Barnett Engineering ARU CV2 instruction manual On/Off Output, Timed Output, Points section

Page 19

Configuration using the PC

3-5

Analog Input

Setting the input port type to Analog allows measurement of voltages between 0 and

+5 volts. As with the other input types, the definition of an analog input is completed in the Points section where the range, setpoints and units are assigned.

An Analog port can be changed to one of the other input types by selecting from the Change Input Port drop-down list. Changing input type will force any variables used in the Hardware section to the default value and will remove any points that make use of this input.

On/Off Output

On/Off outputs operate with two DTMF codes that are set in the Points section. One code turns the output On and the other returns it to the Off state. The output will remain in the last commanded state indefinitely.

To make an On/Off port operational for remote control or as one of the special functions -- Alarm Active or New Alarm -- it must be configured and enabled in the Points section.

Timed Output

Timed outputs are activated by receipt of a single DTMF ‘On’ code. This code is set in the Points section. When the code is received, the output will activate and will remain in that state until the timer expires or the DTMF ‘Off’ code is received.

Two timer ranges, seconds and minutes, are available. The seconds range has a maximum value of 1638 seconds (27 minutes) with a resolution of 25 msec. For longer times the minutes range should be used. When set to minutes, the timer has a maximum value of 65,535 minutes with a resolution of one minute. For short times use the seconds timer to avoid the inaccuracy introduced by the one minute resolution.

When the command to turn on the Timed output has been received and executed, the Cv2 will announce the current state of the output port. If the timer value is set to a short interval, it is possible that the output will have returned to the Off state by the time the status is announced.

To make a Timed port operational for remote control or as one of the special functions -- Alarm Active, New Alarm or Acknowledge Received - it must be configured and enabled in the Points section.

3.5.2 Points section

After the Hardware ports are configured, use the Points section to specify how activities on these ports are processed. There are 30 points available for use as either input or output controls. It is in the Points section that inputs are given the ability to generate alarms and outputs are enabled to perform remote control functions. Each point can be referenced to any of the input or output ports. When a port is selected in Points it will have the characteristics that were set in the Hardware section. If a different type of operation is required for a port, it must be changed in the Hardware section.

B1272M001

BARNETT ENGINEERING LTD.

ProTalk Cv2

Image 19
Contents 1272M001 3UR7DONContents Cv2 Capabilities What constitutes an alarm?Way in which the Cv2 processes alarms is shown in Figure How are alarms processed?What actions should occur when an alarm is detected? How do you want to respond to an alarm call? What do you want the Cv2 to do when you call it? What if an alarm is not acknowledged?Sending remote control commands Troubleshooting IndicatorsAre the inputs connected properly? Mounting Antenna requirementsPackaged model Input port connections Ground closure alarm signalStand-alone model 3 +5 volt alarm signal 2 +12 volt alarm signalAnalog input Output port connections Configuration programming connectionStand-alone Cv2 PC requirements Installing the programStarting the configuration program Desktop and how to access programming functionsGroups File OperationsHardware GeneralHardware section Configuring the Cv2Directories ProgrammingInterval Input Watchdog InputTotalizer Input Timed Output On/Off OutputPoints section Using Group Common Settings for Points Port SelectionPoint Name Dtmf Tag EnabledAlarm State Digital and Watchdog PointsUnits Clear CodeAnalog Point Binary Values CalibrateDecimal Values On/Off Output Point HysteresisDtmf On Code Timed Output Point Dtmf Off CodeGroup section Acknowledge Code Enable This GroupEnable Auto Ack Group NameLong Timer Enable Ack RequestTimers Short TimerAcknowledge Received Alarm ActiveNew Alarm Special Function OutputsWait DialAnswer Auto AckAlert VoiceSite Name SignalAccess Code DeleteTemporary Acknowledge Time Shift Change CodeCall Progress Voice Messages Configuration DataVocabulary Access SetupCommands Dial Cv2 Site ID is Ajax Compressor Station Cv2 Electrical on or Electrical OFF Telset Programming Summary Exit Record Points Query NAM Programmable Features SpecificationsOptions TelephoneWarranty