Line SwitcherOn-Board Points Terminals 11 to 22 DescriptionPoint Sensor Loops Point Parameters Point ParametersLoop Voltage Range Point Response Time 64 mm 1/4 Minimum distance Comm Point Zonex Bus D9412GV3 Terminals and D7412GV3 Off-Board PointsError Condition Result Additional Information Off-Board Point ErrorsD8125 and D9127 Popit Modules 5 D9412GV3/D7412GV3 Responses to Missing Point ConditionsConnecting the D8125 Popex to the D9412GV3 Control Panel Connecting the D8125 Popex to the D7412GV3 Control Panel Installing the D8125 Popex Module Popit Sensor Loops Wiring Data Expansion Loops to Popex ModulesPopit Module Point Assignments Program Record SheetProgram Record Sheet Popit Labels D8128D OctoPOPIT ModuleD8128D OctoPOPIT Layout Requirements for Fire Initiation ApplicationsSetting the OctoPOPIT Switches InstallationAddress Switches D8128D OctoPOPIT Switch Settings for D9412GV3 and D7412GV3Using the Terminal Strip Wiring OctoPOPITsMounting OctoPOPITs Terminal Strip ConnectionsConnecting D8128D OctoPOPITs to the D9412GV3 Connecting D8128D OctoPOPITs to the D7412GV3 Wiring Multiple D8128Ds Using Molex Connectors Using Molex ConnectorsOctoPOPIT Sensor Loops Testing Off-Board Points10.1 D8129 OctoRelay Off-Board RelaysConfiguring the D8129 OctoRelay D8129 OctoRelay Switch SettingsRelay Outputs Wiring Connections 10.2 D811 Arm Status Relay ModuleNumber of D8128Ds Used with D8129s D811 Module Wiring to the D9412GV3 D811 Module Wiring to the D7412GV3 Arming Devices Keypad Address SettingsDescription Keypad Terminals 29 toExtra Power for More Keypads Wire Limits for Individual DevicesD9412GV3 Keypad D7412GV3 Function Wire Terminal Color Keypad ConnectionsKeyswitch 11.3 D279A Independent Zone ControlOperation Maintained Contact Silencing the Bell Momentary ContactInstallation SDI Devices12.3 D9131A Parallel Printer Interface Module SDI Addresses 88 12.4 D9210B Wiegand Control Interface ModuleAddress Settings Network Interface ModulesSupervision Programmer Connector Programmer and Accessory ConnectionsInstaller Keypad and Local Programmers Mode Programmer Access ReportsAccessory connector Programming connector Accessory Connector14.1 D9412GV3 Faceplate FaceplatesD7412GV3 Faceplate 14.2 D7412GV3 FaceplateD9412GV3 Control Panel Appendix a System Wiring Diagrams, Issue aD9412GV3 D9412GV3, SDI Devices System Wiring System Wiring D7412GV3 Control Panel D7412GV3, Power Supply Side System WiringD7412GV3 D7412GV3, SDI Devices System Wiring Zonex 1 Point Address Chart Appendix B Point Address ChartsZonex 2, Points 129 to 247 D9412GV3 Only Zonex 2 Point Address ChartPower Supply SpecificationsD9412GV3/D7412GV3 Operation and Installation Guide Notes Bosch Security Systems, Inc