Barnett Engineering ARU CV2 instruction manual Specifications, Programmable Features

Page 42

Specifications

6-1

5 Specifications

5.1 General

 

Alarm Inputs

• 8 inputs: analog or digital, latching or momentary; plug in

 

screw terminal block.

 

• analog: 0 to 5 VDC, 100k input impedance

 

• digital: normally open or normally closed, ground closure

 

or +10 to +30 VDC input; optionally configured for

 

acknowledge input.

Control Outputs

• 8 independent open collector outputs controlled by

 

DTMF codes; voice announcement when operated; plug

 

in screw terminal block; optionally configured for alarm

 

status indication. Rated 0.4 A, 50 volts max.

Programming Connection

• DB9 - RS232, 9600 baud

Record Connection

• RJ11, using standard telephone set

Voice Quality

• Digitized, toll quality, 32 kbps ADPCM

Power

• +11 to +28 VDC, 125 mA idle, 1.2 A transmitting; plug

 

in screw terminal block

Environment

-20oC to +50oC

Physical

• 8.5"L x 6.0"W x 3.0"D

Cellular Telephone

• Internal

RF Output Power

• Approx. 3.0 watts, maximum (class 1)

Sensitivity

-116 dBm for 12 dB SINAD

Antenna Impedance

• 50 ohms

5.2 Programmable Features

 

Voice Messages

• Site identification, Group identification, Alarm inputs,

 

and control outputs; 60 seconds maximum, non-volatile

Alarm Type

• Individually configured for digital normally open, digital

 

normally closed, or analog 0-5 V

Analog Alarm Range

-999.9 to +999.9

B1272M001

BARNETT ENGINEERING LTD.

ProTalk Cv2

Image 42
Contents 3UR7DON 1272M001Contents What constitutes an alarm? Cv2 CapabilitiesHow are alarms processed? Way in which the Cv2 processes alarms is shown in FigureWhat actions should occur when an alarm is detected? How do you want to respond to an alarm call? What if an alarm is not acknowledged? What do you want the Cv2 to do when you call it?Sending remote control commands Indicators TroubleshootingAre the inputs connected properly? Antenna requirements MountingPackaged model Ground closure alarm signal Input port connectionsStand-alone model 2 +12 volt alarm signal 3 +5 volt alarm signalAnalog input Configuration programming connection Output port connectionsStand-alone Cv2 Desktop and how to access programming functions Installing the programStarting the configuration program PC requirementsGeneral File OperationsHardware GroupsProgramming Configuring the Cv2Directories Hardware sectionWatchdog Input Interval InputTotalizer Input On/Off Output Timed OutputPoints section Common Settings for Points Port Selection Using GroupPoint Name Digital and Watchdog Points EnabledAlarm State Dtmf TagClear Code UnitsAnalog Point Calibrate Binary ValuesDecimal Values Hysteresis On/Off Output PointDtmf On Code Dtmf Off Code Timed Output PointGroup section Group Name Enable This GroupEnable Auto Ack Acknowledge CodeShort Timer Enable Ack RequestTimers Long TimerSpecial Function Outputs Alarm ActiveNew Alarm Acknowledge ReceivedDial WaitVoice Auto AckAlert AnswerDelete SignalAccess Code Site NameShift Change Code Temporary Acknowledge TimeCall Progress Configuration Data Voice MessagesVocabulary Setup AccessCommands Dial Cv2 Site ID is Ajax Compressor Station Cv2 Electrical on or Electrical OFF Telset Programming Summary Exit Record Points Query NAM Specifications Programmable FeaturesTelephone OptionsWarranty