Barnett Engineering ARU CV2 instruction manual Setup, Access, Commands

Page 34

Voice Storage and Configuration with the Telset

4-1

4 Voice Storage and Configuration with the Telset

4.1 Setup

After the configuration database has been transferred to the Cv2, it is ready to accept the voice messages that will be used in the alarm reporting process and it is possible to change some of the configuration data that was transferred from the PC. First ensure a database has been downloaded from the PC to the Cv2. The Cv2 must contain a valid database in order to determine which points have associated voice messages.

The usual method for voice programming is with a phone set plugged directly into the unit; however it is also possible to program voice messages remotely by calling the Cv2 over the phone network.

If you are programming a stand-alone Cv2, a DTMF (TouchTone) telephone set is required to enter the voice messages. A rotary dial pulse telephone set will not work here. Connect the phone set to port J1. If you have a package model, the phone set will already be in the enclosure.

In place of the Enter key or carriage return which you would use to enter data from a keyboard, the Cv2 interprets the characters UU as the Enter command. The programming sequence is controlled by pressing a single digit followed by the UU digits. Ensure that no more than one second separates the two U digits.

4.2 Access

To begin a local programming session, lift the telephone handset to your ear. To perform remote programming call the site from a remote telephone set.

The Cv2 has stored voice prompts to guide you through the programming mode. The first message you will hear is “Enter Command Code.” At this time you can interrogate, acknowledge or control the unit. If the Access Code is entered, the prompt changes to “Enter Program Code” and all LEDs illuminate. The same action occurs if you are calling in remotely.

With the security level set to ‘1' with local programming, the Cv2 will advance to the program mode automatically after 5 seconds if an access code is not entered. An access code is needed for remote programming with all security level settings and locally for levels 2 and 3.

4.3 Commands

After the security requirements have been met, you can begin programming voices or changing the configuration by entering a command code. Each code produces a response from the Cv2 as described below:

0UU - Edit Directories

Cv2: “Enter Directory Code”

After the Cv2 responds with this prompt it waits for you to enter a selection from the

B1272M001

BARNETT ENGINEERING LTD.

ProTalk Cv2

Image 34
Contents 3UR7DON 1272M001Contents What constitutes an alarm? Cv2 CapabilitiesHow are alarms processed? Way in which the Cv2 processes alarms is shown in FigureWhat actions should occur when an alarm is detected? How do you want to respond to an alarm call? What do you want the Cv2 to do when you call it? What if an alarm is not acknowledged?Sending remote control commands Indicators TroubleshootingAre the inputs connected properly? Mounting Antenna requirementsPackaged model Input port connections Ground closure alarm signalStand-alone model 3 +5 volt alarm signal 2 +12 volt alarm signalAnalog input Configuration programming connection Output port connectionsStand-alone Cv2 Desktop and how to access programming functions Installing the programStarting the configuration program PC requirementsGeneral File OperationsHardware GroupsProgramming Configuring the Cv2Directories Hardware sectionInterval Input Watchdog InputTotalizer Input Timed Output On/Off OutputPoints section Using Group Common Settings for Points Port SelectionPoint Name Digital and Watchdog Points EnabledAlarm State Dtmf TagUnits Clear CodeAnalog Point Binary Values CalibrateDecimal Values On/Off Output Point HysteresisDtmf On Code Timed Output Point Dtmf Off CodeGroup section Group Name Enable This GroupEnable Auto Ack Acknowledge CodeShort Timer Enable Ack RequestTimers Long TimerSpecial Function Outputs Alarm ActiveNew Alarm Acknowledge ReceivedDial WaitVoice Auto AckAlert AnswerDelete SignalAccess Code Site NameTemporary Acknowledge Time Shift Change CodeCall Progress Voice Messages Configuration DataVocabulary Access SetupCommands Dial Cv2 Site ID is Ajax Compressor Station Cv2 Electrical on or Electrical OFF Telset Programming Summary Exit Record Points Query NAM Specifications Programmable FeaturesTelephone OptionsWarranty