Barnett Engineering ARU CV2 instruction manual Watchdog Input, Interval Input, Totalizer Input

Page 18

Configuration using the PC

3-4

debounce times, use the seconds timer to avoid the inaccuracy introduced by the one minute resolution.

Default Debounce time: 0.05 sec

A Digital input port can also be used to perform special functions in the Cv2. In the Groups section, it can be selected for the Local Acknowledge function, and in the Hardware section it can be set to operate as a Reset Input for a Totalizer.

Watchdog Input

A Watchdog timer is used to monitor periodic events and will produce an alarm if the event does not occur within the programmed Watchdog interval. Each time an event occurs at the input, the timer is reloaded with the programmed value. When the timer has expired without a refresh event, the alarm is set. Refresh activities can be changes from low to high, changes from high to low, or both.

Watchdog input types use two timers for their operation: the Debounce timer and the Watchdog Interval timer. Refer to the preceding Digital input description for details on the Debounce timer. Two Watchdog time ranges, seconds and minutes, are available. The seconds range has a maximum value of 1638 seconds (27 minutes) with a resolution of 25 msec. For longer Watchdog times the minutes range should be used. When set to minutes, the Watchdog timer has a maximum value of 65,535 minutes with a resolution of one minute. For short Watchdog times, use the seconds timer to avoid the inaccuracy introduced by the one minute resolution. When setting the two timers, take into consideration the relationship between the two. The Debounce time can not be greater than the Watchdog Interval; otherwise a constant alarm condition will occur.

Default Watchdog time: 10 min

Interval Input

Interval timers measure the time interval that an input is active, either how long it is high or how long it is low. The input is conditioned by the Debounce timer which is described in the Digital input section. When setting the Debounce timer, consider the anticipated duration of the interval. Since the Cv2 registers a change only after the Debounce time, long debounce settings will affect the accuracy of the measurement.

Totalizer Input

Totalizer inputs measure the number of times that an event has occurred at the input. The event can be a high to low transition, a low to high transition, or both. Before the change is considered valid, it is conditioned by the Debounce timer - described in the Digital input section. Take into consideration the expected time period between events when setting the Debounce timer.

The count in the totalizer can be reset by two methods: by sending the Reset Code entered in the Points section, or by using the Reset Input selection in the Hardware setup.

B1272M001

BARNETT ENGINEERING LTD.

ProTalk Cv2

Image 18
Contents 3UR7DON 1272M001Contents What constitutes an alarm? Cv2 CapabilitiesHow are alarms processed? Way in which the Cv2 processes alarms is shown in FigureWhat actions should occur when an alarm is detected? How do you want to respond to an alarm call? What if an alarm is not acknowledged? What do you want the Cv2 to do when you call it?Sending remote control commands Indicators TroubleshootingAre the inputs connected properly? Antenna requirements MountingPackaged model Ground closure alarm signal Input port connectionsStand-alone model 2 +12 volt alarm signal 3 +5 volt alarm signalAnalog input Configuration programming connection Output port connectionsStand-alone Cv2 Desktop and how to access programming functions Installing the programStarting the configuration program PC requirementsGeneral File OperationsHardware GroupsProgramming Configuring the Cv2Directories Hardware sectionWatchdog Input Interval InputTotalizer Input On/Off Output Timed OutputPoints section Common Settings for Points Port Selection Using GroupPoint Name Digital and Watchdog Points EnabledAlarm State Dtmf TagClear Code UnitsAnalog Point Calibrate Binary ValuesDecimal Values Hysteresis On/Off Output PointDtmf On Code Dtmf Off Code Timed Output PointGroup section Group Name Enable This GroupEnable Auto Ack Acknowledge CodeShort Timer Enable Ack RequestTimers Long TimerSpecial Function Outputs Alarm ActiveNew Alarm Acknowledge ReceivedDial WaitVoice Auto AckAlert AnswerDelete SignalAccess Code Site NameShift Change Code Temporary Acknowledge TimeCall Progress Configuration Data Voice MessagesVocabulary Setup AccessCommands Dial Cv2 Site ID is Ajax Compressor Station Cv2 Electrical on or Electrical OFF Telset Programming Summary Exit Record Points Query NAM Specifications Programmable FeaturesTelephone OptionsWarranty