Barnett Engineering ARU CV2 instruction manual How do you want to respond to an alarm call?

Page 6

Operations Overview

1-4

For example, to call four telephone numbers, the directory would appear as:

1.[DIAL]2458829 [VOICE]

2.[DIAL]2336700 [VOICE]

3.[DIAL]9842121 [VOICE]

4.[DIAL]9843316 [VOICE]

If you want an alert tone to precede the voice message the directory line would look like this:

1.[DIAL]2458829 [ALERT] [VOICE]

The next example shows a sequence that is used to call a numeric paging terminal. After the call is placed there is a four second delay for the paging terminal to respond before the Cv2 sends the number to be displayed on the pager. When calling a paging terminal, it is sometimes useful to allow the called party time to call the Cv2 back and acknowledge the alarm before the Cv2 advances to the next line in the directory. This can be done by using the Wait command on its own line; the entry below will cause a four minute delay before the next line is executed.

1.[DIAL]2458829 [WAIT]4 [DTMF]4567

2.[WAIT]240

Directory lines can be added, removed, or modified and new lines can be inserted between existing lines.

1.5 How do you want to respond to an alarm call?

After the Cv2 has finished speaking the alarm messages, it prompts the called party with the phrase “Enter Acknowledge Code” and then waits five seconds for the code to be returned. If the code is received, it will terminate any further callout activities until a new alarm occurs; otherwise, it will proceed to the next line in the directory. There is a Temporary Acknowledge Time that can be set in the General section that will override the operation of the Acknowledge Code. If the temporary time is set to a value other than Off, and the received Acknowledge Code has the digit # appended to it, the Cv2 will remain in the acknowledged state only for this time interval. After the timer has expired and if the alarm condition still exists, the Cv2 will resume alarm reporting. This feature is used as a safety measure to ensure that an alarm cannot be acknowledged and then left unattended.

Each group has its own Acknowledge Code which only affects points that have been assigned to the group. Other groups with different Acknowledge Codes will continue alarm reporting if they do not receive their own code.

Using the Auto Ack command in a directory will cause the Cv2 to automatically acknowledge any alarms that are in the group using the directory. This feature must also be enabled for that group, since other groups of points may be using the same directory. Auto Ack must be on the last line in a directory since any further commands will never be executed.

Another method of acknowledging the Cv2 is by activating the special function that allows hardware inputs to be used as local acknowledge controls.

B1272M001

BARNETT ENGINEERING LTD.

ProTalk Cv2

Image 6
Contents 3UR7DON 1272M001Contents What constitutes an alarm? Cv2 CapabilitiesHow are alarms processed? Way in which the Cv2 processes alarms is shown in FigureWhat actions should occur when an alarm is detected? How do you want to respond to an alarm call? What if an alarm is not acknowledged? What do you want the Cv2 to do when you call it?Sending remote control commands Indicators TroubleshootingAre the inputs connected properly? Antenna requirements MountingPackaged model Ground closure alarm signal Input port connectionsStand-alone model 2 +12 volt alarm signal 3 +5 volt alarm signalAnalog input Configuration programming connection Output port connectionsStand-alone Cv2 Desktop and how to access programming functions Installing the programStarting the configuration program PC requirementsGeneral File OperationsHardware GroupsProgramming Configuring the Cv2Directories Hardware sectionWatchdog Input Interval InputTotalizer Input On/Off Output Timed OutputPoints section Common Settings for Points Port Selection Using GroupPoint Name Digital and Watchdog Points EnabledAlarm State Dtmf TagClear Code UnitsAnalog Point Calibrate Binary ValuesDecimal Values Hysteresis On/Off Output PointDtmf On Code Dtmf Off Code Timed Output PointGroup section Group Name Enable This GroupEnable Auto Ack Acknowledge CodeShort Timer Enable Ack RequestTimers Long TimerSpecial Function Outputs Alarm ActiveNew Alarm Acknowledge ReceivedDial WaitVoice Auto AckAlert AnswerDelete SignalAccess Code Site NameShift Change Code Temporary Acknowledge TimeCall Progress Configuration Data Voice MessagesVocabulary Setup AccessCommands Dial Cv2 Site ID is Ajax Compressor Station Cv2 Electrical on or Electrical OFF Telset Programming Summary Exit Record Points Query NAM Specifications Programmable FeaturesTelephone OptionsWarranty