Barnett Engineering ARU CV2 instruction manual Dtmf Off Code, Timed Output Point, Group section

Page 25

Configuration using the PC

3-11

DTMF Off Code

When the Cv2 receives the DTMF Off code, it sets the output port to the Off state. After the Off code has been received and the output port cleared, the Cv2 announces the current status of the output.

This code can be 1 to 7 digits in length and may use any of the 16 DTMF digits including A, B, C, and D.

Default DTMF Off Code: an empty string - no Off Code.

Timed Output Point

In addition to the common settings, there are two DTMF control codes used with an Timed output point.

DTMF On Code

When the Cv2 receives the DTMF On code, it sets the output port to the On state and the timer begins operation. After the On code has been received and the output port set, the Cv2 announces the current status of the output. If the timer is set for a short interval, the output port may have returned to the Off state before the announcement is made.

This code can be 1 to 7 digits in length and may use any of the 16 DTMF digits including A, B, C, and D.

Default DTMF On Code: an empty string - no On Code.

DTMF Off Code

When the Cv2 receives the DTMF Off code it sets the output port to the Off state and terminates the timer operation if it is currently running. The DTMF Off code will have no effect if the output timer has already expired. After the Off code has been received and the output port cleared, the Cv2 announces the current status of the output.

This code can be 1 to 7 digits in length and may use any of the 16 DTMF digits.

Default DTMF Off Code: an empty string - no Off Code.

3.5.3 Group section

In some applications, there may be a requirement for different types of alarms to alert different people. This is handled in the Cv2 by assigning alarms to different groups; there are six groups available for this purpose. Each alarm point has a selection list for setting the Using Group parameter. In the group dialog, the directory that it will be using is selected in the Shift control section. If the group activities are not going to be altered by changing shifts, use the shift 1 selection for all groups. If the use of directories by a group is going to change through the Shift Control, enter the appropriate directory into the shift selections.

Each Group has its own Acknowledge Code, Interrogate Code and Timer settings. Activities for a particular group are performed according to the Shift that is selected. Each shift uses one of the directories as the instruction source for the sequence of actions that occur during alarm

B1272M001

BARNETT ENGINEERING LTD.

ProTalk Cv2

Image 25
Contents 1272M001 3UR7DONContents Cv2 Capabilities What constitutes an alarm?Way in which the Cv2 processes alarms is shown in Figure How are alarms processed?What actions should occur when an alarm is detected? How do you want to respond to an alarm call? What do you want the Cv2 to do when you call it? What if an alarm is not acknowledged?Sending remote control commands Troubleshooting IndicatorsAre the inputs connected properly? Mounting Antenna requirementsPackaged model Input port connections Ground closure alarm signalStand-alone model 3 +5 volt alarm signal 2 +12 volt alarm signalAnalog input Output port connections Configuration programming connectionStand-alone Cv2 Starting the configuration program Installing the programDesktop and how to access programming functions PC requirementsHardware File OperationsGeneral GroupsDirectories Configuring the Cv2Programming Hardware sectionInterval Input Watchdog InputTotalizer Input Timed Output On/Off OutputPoints section Using Group Common Settings for Points Port SelectionPoint Name Alarm State EnabledDigital and Watchdog Points Dtmf TagUnits Clear CodeAnalog Point Binary Values CalibrateDecimal Values On/Off Output Point HysteresisDtmf On Code Timed Output Point Dtmf Off CodeGroup section Enable Auto Ack Enable This GroupGroup Name Acknowledge CodeTimers Enable Ack RequestShort Timer Long TimerNew Alarm Alarm ActiveSpecial Function Outputs Acknowledge ReceivedWait DialAlert Auto AckVoice AnswerAccess Code SignalDelete Site NameTemporary Acknowledge Time Shift Change CodeCall Progress Voice Messages Configuration DataVocabulary Access SetupCommands Dial Cv2 Site ID is Ajax Compressor Station Cv2 Electrical on or Electrical OFF Telset Programming Summary Exit Record Points Query NAM Programmable Features SpecificationsOptions TelephoneWarranty