Barnett Engineering ARU CV2 instruction manual Are the inputs connected properly?

Page 9

Operations Overview

1-7

Are the inputs connected properly?

For digital inputs that are programmed for standard digital operation, create an alarm condition on the input and confirm that the Alarm LED comes on. Make sure the input is applied long enough for the debounce to time out. If the Alarm indicator does not come on, the problem is not necessarily with the input connection. Check that the input is enabled as a valid point, the associated group is enabled, and the directory is programmed to call out..

For analog inputs, interrogate their group to hear the scaled value at the input.

The unit does not dial out.

Check the Alarm LED to confirm that an alarm is present. If this indicator is not flashing, the Cv2 will not call out. Check that the input is enabled as a valid point, the associated group is enabled, and the directory is programmed to call out.

I cannot call into the unit.

If you receive a recording from the telephone company indicating the user is not available, there may be a problem with the installation or you may be calling the wrong number. Use the programming phone to confirm the telephone number in the unit.

B1272M001

BARNETT ENGINEERING LTD.

ProTalk Cv2

Image 9
Contents 1272M001 3UR7DONContents Cv2 Capabilities What constitutes an alarm?Way in which the Cv2 processes alarms is shown in Figure How are alarms processed?What actions should occur when an alarm is detected? How do you want to respond to an alarm call? What if an alarm is not acknowledged? What do you want the Cv2 to do when you call it?Sending remote control commands Troubleshooting IndicatorsAre the inputs connected properly? Antenna requirements MountingPackaged model Ground closure alarm signal Input port connectionsStand-alone model 2 +12 volt alarm signal 3 +5 volt alarm signalAnalog input Output port connections Configuration programming connectionStand-alone Cv2 Starting the configuration program Installing the programDesktop and how to access programming functions PC requirementsHardware File OperationsGeneral GroupsDirectories Configuring the Cv2Programming Hardware sectionWatchdog Input Interval InputTotalizer Input On/Off Output Timed OutputPoints section Common Settings for Points Port Selection Using GroupPoint Name Alarm State EnabledDigital and Watchdog Points Dtmf TagClear Code UnitsAnalog Point Calibrate Binary ValuesDecimal Values Hysteresis On/Off Output PointDtmf On Code Dtmf Off Code Timed Output PointGroup section Enable Auto Ack Enable This GroupGroup Name Acknowledge CodeTimers Enable Ack RequestShort Timer Long TimerNew Alarm Alarm ActiveSpecial Function Outputs Acknowledge ReceivedWait DialAlert Auto AckVoice AnswerAccess Code SignalDelete Site NameShift Change Code Temporary Acknowledge TimeCall Progress Configuration Data Voice MessagesVocabulary Setup AccessCommands Dial Cv2 Site ID is Ajax Compressor Station Cv2 Electrical on or Electrical OFF Telset Programming Summary Exit Record Points Query NAM Programmable Features SpecificationsOptions TelephoneWarranty